Plan Review Details - Permit 16100054
Plan Review Stops For Permit 16100054
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2016-11-21 Cont ID  
Sent By shill Date 2016-11-21 Time 08:40 Rev Time 0.00
Received By shill Date 2016-11-21 Time 08:40 Sent To  
Notes
2016-11-21 08:43:36A BUILDING STOP WAS ADDED DURING THE PLAN REVIEW
 PROCESS. IN THIS DEPARTMENT, ACCESS CONTROL PERMITS ARE
 REVIEWED BY ELECTRICAL AND FIRE ONLY. IT IS NOT CLEAR
 WHY A BUILDING STOP WAS ADDED (VERIFIED THAT SAK AND DH
 DID NOT HAVE INFORMATION).
  
 SHOULD A STAFF PERSON DETERMINE THAT A BUILDING REVIEW
 IS REQUIRED FOR THIS PARTICULAR ACCESS PERMIT, ADD A
 BUILDING REVIEW STOP BUT ALSO PLEASE ADD A BRIEF
 EXPLANATION AS TO WHY IT IS REQUIRED FOR THIS PERMIT.
  
 DUE TO WORK LOAD AND DEPARTMENT PROCEDURES, NO BUILDING
 REVIEW WAS DONE.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-03-10 Cont ID  
Sent By vperez Date 2017-03-10 Time 15:56 Rev Time 0.00
Received By vperez Date 2017-03-10 Time 15:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-02-21 Cont ID  
Sent By vperez Date 2017-02-21 Time 10:40 Rev Time 0.00
Received By vperez Date 2017-02-21 Time 10:40 Sent To  
Notes
2017-02-21 10:40:42PLEASE ADDRESS FIRE COMMENTS FOR AN ELECTRICAL
 APPROVAL..
  
 V PEREZ
 *6717

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-10-11 Cont ID  
Sent By vperez Date 2016-10-11 Time 10:21 Rev Time 0.00
Received By vperez Date 2016-10-11 Time 10:21 Sent To FIRE
Notes
2016-10-11 10:22:44ADDED BUILDING AND FIRE STOP, ACCESS, GATE REFUGE AREA

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-03-09 Cont ID  
Sent By wjolin Date 2017-03-09 Time 13:54 Rev Time 0.00
Received By wjolin Date 2017-03-09 Time 13:54 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-02-15 Cont ID  
Sent By wjolin Date 2017-02-15 Time 12:31 Rev Time 0.00
Received By wjolin Date 2017-02-15 Time 11:32 Sent To E
Notes
2017-02-15 12:31:49333 FERN STREET
 PERMIT #16100054
 MASTER #15031312
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 SHEET SE-100SECURITY CAMERA STILL LOCATED IN EXIT
 PASSAGEWAY #115.
  
 ORIGINAL COMMENT: 1ST FLOOR: ACCESS CONTROL CONDUIT,
 HARDWARE, ETC. AND SECURITY CAMERAS ARE NOT ESSENTIAL
 TO THE FUNCTION OF THE STAIR AND ARE NOT PERMITTED IN
 THE EXIT STAIRS OR EXIT PASSAGEWAY. PER NFPA 101
 SECTION 7.1.3.2.1, PENETRATIONS INTO, AND OPENINGS
 THROUGH, AN EXIT ENCLOSURE ASSEMBLY SHALL BE LIMITED TO
 DOOR ASSEMBLIES FROM NORMALLY OCCUPIED SPACES AND
 CORRIDORS, REQUIRED EXIT DOOR OPENINGS, ELECTRICAL
 CONDUIT SERVING THE EXIT ENCLOSURE, DUCTWORK AND
 EQUIPMENT NECESSARY FOR INDEPENDENT STAIR
 PRESSURIZATION, WATER OR STEAM PIPING NECESSARY FOR THE
 HEATING OR COOLING OF THE EXIT ENCLOSURE, SPRINKLER
 PIPING, STANDPIPES, AND PENETRATIONS FOR FIRE ALARM
 CIRCUITS, WHERE THE CIRCUITS ARE INSTALLED IN METAL
 CONDUIT AND THE PENETRATIONS ARE PROTECTED.
  
