| 2016-10-04 11:35:32 | 1) INDICATE ON THE PLAN WHAT PLUMBING/ PIPING IS |
| | EXISTING AND WHAT IS NEW. THE ORIGINAL PLANS SHOWED THE |
| | PLUMBING AS EXISTING. ONLY THE BREAK ROOM SINK AND |
| | DRINKING FOUNTAIN APPEARED TO BE NEW. CLARIFY. |
| | 2) INDICATE THE WALL FINISH IN THE TOILET /BATHING |
| | ROOMS. COMPLY WITH FBC SEC. 1210.2.2. |
| | 3) THE BREAKROOM SINK SHALL COMPLY WITH SECS. 212.2, |
| | 212.3, 606 OF 2014 FAC. |
| | 4) A SERVICE SINK IS REQUIRED PER THE FPC TABLE 403.1. |
| | THERE WAS A SERVICE SINK PREVIOUSLY IN THIS STRUCTURE |
| | AND IT HAS BEEN REMOVED, CREATING A VIOLATION. |
| | 5) INDICATE ON THE PLAN IF THE WATER HEATER IS NEW OR |
| | AN EXISTING ONE BEING RELOCATED. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 6) INDICATE ON THE PLAN THE PURPOSE OF THE HUB |
| | DRAIN.WHAT IS DRAINING INTO IT? IT WILL REQUIRE A TRAP |
| | PRIMER PER THE FPC SEC.1002.4. |
| | 7) SUBMIT ELEVATION DETAILS OF THE SHOWERS. THEY SHALL |
| | COMPLY WITH FL. ACCESS. CODE SECS.608, 609, 610. |
| | 8) SHOW THE SHOWER DIMENSIONS (LXW) ON THE PLANS. |
| | COMPLY WITH FAC SEC.608.2.1. |
| | 9) THE APPLICATION STATES"PLUMBING AS PER PLANS." THE |
| | ORIGINAL PLANS DID NOT CONTAIN ANY PLUMBING DRAWINGS |
| | AND A PLUMBING REVIEW WAS NEVER PERFORMED ON THE PLANS. |
| | CLARIFY. |
| | 10) SHOW THE LENGTH AND WIDTH DIMENSIONS OF THE TOILET |
| | ROOM/BATHING ROOMS. |
| | 11) SHT. P-2 - RESTROOM REFERENCE NOTE #3 REFERS TO |
| | RESTROOMS # 104 & #106. THERE ARE NO SUCH RESTROOMS ON |
| | THE PLANS. CLARIFY. |
| | 12) CLEANOUTS ARE REQUIRED IN THE WASTE STACKS PERR THE |
| | FPC SEC. 708.3.4. |
| | 13) SIZE ALL THE VENTS ON THE SANITARY RISER DIAGRAM. |
| | 14) THE WATER RISER IS INCOMPLETE.THERE ARE LINES |
| | MISSING (HOT WATER). |
| | 15) SIZE ALL SECTIONS OF THE WATER RISER. WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | 16) THE MINIMUM SIZE OF THE COLD WATER SUPPLY TO THE |
| | WATER HEATER SHALL BE 3/4 INCH. |
| | 17) THE WATER HEATER REQUIRES A PAN AND PAN DRAIN. THE |
| | PAN DRAIN SHALL TERMINATE IN ACCORDANCE WITH FPC |
| | SEC.504.7.2. |
| | 18) SHOW THE FIXTURE CLEARANCES OF THE FIXTURES IN THE |
| | TOILET ROOMS. COMPLY WITH FAC CHAPTER 6 AND FPC SEC. |
| | 405. |
| | 19) PLACE THE TYPE OF OCCUPANCY AND OCCUPANT LOAD ON |
| | THE PLANS PER THE FBC SEC. 302 AND TABLE 1004.1.2. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |