| Plan Review Stops For Permit 16090947 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2016-11-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-11-29 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-11-29 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2016-11-29 08:46:52 | | | | *******REVIEW IN PROGRESS******** | | | | | | | | | 1- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW FOR ALL THE SCOPE OF WORK SHOWN ON PLANS SUBMITTED. | | | VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S | | | OVERHEAD AND PROFIT AND ALL DESIGN PROFESSIONAL FEES. | | | REVISE VALUATION AS REQUIRED. OR PROVIDE COPY OF SIGNED | | | CONTRACT FOR THE CONSTRUCTION AND DESIGN PROFESSIONAL | | | SERVICES FOR BUILDING OFFICIAL REVIEW/APPROVAL. | | | | | | IF YOU HAVE ANY QUESTIONS , PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-11-28 |
Time |
18:33 |
Sent To |
|
|
| Notes |
| 2016-11-28 18:38:10 | | | | | | | | | | *****REVIEW IN PROGRESS.... | | | | | | | | | 1- PROVIDE PRODUCT APPROVAL (TWO COPIES) AS REQUIRED BY | | | FAC 61G20-3.002(33) FOR: | | | A) WINDOWS AS SPECIFIED ON PLANS. | | | | | | B) EXTERIOR DOORS AS SPECIFIED ON PLANS. | | | | | | C) WOOD SHAKES AS SPECIFIED ON PLANS. | | | | | | D) WINDOW MULLIONS AS SHOWN ON PLANS. AND, SPECIFY | | | MULLION SIZE TO VERIFY COMPLIANCE WITH THE DESIGN | | | PRESSURES. | | | | | | E) HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE | | | IMPACT GLASS. AND, PROVIDE COMPLETE INSTALLATION | | | SCHEDULE. SEE CITY SAMPLE. | | | | | | F) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS | | | AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL | | | COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR | | | ENGINEER OF RECORD TO LIST THE FLORIDA PRODUCT APPROVAL | | | NEXT TO EACH SPECIFIED CONNECTOR. | | | | | | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE | | | INSTALLATION OF THE WALL WOOD SHAKES AS REQUIRED BY | | | SEC. R703.5 FBC-RESIDENTIAL, 5TH EDITION (2014). | | | INCLUDE SPECIFICATIONS FOR WALL SHEATHING AND WATER | | | RESISTIVE BARRIER. (NO DOING SHAKES. SEE REVISED PLANS) | | | | | | 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW FOR ALL THE SCOPE OF WORK SHOWN ON PLANS SUBMITTED. | | | VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S | | | OVERHEAD AND PROFIT AND ALL DESIGN PROFESSIONAL FEES. | | | REVISE VALUATION AS REQUIRED. OR PROVIDE COPY OF SIGNED | | | CONTRACT FOR THE CONSTRUCTION AND DESIGN PROFESSIONAL | | | SERVICES FOR BUILDING OFFICIAL REVIEW/APPROVAL. | | | | | | IF YOU HAVE ANY QUESTIONS , PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-10-25 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-10-25 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-10-25 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2016-10-25 16:27:42 | RESIDENTIAL (R3) ALTERATION BUILDING, BUILDING REVIEW | | | COMMENTS. | | | CODE FBC 5TH EDITION (2014) | | | | | | 1- PROVIDE PRODUCT APPROVAL (TWO COPIES) AS REQUIRED BY | | | FAC 61G20-3.002(33) FOR: | | | A) WINDOWS AS SPECIFIED ON PLANS. | | | | | | B) EXTERIOR DOORS AS SPECIFIED ON PLANS. | | | | | | C) WOOD SHAKES AS SPECIFIED ON PLANS. | | | | | | D) WINDOW MULLIONS AS SHOWN ON PLANS. AND, SPECIFY | | | MULLION SIZE TO VERIFY COMPLIANCE WITH THE DESIGN | | | PRESSURES. | | | | | | E) HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE | | | IMPACT GLASS. AND, PROVIDE COMPLETE INSTALLATION | | | SCHEDULE. SEE CITY SAMPLE. | | | | | | F) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS | | | AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL | | | COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR | | | ENGINEER OF RECORD TO LIST THE FLORIDA PRODUCT