| 2016-10-28 14:25:00 | 2ND REVIEW FBC-2014 MECHANICAL |
| | PERMIT #16100033 |
| | 10/28/16 |
| | |
| | 1) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW, PLEASE |
| | PROVIDE PLAN DESIGN CRITERIA- LIST THE CURRENT CODES |
| | AND STANDARDS THE PLANS ARE IN COMPLIANCE WITH. |
| | |
| | 2) THE REVISED PLANS HAVE NOT BEEN SIGNED: ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5 |
| | WPB AMENDMENTS TO THE FBC). |
| | |
| | 3) THE REVISED PLAN SHOWS 4500 CFMS OF SUPPLY AIR, |
| | HOWEVER THE SUBMITTED MANUFACTURER'S SPECIFICATIONS |
| | INDICATE THE SYSTEM WILL PROVIDE A MAXIMUM OF 4000 |
| | CFMS. |
| | |
| | 4) THE REVISED PLAN INDICATES "THE UNIT WILL NOT HAVE A |
| | HEATER", HOWEVER HEAT IS REQUIRED FOR OCCUPIED SPACES. |
| | PLEASE SEE SECTION 309.1 FBC-14 MECHANICAL: |
| | |
| | SECTION 309 TEMPERATURE CONTROL 309.1 SPACE-HEATING |
| | SYSTEMS. |
| | INTERIOR SPACES INTENDED FOR HUMAN OCCUPANCY SHALL BE |
| | PROVIDED WITH ACTIVE OR PASSIVE SPACE-HEATING SYSTEMS |
| | CAPABLE OF MAINTAINING A MINIMUM INDOOR TEMPERATURE OF |
| | 68?F (20?C) AT A POINT 3 FEET (914 MM) ABOVE FLOOR ON |
| | THE DESIGN HEATING DAY. THE INSTALLATION OF PORTABLE |
| | SPACE HEATERS SHALL NOT BE USED TO ACHIEVE COMPLIANCE |
| | WITH THIS SECTION. |
| | |
| | 5) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW, PROVIDE A |
| | DUCT SMOKE DETECTOR IN THE RETURN AIR SYSTEM PER |
| | SECTION 606.2.1. |
| | |
| | 6) THE ENERGYGAUGE CONSERVATION COMPLIANCE SUBMITTAL |
| | MUST BEAR THE SIGNATURE OF THE OWNER/AGENT- SEE PAGE 3 |
| | CERTIFICATIONS. |
| | |
| | 7) THE SUBMITTED ENERGY FORM INDICATES A 3-TON SYSTEM |
| | THAT IS NOT SHOWN ON THE PLAN. |
| | |
| | 8) THE SUBMITTED ENERGY FORM IS A ASHRAE 90.1 ENERGY |
| | COST BUDGET OPTION. INCLUDED IN THE MAIN DOCUMENT AND |
| | THE ATTACHED INPUT DATA REPORT ARE LIGHTING AND |
| | BUILDING CONSTRUCTION COMPONENTS DATA THAT MUST BE |
| | VERIFIED IN PLAN REVIEW AND INSPECTION. TO USE THIS |
| | OPTION PLEASE PROVIDE A PLAN THAT CORRELATES TO ALL |
| | DATA SHOWN IN THE DOCUMENTS- SEE SECTION 11.1.1 ASHRAE |
| | 90.1- 2013. |
| | |
| | 9) THE DESIGNER OR ENGINEER OF RECORD MUST COMPLETE THE |
| | MANDATORY REQUIRMENTS CHECKLIST ON PAGE OF THE ENERGY |
| | SUBMITTAL, |
| | |
| | 10) THE AHU IS LOCATED IN A WAREHOUSE THAT INCLUDES A |
| | GRADE LEVEL GARAGE DOOR- PLEASE PROVIDE PROTECTION FROM |
| | VEHICULAR DAMAGE AS REQUIRED BY SECTION 303.4. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |