Plan Review Details - Permit 16100078
Plan Review Stops For Permit 16100078
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-10-12 Cont ID  
Sent By rmcdouga Date 2016-10-12 Time 17:48 Rev Time 0.00
Received By rmcdouga Date 2016-10-12 Time 17:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-10-12 Cont ID  
Sent By albarran Date 2016-10-12 Time 14:40 Rev Time 0.00
Received By albarran Date 2016-10-12 Time 13:40 Sent To  
Notes
2016-10-12 14:58:19ALL WORK TO COMPLY WITH THE 2011 EDITION OF THE NEC

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-10-18 Cont ID  
Sent By rmcdouga Date 2016-10-18 Time 18:48 Rev Time 0.00
Received By rmcdouga Date 2016-10-18 Time 18:48 Sent To  
Notes
2016-10-18 18:50:21NO GAS PIPING SHOWN ON PLANS, A SEPARATE PERMIT,
 APPLICATION AND REVIEW IS REQUIRED IF ANY CHANGES TO
 GAS PIPING IS REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-18 Cont ID  
Sent By rmcdouga Date 2016-10-18 Time 18:48 Rev Time 0.00
Received By rmcdouga Date 2016-10-04 Time 11:07 Sent To  
Notes
2016-10-05 11:07:38R05

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-10-28 Cont ID  
Sent By rmcdouga Date 2016-10-28 Time 13:27 Rev Time 0.00
Received By rmcdouga Date 2016-10-28 Time 13:27 Sent To  
Notes
2016-10-28 13:30:13DOCUMENTS FOR MONOGRAM 48" GAS RANGE RECIEVED AND ADDED
 TO PERMIT DOCUMENTS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-10-18 Cont ID  
Sent By rmcdouga Date 2016-10-18 Time 18:48 Rev Time 0.00
Received By rmcdouga Date 2016-10-18 Time 18:48 Sent To  
Notes
2016-10-18 19:00:58PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS, INSTALLATION
 INSTRUCTIONS AND PRODUCT LISTING INFORMATION FOR THE
 NEW GAS RANGE. NOTE: COMMERCIAL RANGES CAN NOT BE USED
 FOR RESIDENTIAL APPLICATION. FBC MECHANICAL 301.7 AND
 917.3

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-10-18 Cont ID  
Sent By rmcdouga Date 2016-10-18 Time 18:47 Rev Time 0.00
Received By rmcdouga Date 2016-10-18 Time 18:47 Sent To  
Notes
***NONE***