Plan Review Details - Permit 16100011
Plan Review Stops For Permit 16100011
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-27 Cont ID  
Sent By ccole Date 2016-10-27 Time 09:53 Rev Time 0.00
Received By ccole Date 2016-10-26 Time 11:56 Sent To  
Notes
2016-10-26 11:56:53CCOLE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-11 Cont ID  
Sent By ccole Date 2016-10-11 Time 12:10 Rev Time 0.00
Received By ccole Date 2016-10-03 Time 08:57 Sent To  
Notes
2016-10-04 08:58:35ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-10-27 Cont ID  
Sent By ccole Date 2016-10-27 Time 09:54 Rev Time 0.00
Received By ccole Date 2016-10-27 Time 09:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-10-11 Cont ID  
Sent By ccole Date 2016-10-11 Time 12:11 Rev Time 0.00
Received By ccole Date 2016-10-11 Time 12:11 Sent To  
Notes
2016-10-11 12:14:201ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16100011
 10/11/16
  
 1) PROVIDE THE GAGE OF STAINLESS STEEL FOR THE GREASE
 DUCTS- SECTION 506.3.1.1.
  
 2) PROVIDE PLAN AND ELEVATION VIEWS OF THE GREASE DUCTS
 SHOWING THE REQUIRED 18" CLEARANCES TO COMBUSTIBLES.
 CLARIFY IF IF THE DUCTS WILL BE WRAPPED WITH APPROVED
 FIREWRAPPING AND HOW THE COMBUSTIBLE ROOF WILL BE
 PROTECTED AT THE DUCT PENETRATIONS- SECTION 506.3.6.
  
 3) PROVIDE THE HEIGHT OF EXHAUST FAN DISCHARGE OPENINGS
 ABOVE THE ROOF SURFACE- 506.3.13.1.
  
 4) PROVIDE A ROOF PLAN SHOWING THE REQUIRED CLEARANCES
 FOR THE EXHAUST TERMINATIONS AS REQUIRED IN SECTION
 506.3.13.3
  
 5) THE ENGINEERING FOR THE EXHAUST AND SUPPLY FANS IS
 INCOMPLETE: A) THE SUBMITTED NOA FOR THE EXHAUST FANS
 IS A BAD COPY AND IS NOT LEGIBLE. PLEASE PROVIDE A
 CLEAR COPY OF THE NOA WITH ALL APPLICABLE INSTALLATIONS
 DETAILS, NOTES, AND DESIGN PRESSURES CIRCLED,
 HIGHLIGHTED, OR OTHERWISE MARKED BY THE ENGINEER OF
 RECORD. B) THE SUBMITTED ENGINERERING FROM SEACOAST
 APPEAR TO
 HAVE COPIED SIGNATURES AND SEALS, AND ENGINEERING FOR
 KSF-3 WAS NOT SUBMITTED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  