Plan Review Details - Permit 16100154
Plan Review Stops For Permit 16100154
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-01-19 Cont ID  
Sent By rmcdouga Date 2017-01-19 Time 09:11 Rev Time 0.00
Received By rmcdouga Date 2017-01-18 Time 18:32 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-12-06 Cont ID  
Sent By rmcdouga Date 2016-12-06 Time 19:03 Rev Time 0.00
Received By rmcdouga Date 2016-12-06 Time 17:00 Sent To  
Notes
2016-12-06 19:03:11PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ON SHEETS A-3 AND A-4 THERE ARE ID TAGS FOR ROOF TO
 WALL CONNECTORS MARKED 1/A4 AND 2/A4, HOWEVER, THERE
 ARE NO CORRESPONDING DETAILS FOR THEM ON SHEET A-4.
 PLEASE CLARIFY. FBC 107.2.1
  
 2) THE ENERGY FORM 405 IS NOT COMPLETE AND IS NOT
 ACCURATE. THE ADDRESS OR OTHER IDENTIFICATION OF THE
 RESIDENCE IS MISSING. THE OWNER'S NAME AND BUILDER'S
 NAMES ARE MISSING. THE NAME OF THE PREPARER IS NOT
 LEGIBLE. FBC ENERGY R101.5.1.1.2 AND R103.2
  
 3) THE NUMBER OF OCCUPANTS FOR THE RESIDENCE IS
 SPECIFIED AS 4 (MAIN) AND 8 (BEDROOMS) FOR A TOTAL OF
 12 ON THE ENERGY FORM 405. IN THE EQUIPMENT SIZING
 CALCULATIONS THE NUMBER OF OCCUPANTS ARE SPECIFIED AS 6
 (MAIN) AND 8 (BEDROOMS) FOR A TOTAL OF 14. EXPLAIN HOW
 YOU ARE DETERMINING THE NUMBER OF OCCUPANTS AND WHY
 THEY ARE DIFFERENT OF FORM 405 AND THE SIZING
 CALCULATIONS. FBC 107.2.1
  
 4) THIS PERMIT IS FOR A SPECIFIC RESIDENCE THAT WILL BE
 BUILT ON A SPECIFIED LOT. IT IS NOT THE MASTER FOR A
 MODEL THAT WILL BE BUILT ON DIFFERENT LOTS WITH
 MULTIPLE ORIENTATIONS. THEREFORE, THE ENERGY
 CALCULATIONS ARE SITE SPECIFIC AND ARE NOT WORST CASE.
 USE THE ACTUAL DIRECTIONAL ORIENTATION OF THE BUILDING
 IN THE ENERGY CALCULATIONS AND EQUIPMENT SIZING
 CALCULATIONS. THERE SHOULD NOT BE ANY ROTATE ANGLE. FBC
 ENERGY R403.6.1 AND R405.4.2
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-11-03 Cont ID  
Sent By rmcdouga Date 2016-11-03 Time 11:37 Rev Time 0.00
Received By rmcdouga Date 2016-11-02 Time 11:21 Sent To P
Notes
2016-11-03 09:50:03PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE BUILDING CODE AND THE STANDARDS THAT ARE
 SPECIFIED ON SHEET C-1 ARE INCORRECT. PLEASE UPDATE TO
 THE 2014 FBC, ASTM C94-09, ASTM C90-11B, ASTM C270-08A,
 ASTM A615-09 AND ASTM A307-07B. 2014 FBC CHAPTER 46.
  
 2) THE DOOR FROM THE GARAGE TO THE RESIDENCE IS
 REQUIRED TO HAVE A SELF CLOSING DEVICE. FBC-R 302.5.1
  
 3) THE TOTAL AREA SHOWN IN THE CALCULATION TABLE ON
 SHEET A-1 SHOULD BE 5593 SQUARE FEET. PLEASE CORRECT.
 FBC 107.2.1
  
 4) ON SHEET A-3 THERE ARE TAGS FOR 1/A4 AND THERE IS NO
 CORRESPONDING DETAIL FOR THEM ON SHEET A-4. PLEASE
 CLARIFY. FBC 107.2.1
  
 5) THE PLANS DO NOT SPECIFY THE INSULATION IN THE WALLS
 THAT ARE ADJACENT TO THE UNCONDITIONED GARAGE. FBC
 ENERGY CONSERVATION SECTION R303
  
