Plan Review Details - Permit 16100063
Plan Review Stops For Permit 16100063
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-12-07 Cont ID  
Sent By shill Date 2016-12-07 Time 06:51 Rev Time 0.00
Received By shill Date 2016-12-07 Time 06:51 Sent To  
Notes
2016-12-07 06:52:35****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PROVISO:
  
 1. A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED PRIOR TO C.O.
  
 2. PRIOR TO INSTALLATION, SUBMIT A LETTER CLARIFYING
 WIND DESIGN CRITERIA FOR THE ROOFTOP MECHANICAL
 EQUIPMENT, DETAIL ON M2. THE WIND SPEED WAS PROVIDED
 BUT EXPOSURE CLASSIFICATION WAS NOT. SEE FBC
 1603.1.4(3). THIS SITE REQUIRES A MINIMUM DESIGN
 CRITERIA OF EXPOSURE C.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-11-30 Cont ID  
Sent By shill Date 2016-11-30 Time 12:12 Rev Time 0.00
Received By shill Date 2016-11-30 Time 12:12 Sent To  
Notes
2016-11-30 12:19:52****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 ALL BUILDING COMMENTS HAVE BEEN ADDRESSED.
  
 THE NEW PLAN SHOWS THAT THE PROPOSED WORK IS IN SUITES
 5-6, BUT THE APPLICATION IS FOR SUITE 3. PLEASE SUBMIT
 A NEW APPLICATION THROUGH THE FRONT COUNTER; THE
 ADDRESS FOR THE PERMIT RECORD MUST ALSO BE CHANGED. FEE
 MAY APPLY.
  
 WHEN THIS IS DONE, PLEASE ADVISE AND THE PLAN REVIEW
 WILL BE PASSED.
  
 THIS PERMIT WILL BE ISSUED WITH PROVISO:
  
 1. A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED PRIOR TO C.O.
  
 2. PRIOR TO INSTALLATION, SUBMIT A LETTER CLARIFYING
 WIND DESIGN CRITERIA FOR THE ROOFTOP MECHANICAL
 EQUIPMENT, DETAIL ON M2. THE WIND SPEED WAS PROVIDED
 BUT EXPOSURE CLASSIFICATION WAS NOT. SEE FBC
 1603.1.4(3). THIS SITE REQUIRES A MINIMUM DESIGN
 CRITERIA OF EXPOSURE C.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-10-18 Cont ID  
Sent By shill Date 2016-10-18 Time 14:58 Rev Time 0.00
Received By shill Date 2016-10-18 Time 14:57 Sent To  
Notes
2016-10-18 14:59:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE THE PERMIT NUMBER WHICH INCLUDED POURING THE
 FLOOR SLAB FOR THIS STRUCTURE, FBC 107. IF IT IS A PART
 OF THIS PERMIT, REVISE PLAN TO REFLECT THIS WORK.
  
 2. VALUE HAS BEEN ADJUSTED PER ICC TABLES. PAY THE
 BALANCE OF THE PLAN REVIEW FEES PRIOR TO RESUBMITTAL,
 FBC 109.
  
 3. PLANS AND ENERGY CALCS STATE THAT THIS IS AN
 ALTERATION. THIS BUILDING HAS NOT BEEN ISSUED A C.O. AS
 THE PERMITTING IS PHASED. THIS IS THE SECOND PHASE
 (FIRST OCCUPANCY) FOR THIS STRUCTURE. REVISE
 ACCORDINGLY.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-12-08 Cont ID  
Sent By mvaldes Date 2016-12-08 Time 17:59 Rev Time 0.00
Received By mvaldes Date 2016-12-08 Time 17:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-10-17 Cont ID  
Sent By mvaldes Date 2016-10-17 Time 17:00 Rev Time 0.00
Received By mvaldes Date 2016-10-17 Time 14:00 Sent To  
Notes
2016-10-17 17:21:14JOB PERMIT NUMBER: 16100063
 JOB ADDRESS: 8170 OKEECHOBEE BLVD SUITE #3
 WEST PALM BEACH FLORIDA
 DATE: OCTOBER 17, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. BELOW IS A LIST OF ITEMS NOTED.
  
 1] LOW VOLTAGE SHALL BE UNDER A SEPARATE PERMIT
  
 2] ADD EMERGENCY LIGHTING TO THE MEANS OF EGRESS PATH
 INCLUDING THE EXIT DISCHARGE IN MAIN ROOM AREA, STOCK
 PREP ROOM, AND FUTURE CLEAN ROOM. THE ILLUMINATION
 LEVEL UNDER EMERGENCY POWER SHALL BE A MINIMUM 1'
 CANDLE AT THE WALKING SURFACE. FBC-1006
  
 3] THE LIGHTING IN THE MECHANICAL ROOM WHERE THE
 ELECTRICAL PANEL IS LOCATED SHALL NOT BE CONTROLLED BY
 AUTOMATIC MEANS. NEC 110.26(D)
  
 4] CLARIFY IF FUTURE CLEAN ROOM CONTAINS EXPLOSIVE
 CHEMICALS OR ACIDS THEREFORE CLASSIFIED AS A HAZARDOUS
 LOCATION PER NEC 500 ?
  
