Plan Review Details - Permit 16100033
Plan Review Stops For Permit 16100033
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-02-15 Cont ID  
Sent By ccole Date 2017-02-15 Time 17:25 Rev Time 0.00
Received By ccole Date 2017-02-14 Time 11:52 Sent To  
Notes
2017-02-15 11:53:06RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-02-13 Cont ID  
Sent By ccole Date 2017-02-13 Time 09:12 Rev Time 0.00
Received By ccole Date 2017-02-09 Time 16:23 Sent To  
Notes
2017-02-09 16:23:09RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-28 Cont ID  
Sent By ccole Date 2016-10-28 Time 13:35 Rev Time 0.00
Received By ccole Date 2016-10-27 Time 15:30 Sent To  
Notes
2016-10-27 15:30:12CCOLE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-04 Cont ID  
Sent By ccole Date 2016-10-04 Time 10:57 Rev Time 0.00
Received By ccole Date 2016-10-03 Time 14:42 Sent To  
Notes
2016-10-03 14:42:37ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-02-15 Cont ID  
Sent By ccole Date 2017-02-15 Time 17:25 Rev Time 0.00
Received By ccole Date 2017-02-15 Time 17:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-02-13 Cont ID  
Sent By ccole Date 2017-02-13 Time 09:07 Rev Time 0.00
Received By ccole Date 2017-02-13 Time 09:07 Sent To  
Notes
2017-02-13 09:11:563RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16100033
 2/13/17
  
 1) ENERGY CONSERVATION COMPLIANCE: PLEASE SUBMIT THE
 FULL INPUT DATA REPORT AS REQUIRED- SEE PAGE 1,
 CHECKLIST ITEM 3 OF THE SUBMITTED ENERGY GAUGE
 COMPLIANCE REPORT.
  
 2) THE DESCRIPTION OF WORK ON THE APPLICATION MUST BE
 REVISED TO INDICATE INSTALLATION OF TWO 10-TON AC
 SYSTEMS, INCLUDING DUCTWORK, AND EXHAUST VENTILATION
 FOR THE TOILET ROOMS.
  
 3) PLEASE ADJUST THE VALUE OF $12,000 LISTED ON THE
 PERMIT APPLICATION TO AN ACCURATE VALUE THAT REFLECTS
 THE TOTAL SCOPE OF THE MECHANICAL WORK INCLUDING LABOR,
 MATERIALS, EQUIPMENT, AND DESIGN FEES- SECTION
 109.3VWPB AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-10-28 Cont ID  
Sent By ccole Date 2016-10-28 Time 13:35 Rev Time 0.00
Received By ccole Date 2016-10-28 Time 13:35 Sent To  
Notes
2016-10-28 14:25:002ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16100033
 10/28/16
  
 1) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW, PLEASE
 PROVIDE PLAN DESIGN CRITERIA- LIST THE CURRENT CODES
 AND STANDARDS THE PLANS ARE IN COMPLIANCE WITH.
  
 2) THE REVISED PLANS HAVE NOT BEEN SIGNED: ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5
 WPB AMENDMENTS TO THE FBC).
  
 3) THE REVISED PLAN SHOWS 4500 CFMS OF SUPPLY AIR,
 HOWEVER THE SUBMITTED MANUFACTURER'S SPECIFICATIONS
 INDICATE THE SYSTEM WILL PROVIDE A MAXIMUM OF 4000
 CFMS.
  
 4) THE REVISED PLAN INDICATES "THE UNIT WILL NOT HAVE A
 HEATER", HOWEVER HEAT IS REQUIRED FOR OCCUPIED SPACES.
 PLEASE SEE SECTION 309.1 FBC-14 MECHANICAL:
  
 SECTION 309 TEMPERATURE CONTROL 309.1 SPACE-HEATING
 SYSTEMS.
 INTERIOR SPACES INTENDED FOR HUMAN OCCUPANCY SHALL BE
 PROVIDED WITH ACTIVE OR PASSIVE SPACE-HEATING SYSTEMS
 CAPABLE OF MAINTAINING A MINIMUM INDOOR TEMPERATURE OF
 68?F (20?C) AT A POINT 3 FEET (914 MM) ABOVE FLOOR ON
 THE DESIGN HEATING DAY. THE INSTALLATION OF PORTABLE
 SPACE HEATERS SHALL NOT BE USED TO ACHIEVE COMPLIANCE
 WITH THIS SECTION.
  
