| Plan Review Stops For Permit 16100154 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2017-01-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-01-19 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-01-18 |
Time |
18:32 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2016-12-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-12-06 |
Time |
19:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-12-06 |
Time |
17:00 |
Sent To |
|
|
| Notes |
| 2016-12-06 19:03:11 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) ON SHEETS A-3 AND A-4 THERE ARE ID TAGS FOR ROOF TO | | | WALL CONNECTORS MARKED 1/A4 AND 2/A4, HOWEVER, THERE | | | ARE NO CORRESPONDING DETAILS FOR THEM ON SHEET A-4. | | | PLEASE CLARIFY. FBC 107.2.1 | | | | | | 2) THE ENERGY FORM 405 IS NOT COMPLETE AND IS NOT | | | ACCURATE. THE ADDRESS OR OTHER IDENTIFICATION OF THE | | | RESIDENCE IS MISSING. THE OWNER'S NAME AND BUILDER'S | | | NAMES ARE MISSING. THE NAME OF THE PREPARER IS NOT | | | LEGIBLE. FBC ENERGY R101.5.1.1.2 AND R103.2 | | | | | | 3) THE NUMBER OF OCCUPANTS FOR THE RESIDENCE IS | | | SPECIFIED AS 4 (MAIN) AND 8 (BEDROOMS) FOR A TOTAL OF | | | 12 ON THE ENERGY FORM 405. IN THE EQUIPMENT SIZING | | | CALCULATIONS THE NUMBER OF OCCUPANTS ARE SPECIFIED AS 6 | | | (MAIN) AND 8 (BEDROOMS) FOR A TOTAL OF 14. EXPLAIN HOW | | | YOU ARE DETERMINING THE NUMBER OF OCCUPANTS AND WHY | | | THEY ARE DIFFERENT OF FORM 405 AND THE SIZING | | | CALCULATIONS. FBC 107.2.1 | | | | | | 4) THIS PERMIT IS FOR A SPECIFIC RESIDENCE THAT WILL BE | | | BUILT ON A SPECIFIED LOT. IT IS NOT THE MASTER FOR A | | | MODEL THAT WILL BE BUILT ON DIFFERENT LOTS WITH | | | MULTIPLE ORIENTATIONS. THEREFORE, THE ENERGY | | | CALCULATIONS ARE SITE SPECIFIC AND ARE NOT WORST CASE. | | | USE THE ACTUAL DIRECTIONAL ORIENTATION OF THE BUILDING | | | IN THE ENERGY CALCULATIONS AND EQUIPMENT SIZING | | | CALCULATIONS. THERE SHOULD NOT BE ANY ROTATE ANGLE. FBC | | | ENERGY R403.6.1 AND R405.4.2 | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-11-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-11-03 |
Time |
11:37 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-11-02 |
Time |
11:21 |
Sent To |
P |
|
| Notes |
| 2016-11-03 09:50:03 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE BUILDING CODE AND THE STANDARDS THAT ARE | | | SPECIFIED ON SHEET C-1 ARE INCORRECT. PLEASE UPDATE TO | | | THE 2014 FBC, ASTM C94-09, ASTM C90-11B, ASTM C270-08A, | | | ASTM A615-09 AND ASTM A307-07B. 2014 FBC CHAPTER 46. | | | | | | 2) THE DOOR FROM THE GARAGE TO THE RESIDENCE IS | | | REQUIRED TO HAVE A SELF CLOSING DEVICE. FBC-R 302.5.1 | | | | | | 3) THE TOTAL AREA SHOWN IN THE CALCULATION TABLE ON | | | SHEET A-1 SHOULD BE 5593 SQUARE FEET. PLEASE CORRECT. | | | FBC 107.2.1 | | | | | | 4) ON SHEET A-3 THERE ARE TAGS FOR 1/A4 AND THERE IS NO | | | CORRESPONDING DETAIL FOR THEM ON SHEET A-4. PLEASE | | | CLARIFY. FBC 107.2.1 | | | | | | 5) THE PLANS DO NOT SPECIFY THE INSULATION IN THE WALLS | | | THAT ARE ADJACENT TO THE UNCONDITIONED GARAGE. FBC | | | ENERGY CONSERVATION SECTION R303 | | | | | | 6) ON SHEET A-4 THE TRUSS ANCHOR IDENTIFICATION TAGS | | | DID NOT PRINT DARK ENOUGH AND ARE BARELY LEGIBLE. THEY | | | ARE NOT ACCEPTABLE TO BE SCANNED FOR PUBLIC RECORDS. | | | FBC 107.2.1.4 | | | | | | 7) PRODUCT APPROVALS WERE SUBMITTED FOR SKYLIGHTS. SHOW | | | THE SIZE AND LOCATION OF THE SKYLIGHT(S) ON THE PLANS. | | | FBC-R 301.2.1 | | | | | | 8) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT | | | APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION | | | INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE 16' | | | WIDE SECTIONAL GARAGE DOOR. THE ONE THAT WAS