 5] PROVIDE A LIGHTING POWER DENSITY CHART TO
 DEMONSTRATE MAXIMUM ENERGY ALLOWANCES. SHOW COMPLIANCE
 USING THE TOTAL BUILDING OR SPACE BY SPACE METHODS WITH
 TRADE OFF PER FBC-E SEC C405.5.
  
 6] PROVIDE VOLTAGE DROP CALCULATIONS FOR FEEDERS OF
 PANEL A LOCATED IN SUITE #5. FEEDERS & CUSTOMER OWNED
 SERVICE CONDUCTORS SHALL BE SIZED FOR A MAXIMUM OF 2%
 VOLTAGE DROP. BRANCH CIRCUITS SHALL BE SIZED FOR A
 MAXIMUM OF 3% VOLTAGE DROP. ADD TO ELECT NOTES.
  
 7] ADD TO ELECT NOTES THE SOURCE OF POWER
 IDENTIFICATION MARK AT PANELBOARD PER NEC 408.4(B)
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-10-12 Cont ID  
Sent By wjolin Date 2016-10-12 Time 13:31 Rev Time 0.00
Received By wjolin Date 2016-10-12 Time 13:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-21 Cont ID  
Sent By gjohnson Date 2016-12-21 Time 11:50 Rev Time 0.00
Received By gjohnson Date 2016-11-28 Time 13:34 Sent To  
Notes
2016-11-28 13:34:34B23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-07 Cont ID  
Sent By shill Date 2016-10-25 Time 06:46 Rev Time 0.00
Received By shill Date 2016-10-04 Time 12:50 Sent To  
Notes
2016-10-05 12:51:01B03

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-10-31 Cont ID  
Sent By shill Date 2016-10-31 Time 08:15 Rev Time 0.00
Received By shill Date 2016-10-31 Time 08:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-12-16 Cont ID  
Sent By ccole Date 2016-12-02 Time 11:02 Rev Time 0.00
Received By ccole Date 2016-12-02 Time 11:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-10-13 Cont ID  
Sent By ccole Date 2016-10-13 Time 11:55 Rev Time 0.00
Received By ccole Date 2016-10-13 Time 11:55 Sent To  
Notes
2016-10-13 12:13:171ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16100063
 10/13/16
  
 1) SHEET M2: THE VENTILATION RATE FOR THE STOCK AND
 PREPARATION ROOM SHALL BE CALCULATED AT- (10 PERSONS
 PER 1000 SQ. FT.) AT (5 CFM PER PERSON) AND (0.18 CFMS
 PER SQ. FT.). PLEASE CORRECT THE FRESH AIR CALCULATION.
  
 2) THE FUTURE CLEAN ROOM CANNOT BE PERMITTED UNDER THIS
 APPLICATION WITHOUT MORE SPECIFIC INFORMATION TO
 CLARIFY THE PROCESSES THAT WILL BE CONDUCTED IN THE
 ROOM; WHAT EQUIPMENT WILL BE IN THE ROOM, WHAT
 MATERIALS WILL BE STORED IN THE ROOM, HOW PARTICLE
 CONCENTRATION AND ENVIRONMENTAL CONDITIONS WILL BE
 CONTROLLED, AND HOW CROSS-CONTAMINATION WILL BE
 PREVENTED ETC. THE CURRENT LAYOUT PLAN SHOWS AIR
 COMMUNICATING FROM OTHER SPACES INTO THE CLEAN ROOM AND
 VICE-VERSA WHICH MAY BE PROHIBITED PER FDA OR OTHER
 REGULATORY GUIDELINES. VERY TYPICALLY HEPA FILTERS ARE
 USED FOR AIR DEVICES IN THESE TYPES OF ROOMS, HOWEVER
 NONE HAVE BEEN SPECIFIED. PLEASE REFER TO CHAPTER 18 OF
 THE ASHRAE HANDBOOK FOR MORE INFORMATION.
  
 3) M2: THE WIND LOAD DESGIN CRITERIA FOR ATTACHING THE
 RTU IS INCOMPLETE AND ALSO SPECIFIES AN INCORRECT WIND
 SPEED FOR WPB. REFER TO SECTION 1609 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status P Date 2016-11-30 Cont ID  
Sent By shill Date 2016-11-30 Time 11:27 Rev Time 0.00
Received By shill Date 2016-11-30 Time 11:27 Sent To  
Notes
2016-11-30 11:29:02PROVISO
  
 FINISHED CONSTRUCTION ELEVATION CERTIFICATE REQUIRED
 PRIOR TO CO

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-12-21 Cont ID  
Sent By gjohnson Date 2016-12-21 Time 11:49 Rev Time 0.00
Received By gjohnson Date 2016-12-21 Time 09:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-10-25 Cont ID  
Sent By gjohnson Date 2016-10-25 Time 14:02 Rev Time 0.00
Received By gjohnson Date 2016-10-25 Time 14:02 Sent To  
Notes
2016-10-25 14:05:071ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHOW CLEAR FLOOR SPACE AND HEIGHT FOR KITCHENETTE.
 SHALL COMPLY WITH FBCACC 808/ 606.2/ 606.3

Review Stop Z ZONING
Rev No 1 Status P Date 2016-10-25 Cont ID  
Sent By eschneid Date 2016-10-25 Time 09:28 Rev Time 0.50
Received By eschneid Date 2016-10-24 Time 17:00 Sent To  
Notes
***NONE***