| Plan Review Stops For Permit 16100098 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-10-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-10-11 |
Time |
07:44 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-10-11 |
Time |
07:44 |
Sent To |
|
|
| Notes |
| 2016-10-11 07:50:15 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE | | | 9N-3. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH FL OR | | | NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND | | | MAXIMUM DESIGN PRESSURES FOR THE ROOFING MATERIALS. | | | | | | 2) SUBMIT TWO SETS OF SIGNED AND SEALED WINDLOAD DATA | | | WITH REQUIRED COMPONENT AND CLADDING PRESSURES FOR THE | | | PROJECT. FBC 107.2.1 & 107.2.1.3 | | | | | | 3) SUBMIT TWO SETS OF ANY OTHER DOCUMENTS THAT ARE | | | REQUIRED BY THE PRODUCT APPROVALS OR ROOFING STANDARDS, | | | SUCH AS, MOISTURE TESTS FOR THE INSULATION ABOVE THE | | | ROOF DECK. FBC 107.2.1 |
|
|