 6) ON SHEET A-4 THE TRUSS ANCHOR IDENTIFICATION TAGS
 DID NOT PRINT DARK ENOUGH AND ARE BARELY LEGIBLE. THEY
 ARE NOT ACCEPTABLE TO BE SCANNED FOR PUBLIC RECORDS.
 FBC 107.2.1.4
  
 7) PRODUCT APPROVALS WERE SUBMITTED FOR SKYLIGHTS. SHOW
 THE SIZE AND LOCATION OF THE SKYLIGHT(S) ON THE PLANS.
 FBC-R 301.2.1
  
 8) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE 16'
 WIDE SECTIONAL GARAGE DOOR. THE ONE THAT WAS SUBMITTED
 IS LIMITED TO 9' WIDE DOORS.
  
 9) SUBMIT THE UPDATED 2014 CODE VERSION OF FL 10445 FOR
 THE FRONT DOORS. FBC 107.3.4
  
 10) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE
 OUTDOOR BBQ AND ITS EXHAUST HOOD. FBC 107.2.1
  
 11) THE ENERGY COMPLIANCE FORM 405-10 THAT WAS
 SUBMITTED IS FOR THE 2010 FBC. SUBMIT TWO COPIES OF
 FORM 405-14 FOR THE 2014 FBC ENERGY CONSERVATION
 SECTION R405
  
 12) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 FORM 405-14. FBC ENERGY CONSERVATION SECTION R103.1.1.2
  
 13) THE ENERGY FORM LISTS A 50 GALLON GAS WATER HEATER
 AND THE PLANS SPECIFY TWO GAS TANKLESS WATER HEATERS.
 PLEASE CORRECT. FBC 107.2.1
  
 14) THE ENERGY CALCULATION FORMS STATE THAT THIS IS NOT
 A WORST CASE, THEN SPECIFIES A 90 DEGREE ROTATE ANGLE.
 THE ACTUAL ORIENTATION OF THE STRUCTURE ON THE LOT IS
 REQUIRED TO BE USED WHEN NOT USING WORST CASE. PLEASE
 CORRECT. FBC ENERGY CONSERVATION SECTION R405.4.2
  
 15) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-12-08 Cont ID  
Sent By mvaldes Date 2016-12-08 Time 14:18 Rev Time 0.00
Received By mvaldes Date 2016-12-08 Time 13:01 Sent To  
Notes
2016-12-08 14:18:152ND REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO
  