 5) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW, PROVIDE A
 DUCT SMOKE DETECTOR IN THE RETURN AIR SYSTEM PER
 SECTION 606.2.1.
  
 6) THE ENERGYGAUGE CONSERVATION COMPLIANCE SUBMITTAL
 MUST BEAR THE SIGNATURE OF THE OWNER/AGENT- SEE PAGE 3
 CERTIFICATIONS.
  
 7) THE SUBMITTED ENERGY FORM INDICATES A 3-TON SYSTEM
 THAT IS NOT SHOWN ON THE PLAN.
  
 8) THE SUBMITTED ENERGY FORM IS A ASHRAE 90.1 ENERGY
 COST BUDGET OPTION. INCLUDED IN THE MAIN DOCUMENT AND
 THE ATTACHED INPUT DATA REPORT ARE LIGHTING AND
 BUILDING CONSTRUCTION COMPONENTS DATA THAT MUST BE
 VERIFIED IN PLAN REVIEW AND INSPECTION. TO USE THIS
 OPTION PLEASE PROVIDE A PLAN THAT CORRELATES TO ALL
 DATA SHOWN IN THE DOCUMENTS- SEE SECTION 11.1.1 ASHRAE
 90.1- 2013.
  
 9) THE DESIGNER OR ENGINEER OF RECORD MUST COMPLETE THE
 MANDATORY REQUIRMENTS CHECKLIST ON PAGE OF THE ENERGY
 SUBMITTAL,
  
 10) THE AHU IS LOCATED IN A WAREHOUSE THAT INCLUDES A
 GRADE LEVEL GARAGE DOOR- PLEASE PROVIDE PROTECTION FROM
 VEHICULAR DAMAGE AS REQUIRED BY SECTION 303.4.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-10-04 Cont ID  
Sent By ccole Date 2016-10-04 Time 10:57 Rev Time 0.00
Received By ccole Date 2016-10-04 Time 09:41 Sent To  
Notes
2016-10-04 10:56:541ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16100033
 10/4/16
  
 1) PLEASE PROVIDE THE NAME OF THE PROPOSED BUSINESS ON
 THE PLAN.
  
 2) DESIGN CRITERIA: LIST THE CURRENT CODES AND
 STANDARDS USED IN THE DESIGN OF THE PROJECT.
  
 3) PROVIDE COMPLETE EQUIPMENT SCHEDULES ON THE PLAN FOR
 THE AHU AND CONDENSER, AND SUBMIT AN AHRI CERTIFICATE.
 PLEASE NOTE THE PRODUCT SUBMITTAL DOESN'T INDICATE THE
 HEATING CAPACITY.
  
 4) A DUCT SMOKE DETECTOR IS REQUIRED TO BE INSTALLED IN
 THE RETURN AIR PLENUM PER SECTION 606.2.1.
  
 5) PROVIDE DUCT HANGING AND CONNECTION DETAILS PER
 SMACNA STANDARDS
  
 6) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE
 EXTERIOR CONDENSER- SECTION 310.15.
  
 7) THE PREVIOUSLY UNCONDITIONED WAREHOUSE NOW BEING
 CONDITIONED MUST BE BROUGHT INTO FULL COMPLIANCE WITH
 THE FLORIDA ENERGY CONSERVATION CODE AS REQUIRED IN
 SECTION C101.4.5. PLEASE SUBMIT DOCUMENTATION OF
 COMPLIANCE USING ONE OF THE PATHS OR METHODS LISTED
 UNDER SECTION C401.2.
  
 8) ADVISORY NOTE: THE MAIN PLANS FOR THE PROPOSED
 CHANGE OF OCCUPANCY HAVE NOT BEEN SUBMITTED FOR REVIEW
 AND APPROVAL. FURTHER COMMENTS MAY OCCUR UPON
 RESUBMITTAL OF CORRECTED PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  