SUBMITTED | | | IS LIMITED TO 9' WIDE DOORS. | | | | | | 9) SUBMIT THE UPDATED 2014 CODE VERSION OF FL 10445 FOR | | | THE FRONT DOORS. FBC 107.3.4 | | | | | | 10) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE | | | OUTDOOR BBQ AND ITS EXHAUST HOOD. FBC 107.2.1 | | | | | | 11) THE ENERGY COMPLIANCE FORM 405-10 THAT WAS | | | SUBMITTED IS FOR THE 2010 FBC. SUBMIT TWO COPIES OF | | | FORM 405-14 FOR THE 2014 FBC ENERGY CONSERVATION | | | SECTION R405 | | | | | | 12) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE | | | FORM 405-14. FBC ENERGY CONSERVATION SECTION R103.1.1.2 | | | | | | 13) THE ENERGY FORM LISTS A 50 GALLON GAS WATER HEATER | | | AND THE PLANS SPECIFY TWO GAS TANKLESS WATER HEATERS. | | | PLEASE CORRECT. FBC 107.2.1 | | | | | | 14) THE ENERGY CALCULATION FORMS STATE THAT THIS IS NOT | | | A WORST CASE, THEN SPECIFIES A 90 DEGREE ROTATE ANGLE. | | | THE ACTUAL ORIENTATION OF THE STRUCTURE ON THE LOT IS | | | REQUIRED TO BE USED WHEN NOT USING WORST CASE. PLEASE | | | CORRECT. FBC ENERGY CONSERVATION SECTION R405.4.2 | | | | | | 15) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT | | | A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW | | | COMMENTS HAS BEEN ADDRESSED. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-12-08 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-12-08 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-12-08 |
Time |
13:01 |
Sent To |
|
|
| Notes |
| 2016-12-08 14:18:15 | 2ND REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | PASSED WITH THE FOLLOWING PROVISO | | | | | | 1] GARAGE DOOR OPENER RECEPTACLE OUTLET SHALL BE GFCI | | | PROTECTED PER FBC SECTION E3902.2. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-10-18 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2016-10-18 |
Time |
12:01 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2016-10-13 |
Time |
19:22 |
Sent To |
|
|
| Notes |
| 2016-10-18 12:01:41 | ELECTRICAL REVIEW NOTES | | | REVIEWED FOR COMPLIANCE WITH: | | | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) | | | | | | PROJECT NAME: NEW SFR | | | JOB ADDRESS: 71232 WINDING BAY LANE | | | DESCRIPTION: NEW SFR | | | MASTER PERMIT: 16100154 | | | | | | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. | | | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF | | | SUBMITTED CORRECTIONS. | | | | | | 1. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS: THE CODE | | | TO WHICH THE PROJECT IS BEING DESIGNED SHALL BE CLEARLY | | | INDICATED ON THE DRAWINGS. | | | 2. FBC-RE3902.12 HAS SPECIFIC REQUIREMENTS FOR | | | ARC-FAULT PROTECTION AND THEY GO BEYOND THOSE INDICATED | | | ON THE DRAWINGS. CORRECT BLOCK NOTE ACCORDINGLY. | | | 3. FBC-RE4002.9 (NEC406.9(B)) IS THE APPLICABLE CODE | | | SECTION WHICH REQUIRES THAT RECEPTACLES INSTALLED IN | | | WET OR DAMP LOCATIONS BE LISTED WEATHER RESISTANT. | | | CORRECT BLOCK NOTE ACCORDINGLY. | | | 4. FBC-RE3905.8: BOXES USED FOR THE SOLE SUPPORT OF | | | CEILING FANS SHALL BE MARKED BY THE MANUFACTURER AS | | | SUITABLE FOR THE PURPOSE AND SUPPORT LOADS GREATER THAN | | | 70 LBS. THIS SHALL BE ADDED TO THE BLOCK NOTES. | | | 5. ACCORDING TO FBC REQUIREMENTS BATHROOM VENTILATION | | | FOR THE CABANA BATH IS REQUIRED WHENEVER THE ROOM IS | | | OCCUPIED AND THEREFORE SHALL GO ON WITH THE LIGHTS. THE | | | EXHAUST FAN SHALL BE CONNECTED TO THE LIGHTING. | | | 6. YOU INDICATED LIGHTING FOR THE ATTIC ACCESS ON THE | | | PLANS. MAY I SUGGEST THAT THIS BE SWITCHED OUTSIDE THE | | | ATTIC AND CONTROLLED WITH A SWITCH THAT HAS A PILOT SO | | | AS TO INDICATE IF THE LIGHT IS ACCIDENTLY LEFT ON. | | | FURTHERMORE, THERE SHALL BE LIGHTING AND A GFCI | | | PROTECTED SERVICE OUTLET BY THE HVAC