 1] GARAGE DOOR OPENER RECEPTACLE OUTLET SHALL BE GFCI
 PROTECTED PER FBC SECTION E3902.2.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-10-18 Cont ID  
Sent By albarran Date 2016-10-18 Time 12:01 Rev Time 0.00
Received By albarran Date 2016-10-13 Time 19:22 Sent To  
Notes
2016-10-18 12:01:41ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: NEW SFR
 JOB ADDRESS: 71232 WINDING BAY LANE
 DESCRIPTION: NEW SFR
 MASTER PERMIT: 16100154
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS: THE CODE
 TO WHICH THE PROJECT IS BEING DESIGNED SHALL BE CLEARLY
 INDICATED ON THE DRAWINGS.
 2. FBC-RE3902.12 HAS SPECIFIC REQUIREMENTS FOR
 ARC-FAULT PROTECTION AND THEY GO BEYOND THOSE INDICATED
 ON THE DRAWINGS. CORRECT BLOCK NOTE ACCORDINGLY.
 3. FBC-RE4002.9 (NEC406.9(B)) IS THE APPLICABLE CODE
 SECTION WHICH REQUIRES THAT RECEPTACLES INSTALLED IN
 WET OR DAMP LOCATIONS BE LISTED WEATHER RESISTANT.
 CORRECT BLOCK NOTE ACCORDINGLY.
 4. FBC-RE3905.8: BOXES USED FOR THE SOLE SUPPORT OF
 CEILING FANS SHALL BE MARKED BY THE MANUFACTURER AS
 SUITABLE FOR THE PURPOSE AND SUPPORT LOADS GREATER THAN
 70 LBS. THIS SHALL BE ADDED TO THE BLOCK NOTES.
 5. ACCORDING TO FBC REQUIREMENTS BATHROOM VENTILATION
 FOR THE CABANA BATH IS REQUIRED WHENEVER THE ROOM IS
 OCCUPIED AND THEREFORE SHALL GO ON WITH THE LIGHTS. THE
 EXHAUST FAN SHALL BE CONNECTED TO THE LIGHTING.
 6. YOU INDICATED LIGHTING FOR THE ATTIC ACCESS ON THE
 PLANS. MAY I SUGGEST THAT THIS BE SWITCHED OUTSIDE THE
 ATTIC AND CONTROLLED WITH A SWITCH THAT HAS A PILOT SO
 AS TO INDICATE IF THE LIGHT IS ACCIDENTLY LEFT ON.
 FURTHERMORE, THERE SHALL BE LIGHTING AND A GFCI
 PROTECTED SERVICE OUTLET BY THE HVAC EQUIPMENT INSIDE
 THE ATTIC AS WELL.
 7. ON THE RISER DIAGRAM YOU SHOW DOUBLE TAPPING AT THE
 METER SOCKET. UNLESS THE METER IS DOUBLE LUGGED THIS IS
 AGAINST CODE AND THEREFORE NOT ALLOWED. PROVIDE EITHER
 SPECS FOR THE PROPOSED DOUBLE LUGGED METER CAN OR A
 BLOCK NOTE ADDRESSING THIS ISSUE.
 8. FBC-ER404.1: A MINIMUM OF 75% OF THE PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE OF THE
 HIGH-EFFICACY TYPE OR HAVE A MINIMUM OF 75% OF THE
 FIXTURES SHALL CONTAIN HIGH-EFFICACY LAMPS.
 9. IN ADDITION TO THE ABOVE ENERGY CONSERVATION
 REQUIREMENT, LET ME SUGGEST THE USE OF ADDITIONAL
 SWITCHING (3 WAY ETC.) FOR THE MASTER BEDROOM ENTRY AND
 MASTER BEDROOM CORRIDOR.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop G GAS REVIEW
Rev No 4 Status N Date 2017-03-07 Cont ID  
Sent By gjohnson Date 2017-03-07 Time 10:27 Rev Time 0.00
Received By gjohnson Date 2017-03-07 Time 10:27 Sent To  
Notes
2017-03-07 10:46:07GAS APPROVED UNDER SEPARATE PLANS AND PERMIT SUPPLIED
 BY GAS CONTRACTOR PERMIT # 17020987
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2017-01-24 Cont ID  
Sent By gjohnson Date 2017-01-24 Time 14:34 Rev Time 0.00
Received By gjohnson Date 2017-01-24 Time 14:34 Sent To  
Notes
2017-01-24 14:43:521ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. ISOMETRIC DRAWING IS UNCLEAR AT WHAT POINT YOUR
 REDUCING FROM 2LB TO .5LB SYSTEM. PLEASE SHOW REG. PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 3. PROVIDE TABLES USED TO SIZE THE SYSTEM. PER WPB
 AMEND TO FBC 107.2.1
  
 4. LOCATION OF THE POOL HEATER ON THE GAS RISER DOES
 NOT MATCH FLOOR PLAN PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 5.IT IS UNCLEAR ON THE RISER HOW THE BRANCH FOR THE
 COOK TOP AND DRYER CONNECT TO THE MAIN RUN PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2016-12-12 Cont ID  
Sent By gjohnson Date 2016-12-12 Time 18:14 Rev Time 0.00
Received By gjohnson Date 2016-12-12 Time 18:14 Sent To  
Notes
2016-12-12 18:24:541ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS IT IS
 UNCLEAR AT WHAT POINT YOUR REDUCING FROM 2LB TO .5LB
 SYSTEM. PER FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 3. PROVIDE TABLES USED TO SIZE THE SYSTEM. PER WPB
 AMEND TO FBC 107.2.1
  
 4. PROVIDE FLOOR PLAN SHOWING GAS PIPING THE LOCATION
 OF THE POOL HEATER DOES NOT MATCH FLOOR PLAN. PER WPB
 AMEND TO FBC 107.2.1

