Plan Review Details - Permit 16090983
Plan Review Stops For Permit 16090983
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-10-13 Cont ID  
Sent By rmcdouga Date 2016-10-13 Time 07:44 Rev Time 0.00
Received By rmcdouga Date 2016-10-13 Time 07:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-09-30 Cont ID  
Sent By rmcdouga Date 2016-09-30 Time 07:52 Rev Time 0.00
Received By rmcdouga Date 2016-09-30 Time 07:07 Sent To E
Notes
2016-09-30 07:52:02PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) BEFORE A POOL RESURFACING PERMIT CAN BE ISSUED A
 POOL RESURFACING NOTIFICATION FORM THAT HAS BEEN
 REVIEWED AND APPROVED BY THE PALM BEACH COUNTY HEALTH
 DEPARTMENT IS REQUIRED TO BE SUBMITTED. THE FORM THAT
 WAS SUBMITTED IS NOT SIGNED AND DATED BY THE HEALTH
 DEPARTMENT.

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2016-10-12 Cont ID  
Sent By vperez Date 2016-10-12 Time 11:19 Rev Time 0.00
Received By vperez Date 2016-10-12 Time 11:19 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-10-03 Cont ID  
Sent By vperez Date 2016-10-03 Time 15:50 Rev Time 0.00
Received By vperez Date 2016-10-03 Time 15:50 Sent To  
Notes
2016-10-03 15:51:57PLEASE CLARIFY IF EQUIPOTENTIAL BONDING WILL NOT BE
 ALTERED OR DISTURBED BY SCOPE OF POOL WORK.
  
 VAL PEREZ
 *6717

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-09-30 Cont ID  
Sent By tklarge Date 2016-09-30 Time 04:48 Rev Time 0.00
Received By tklarge Date 2016-09-30 Time 04:48 Sent To  
Notes
2016-09-30 04:49:14NO GAS WORK BEING DONE UNDER THIS PERMIT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-13 Cont ID  
Sent By rmcdouga Date 2016-10-13 Time 07:44 Rev Time 0.00
Received By rmcdouga Date 2016-10-11 Time 07:53 Sent To  
Notes
2016-10-12 07:53:28RESUB ROUTED TO VPEREZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-03 Cont ID  
Sent By vperez Date 2016-10-03 Time 15:52 Rev Time 0.00
Received By vperez Date 2016-10-03 Time 15:52 Sent To  
Notes
2016-09-28 13:35:13ROUTED TO POOL BOX

Review Stop P PLUMBING
Rev No 2 Status N Date 2016-10-13 Cont ID  
Sent By tklarge Date 2016-10-13 Time 06:24 Rev Time 0.00
Received By tklarge Date 2016-10-13 Time 06:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-09-30 Cont ID  
Sent By tklarge Date 2016-09-30 Time 04:53 Rev Time 0.00
Received By tklarge Date 2016-09-30 Time 04:49 Sent To  
Notes
2016-09-30 04:53:16INDICATE ON SCOPE OF WORK IF ANY OF THE POOL PIPING
 SYSTEM ( MAIN DRAIN, POOL PIPING, GUTTERS, ETC.) WILL
 BE AFFECTED BY THE SCOPE OF THIS WORK.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  