EQUIPMENT INSIDE | | | THE ATTIC AS WELL. | | | 7. ON THE RISER DIAGRAM YOU SHOW DOUBLE TAPPING AT THE | | | METER SOCKET. UNLESS THE METER IS DOUBLE LUGGED THIS IS | | | AGAINST CODE AND THEREFORE NOT ALLOWED. PROVIDE EITHER | | | SPECS FOR THE PROPOSED DOUBLE LUGGED METER CAN OR A | | | BLOCK NOTE ADDRESSING THIS ISSUE. | | | 8. FBC-ER404.1: A MINIMUM OF 75% OF THE PERMANENTLY | | | INSTALLED LIGHTING FIXTURES SHALL BE OF THE | | | HIGH-EFFICACY TYPE OR HAVE A MINIMUM OF 75% OF THE | | | FIXTURES SHALL CONTAIN HIGH-EFFICACY LAMPS. | | | 9. IN ADDITION TO THE ABOVE ENERGY CONSERVATION | | | REQUIREMENT, LET ME SUGGEST THE USE OF ADDITIONAL | | | SWITCHING (3 WAY ETC.) FOR THE MASTER BEDROOM ENTRY AND | | | MASTER BEDROOM CORRIDOR. | | | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | | GREATLY APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | PH: 561-805-6746 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
N |
Date |
2017-03-07 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-03-07 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-03-07 |
Time |
10:27 |
Sent To |
|
|
| Notes |
| 2017-03-07 10:46:07 | GAS APPROVED UNDER SEPARATE PLANS AND PERMIT SUPPLIED | | | BY GAS CONTRACTOR PERMIT # 17020987 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2017-01-24 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-01-24 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-01-24 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2017-01-24 14:43:52 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. ISOMETRIC DRAWING IS UNCLEAR AT WHAT POINT YOUR | | | REDUCING FROM 2LB TO .5LB SYSTEM. PLEASE SHOW REG. PER | | | FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2. | | | | | | 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | | | 3. PROVIDE TABLES USED TO SIZE THE SYSTEM. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 4. LOCATION OF THE POOL HEATER ON THE GAS RISER DOES | | | NOT MATCH FLOOR PLAN PLEASE CLARIFY. PER WPB AMEND TO | | | FBC 107.2.1 | | | | | | 5.IT IS UNCLEAR ON THE RISER HOW THE BRANCH FOR THE | | | COOK TOP AND DRYER CONNECT TO THE MAIN RUN PLEASE | | | CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2016-12-12 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-12-12 |
Time |
18:14 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-12-12 |
Time |
18:14 |
Sent To |
|
|
| Notes |
| 2016-12-12 18:24:54 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL | | | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS IT IS | | | UNCLEAR AT WHAT POINT YOUR REDUCING FROM 2LB TO .5LB | | | SYSTEM. PER FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2. | | | | | | 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | | | 3. PROVIDE TABLES USED TO SIZE THE SYSTEM. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 4. PROVIDE FLOOR PLAN SHOWING GAS PIPING THE LOCATION | | | OF THE POOL HEATER DOES NOT MATCH FLOOR PLAN. PER WPB | | | AMEND TO FBC 107.2.1 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2016-11-03 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-11-03 |
Time |
12:11 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-11-03 |
Time |
12:11 |
Sent To |
|
|
| Notes |
| 2016-11-03 12:22:14 | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | | THIS TIME. A GAS PERMIT IS REQUIRED FOR A CONTRACTOR TO | | | PERFORM THE RELATED WORK. PROVIDE COMPLETE PLANS THAT | | | REFLECT THE ENTIRE SCOPE OF GAS WORK TO BE DONE. WPB | | | AMEND. TO FBC SEC.107.2.1. | | | | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE | | | FBC-R, SEC. G2404.3. | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL | | | GAS SEC. 301.3. | | | | | | A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2017-09-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-09-01 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-08-29 |