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-11-03 Cont ID  
Sent By tklarge Date 2016-11-03 Time 12:11 Rev Time 0.00
Received By tklarge Date 2016-11-03 Time 12:11 Sent To  
Notes
2016-11-03 12:22:14A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A GAS PERMIT IS REQUIRED FOR A CONTRACTOR TO
 PERFORM THE RELATED WORK. PROVIDE COMPLETE PLANS THAT
 REFLECT THE ENTIRE SCOPE OF GAS WORK TO BE DONE. WPB
 AMEND. TO FBC SEC.107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-09-01 Cont ID  
Sent By rmcdouga Date 2017-09-01 Time 09:22 Rev Time 0.00
Received By rmcdouga Date 2017-08-29 Time 15:16 Sent To  
Notes
2017-08-31 15:16:24IMPACT FEES ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-01-24 Cont ID  
Sent By gjohnson Date 2017-01-24 Time 14:44 Rev Time 0.00
Received By gjohnson Date 2017-01-12 Time 11:25 Sent To  
Notes
2017-01-13 11:25:49RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-12 Cont ID  
Sent By gjohnson Date 2016-12-12 Time 18:25 Rev Time 0.00
Received By gjohnson Date 2016-11-18 Time 14:52 Sent To  
Notes
2016-11-21 14:53:17R23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-03 Cont ID  
Sent By tklarge Date 2016-11-03 Time 12:22 Rev Time 0.00
Received By tklarge Date 2016-10-11 Time 08:11 Sent To  
Notes
2016-10-12 08:11:51R21

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-09-01 Cont ID  
Sent By rmcdouga Date 2017-09-01 Time 09:22 Rev Time 0.00
Received By rmcdouga Date 2017-09-01 Time 09:22 Sent To  
Notes
2017-09-01 10:48:35MU 2017 - 13114, PAID $9,904.34

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-11-02 Cont ID  
Sent By rmcdouga Date 2016-11-02 Time 11:20 Rev Time 0.00
Received By rmcdouga Date 2016-11-02 Time 11:20 Sent To  
Notes
2016-11-02 11:20:48BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-12-06 Cont ID  
Sent By rmcdouga Date 2016-12-06 Time 16:59 Rev Time 0.00
Received By rmcdouga Date 2016-12-06 Time 16:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-11-03 Cont ID  
Sent By rmcdouga Date 2016-11-03 Time 08:56 Rev Time 0.00
Received By rmcdouga Date 2016-11-03 Time 08:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2017-03-07 Cont ID  
Sent By gjohnson Date 2017-03-07 Time 10:47 Rev Time 0.00
Received By gjohnson Date 2017-03-07 Time 10:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2017-01-24 Cont ID  
Sent By gjohnson Date 2017-01-24 Time 14:33 Rev Time 0.00
Received By gjohnson Date 2017-01-24 Time 14:33 Sent To  
Notes
2017-01-24 14:33:533RD REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. COMPLY WITH GAS COMMENTS. PER WPB AMEND TO FBC
 107.2.1

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-12-12 Cont ID  
Sent By gjohnson Date 2016-12-12 Time 18:12 Rev Time 0.00
Received By gjohnson Date 2016-12-12 Time 17:03 Sent To  
Notes
2016-12-12 18:14:121ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. COMPLY WITH GAS COMMENTS. PER WPB AMEND TO FBC
 107.2.1

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-11-03 Cont ID  
Sent By tklarge Date 2016-11-03 Time 12:10 Rev Time 0.00
Received By tklarge Date 2016-10-22 Time 08:27 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2017-01-18 Cont ID  
Sent By rmcdouga Date 2017-01-18 Time 18:57 Rev Time 0.00
Received By rmcdouga Date 2017-01-18 Time 18:32 Sent To  
Notes
2017-01-18 18:57:43EAGLE ROOF TILE - FL7473-R6
 3M FOAM ROOF TILE ADHESIVE AH-160

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2016-12-01 Time   Rev Time 0.00
Received By pgreilic Date 2016-12-01 Time 16:00 Sent To  
Notes
2016-12-01 16:01:26PAUL GREILICH, SENIOR PLANNER
 (561)-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2016-10-31 Cont ID  
Sent By pgrehic Date 2016-10-31 Time   Rev Time 0.00
Received By pgreilic Date 2016-10-31 Time 15:55 Sent To  
Notes
2016-10-31 15:12:16PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]