APPROVAL | | | NEXT TO EACH SPECIFIED CONNECTOR. | | | | | | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE | | | INSTALLATION OF THE WALL WOOD SHAKES AS REQUIRED BY | | | SEC. R703.5 FBC-RESIDENTIAL, 5TH EDITION (2014). | | | INCLUDE SPECIFICATIONS FOR WALL SHEATHING AND WATER | | | RESISTIVE BARRIER. | | | | | | 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW FOR ALL THE SCOPE OF WORK SHOWN ON PLANS SUBMITTED. | | | VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S | | | OVERHEAD AND PROFIT AND ALL DESIGN PROFESSIONAL FEES. | | | REVISE VALUATION AS REQUIRED. OR PROVIDE COPY OF SIGNED | | | CONTRACT FOR THE CONSTRUCTION AND DESIGN PROFESSIONAL | | | SERVICES FOR BUILDING OFFICIAL REVIEW/APPROVAL. | | | | | | IF YOU HAVE ANY QUESTIONS , PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-11-12 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-11-12 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-11-12 |
Time |
14:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-10-17 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-10-17 |
Time |
16:58 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-10-17 |
Time |
16:58 |
Sent To |
|
|
| Notes |
| 2016-10-17 16:59:32 | PLEASE ADDRESS HISTORIC COMMENTS FOR A COMPLETE | | | ELECTRICAL REVIEW | | | | | | VAL PEREZ | | | *6717 |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-11-10 |
|
|
Cont ID |
|
| Sent By |
destabro |
Date |
2016-11-10 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
destabro |
Date |
2016-11-10 |
Time |
10:27 |
Sent To |
B |
|
| Notes |
| 2016-11-10 10:29:03 | 11/10/2016 - APPLICANT ADDRESSED PREVIOUS REVIEW | | | COMMENTS. EXISTING WINDOWS ARE NOT HISTORIC; PROPOSED | | | WHITE FRAME ALUMINUM REPLACEMENT WINDOWS WITH RAISED | | | MUNTIN PROFILES MEET DESIGN GUIDELINES FOR HISTORIC | | | DISTRICT. MATCH EXISTING WINDOW CONFIGURATIONS. DLE | | 2016-11-09 11:44:41 | ROUTED TO DESIREE ESTABROOK |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-10-04 |
|
|
Cont ID |
|
| Sent By |
destabro |
Date |
2016-10-04 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
destabro |
Date |
2016-10-04 |
Time |
10:45 |
Sent To |
B |
|
| Notes |
| 2016-10-04 10:50:55 | 10/4/2016 - THIS IS A CONTRIBUTING PROPERTY TO THE | | | GRANDVIEW HEIGHTS HISTORIC DISTRICT. PROPOSED SCOPE OF | | | WORK EXCEEDS WHAT IS ALLOWABLE AT THE PERMIT LEVEL. THE | | | RECLADDING OF THE EXTERIOR, THE REPLACEMENT OF WINDOWS, | | | AND STRUCTURAL REINFORCEMENT PLANS REQUIRE A COA AND | | | HISTORIC PRESERVATION BOARD APPROVAL. PLEASE COMPLETE | | | THE COA APPLICATION FOUND ON OUR WEBSITE FOR | | | ALTERATIONS/WINDOWS: HTTP://WPB.ORG/DEPARTMENTS/DEVELOP | | | MENT-SERVICES/HISTORIC-PRESERVATION/APPLICATIONS?PAGE=2 | | | MATERIALS RECEIVED BY OCTOBER 19TH WILL BE HEARD AT THE | | | NOVEMBER HPB MEETING. DIRECT QUESTIONS TO: DESIREE | | | ESTABROOK, HISTORIC PRESERVATION PLANNER AT | | | 561.822.1428. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-11-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-11-29 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-11-04 |
Time |
16:15 |
Sent To |
|
|
| Notes |
| 2016-11-04 16:15:59 | RESUB ROUTED TO VPEREZ |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-10-25 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-10-25 |
Time |
19:01 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-09-27 |
Time |
13:24 |
Sent To |
|
|
| Notes |
| 2016-10-17 16:22:19 | R15 | | 2016-09-28 13:24:13 | R28 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2016-10-24 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-10-24 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-10-24 |
Time |
13:20 |
Sent To |
|
|
| Notes |
|
|