Plan Review Details - Permit 16091103
Plan Review Stops For Permit 16091103
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-10-12 Cont ID  
Sent By cthroop Date 2016-10-12 Time 15:43 Rev Time 0.00
Received By cthroop Date 2016-10-12 Time 15:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-10-03 Cont ID  
Sent By cthroop Date 2016-10-03 Time 13:11 Rev Time 0.00
Received By cthroop Date 2016-10-03 Time 12:27 Sent To E
Notes
2016-10-03 13:14:33BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
 1. PLANS TO BE SIGNED BY DESIGNER.
 2. STATE GOVERNING CODES ON PLANS.
 3. PROVIDE FRAMING DETAILS WITH DEMENSIONS.
 4. REMOVE PLUMBING RISER DIAGRAHM FROM PLANS.
 5. ELECTRICAL PERMIT REQUIRED.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2016-10-12 Cont ID  
Sent By mvaldes Date 2016-10-12 Time 15:37 Rev Time 0.00
Received By mvaldes Date 2016-10-12 Time 15:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-10-03 Cont ID  
Sent By mvaldes Date 2016-10-03 Time 13:32 Rev Time 0.00
Received By mvaldes Date 2016-10-03 Time 13:24 Sent To  
Notes
2016-10-03 13:43:49REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] DESCRIBE THE EXTENT OF THE ELECTRICAL SCOPE OF WORK,
 PLANS MUST BE SIGNED WITH THE JOB ADDRESS, APPLICABLE
 CODES, AND THE PERSON RESPONSIBLE FOR THE DESIGN. FBC
 107 ( IF THE ELECTRICAL WORK IS BEING PERFORMED UNDER A
 SEPERATE PERNIT PLEASE REFERENCE THAT PERMIT # )
  
 2] SMOKE ALARMS AND CARBON MONOXIODE ALARMS REQUIRED
 PER FBC-R 314 & 315. ( A NOTE WILL SUFFICE IF EXISTING
 OTHERWISE SHOW LOCATION ON FLOOR PLANS )
  
 3] ANY NEWLY MODIFIED CIRCUIT IN AREAS SPECIFIED IN NEC
 210.52 WILL BE SUBJECT TO ARC-FAULT PROTECTION IN
 ACCORDANCE WITH NEC 210.12(B).

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-12 Cont ID  
Sent By cthroop Date 2016-10-12 Time 15:43 Rev Time 0.00
Received By cthroop Date 2016-10-12 Time 15:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-03 Cont ID  
Sent By mvaldes Date 2016-10-03 Time 13:44 Rev Time 0.00
Received By mvaldes Date 2016-09-30 Time 09:32 Sent To  
Notes
2016-10-03 09:32:51BLDG <5K