Plan Review Details - Permit 16100012
Plan Review Stops For Permit 16100012
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-27 Cont ID  
Sent By ccole Date 2016-10-27 Time 07:35 Rev Time 0.00
Received By ccole Date 2016-10-26 Time 11:52 Sent To  
Notes
2016-10-26 11:52:46CCOLE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-11 Cont ID  
Sent By ccole Date 2016-10-11 Time 11:16 Rev Time 0.00
Received By ccole Date 2016-10-03 Time 08:58 Sent To  
Notes
2016-10-04 08:59:11ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-10-27 Cont ID  
Sent By ccole Date 2016-10-27 Time 07:35 Rev Time 0.00
Received By ccole Date 2016-10-27 Time 07:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-10-11 Cont ID  
Sent By ccole Date 2016-10-11 Time 11:16 Rev Time 0.00
Received By ccole Date 2016-10-11 Time 11:16 Sent To  
Notes
2016-10-11 11:19:451ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16100012
 10/11/16
  
 1) PROVIDE THE GAGE OF STAINLESS STEEL FOR THE GREASE
 DUCT- SECTION 506.3.1.1.
  
 2) PROVIDE PLAN AND ELEVATION VIEWS OF THE GREASE DUCT
 SHOWING THE REQUIRED 18" CLEARANCES TO COMBUSTIBLES.
 CLARIFY IF IF THE DUCT WILL BE WRAPPED WITH APPROVED
 FIREWRAPPING AND HOW THE COMBUSTIBLE ROOF WILL BE
 PROTECTED AT THE DUCT PENETRATION- SECTION 506.3.6.
  
 3) PROVIDE THE HEIGHT OF EXHAUST FAN DISCHARGE OPENING
 ABOVE THE ROOF SURFACE- 506.3.13.1.
  
 4) PROVIDE A ROOF PLAN SHOWING THE REQUIRED CLEARANCES
 FOR THE EXHAUST TERMINATION AS REQUIRED IN SECTION
 506.3.13.3
  
 5) PROVIDE ENGINEERING FOR ANCHORING THE FANS AND CURBS
 TO THE ROOF STRUCTURE- SECTION 301.15.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  