Time |
15:16 |
Sent To |
|
|
| Notes |
| 2017-08-31 15:16:24 | IMPACT FEES ROUTED TO RMCDOUGAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-01-24 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-01-24 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-01-12 |
Time |
11:25 |
Sent To |
|
|
| Notes |
| 2017-01-13 11:25:49 | RESUB ROUTED TO RMCDOUGAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-12-12 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-12-12 |
Time |
18:25 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-11-18 |
Time |
14:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-11-03 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-11-03 |
Time |
12:22 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-10-11 |
Time |
08:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2017-09-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-09-01 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-09-01 |
Time |
09:22 |
Sent To |
|
|
| Notes |
| 2017-09-01 10:48:35 | MU 2017 - 13114, PAID $9,904.34 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2016-11-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-11-02 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-11-02 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2016-11-02 11:20:48 | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2016-12-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-12-06 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-12-06 |
Time |
16:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2016-11-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-11-03 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-11-03 |
Time |
08:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2017-03-07 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-03-07 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-03-07 |
Time |
10:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2017-01-24 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-01-24 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-01-24 |
Time |
14:33 |
Sent To |
|
|
| Notes |
| 2017-01-24 14:33:53 | 3RD REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. COMPLY WITH GAS COMMENTS. PER WPB AMEND TO FBC | | | 107.2.1 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2016-12-12 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-12-12 |
Time |
18:12 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-12-12 |
Time |
17:03 |
Sent To |
|
|
| Notes |
| 2016-12-12 18:14:12 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. COMPLY WITH GAS COMMENTS. PER WPB AMEND TO FBC | | | 107.2.1 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2016-11-03 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-11-03 |
Time |
12:10 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-10-22 |
Time |
08:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2017-01-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-01-18 |
Time |
18:57 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-01-18 |
Time |
18:32 |
Sent To |
|
|
| Notes |
| 2017-01-18 18:57:43 | EAGLE ROOF TILE - FL7473-R6 | | | 3M FOAM ROOF TILE ADHESIVE AH-160 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2016-12-01 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2016-12-01 |
Time |
16:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2016-10-31 |
|
|
Cont ID |
|
| Sent By |
pgrehic |
Date |
2016-10-31 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2016-10-31 |
Time |
15:55 |
Sent To |
|
|
| Notes |
|
|