 SHEET SE-106: DOOR HARDWARE DR20 AND DR21 ARE EQUIPPED
 WITH MAGNETIC LOCKS AND NO PUSH BUTTON OR OCCUPANCY
 SENSOR ON THE INTERIOR EGRESS SIDE OF THE DOOR. REFER
 TO ARCHITECTURAL LIFE SAFETY PLAN LS-7.0 WHEREBY THESE
 TWO DOORS ARE EXITING OCCUPANTS FROM INSIDE ROOM 701.01
 THROUGH THE OUTSIDE POOL DECK.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-10-12 Cont ID  
Sent By wjolin Date 2016-10-12 Time 12:00 Rev Time 0.00
Received By wjolin Date 2016-10-12 Time 11:42 Sent To B
Notes
2016-10-12 11:53:02333 FERN STREET
 PERMIT #16100054
 MASTER #15031312
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1ST FLOOR: ACCESS CONTROL CONDUIT, HARDWARE, ETC. AND
 SECURITY CAMERAS ARE NOT ESSENTIAL TO THE FUNCTION OF
 THE STAIR AND ARE NOT PERMITTED IN THE EXIT STAIRS OR
 EXIT PASSAGEWAY. PER NFPA 101 SECTION 7.1.3.2.1,
 PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT
 ENCLOSURE ASSEMBLY SHALL BE LIMITED TO DOOR ASSEMBLIES
 FROM NORMALLY OCCUPIED SPACES AND CORRIDORS, REQUIRED
 EXIT DOOR OPENINGS, ELECTRICAL CONDUIT SERVING THE EXIT
 ENCLOSURE, DUCTWORK AND EQUIPMENT NECESSARY FOR
 INDEPENDENT STAIR PRESSURIZATION, WATER OR STEAM PIPING
 NECESSARY FOR THE HEATING OR COOLING OF THE EXIT
 ENCLOSURE, SPRINKLER PIPING, STANDPIPES, AND
 PENETRATIONS FOR FIRE ALARM CIRCUITS, WHERE THE
 CIRCUITS ARE INSTALLED IN METAL CONDUIT AND THE
 PENETRATIONS ARE PROTECTED.
  
 GENERAL: PER NFPA 101 SECTION 7.2.1.6.2,
 ACCESS-CONTROLLED EGRESS DOORS ARE PERMITTED PROVIDED
 THAT ALL SEVEN OF THE FOLLOWING CRITERIA ARE MET:
 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT
 ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON
 DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER
 TO THE SENSOR.
 2. LOSS OF POWER TO THE PART OF THE ACCESS CONTROL
 SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK
 THE DOORS IN THE DIRECTION OF EGRESS.
 3. THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND
 WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS.
 4. THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 PUSH TO EXIT.
 5. WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK,
 INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS,
 AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN
 30 SECONDS.
 6. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
 7. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER
 SYSTEM OR AUTOMATIC DETECTION SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
  
 7TH FLOOR: ELEVATOR LOBBY MAG LOCK DOES NOT SHOW AN
 OCCUPANT SENSOR OR A PUSH TO EXIT BUTTON.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-03-10 Cont ID  
Sent By cpuell Date 2017-03-10 Time 16:39 Rev Time 0.00
Received By cpuell Date 2017-03-10 Time 16:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-03-10 Cont ID  
Sent By vperez Date 2017-03-10 Time 15:56 Rev Time 0.00
Received By vperez Date 2017-03-10 Time 15:56 Sent To  
Notes
2017-03-07 11:12:23RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-21 Cont ID  
Sent By vperez Date 2017-02-21 Time 10:40 Rev Time 0.00
Received By vperez Date 2017-02-21 Time 10:40 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-21 Cont ID  
Sent By shill Date 2016-11-21 Time 08:43 Rev Time 0.00
Received By shill Date 2016-10-03 Time 13:26 Sent To  
Notes
2016-11-19 11:21:5911/19 ON SH DESK
  
  
2016-11-16 07:55:4111/16 TO JW DESK TO DETERMINE WHETHER OR NOT BUILDING
 REVIEW IS REQUIRED FOR THIS ACCESS CONTROL PERMIT
  
  
  
2016-10-04 13:26:37ROUTED TO ELECTRICAL INBOX