Plan Review Details - Permit 16090934
Plan Review Stops For Permit 16090934
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-10-25 Cont ID  
Sent By jwitmer Date 2016-10-25 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2016-10-25 Time 06:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-11-28 Cont ID  
Sent By mvaldes Date 2016-11-28 Time 14:05 Rev Time 0.00
Received By mvaldes Date 2016-11-28 Time 14:05 Sent To  
Notes
2016-11-28 14:10:47REVISION 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO
  
 1] FBC-E SECTION C405.7.1 IN CONFORMANCE WITH ASHREA
 90.1, AT LEAST 50% OF ALL 125 VOLT, 15 & 20 AMPERE
 RECEPTACLES SHALL BE AUTOMATICALLY CONTROLLED WHERE
 INSTALLED IN PRIVATE OFFICES, OPEN OFFICES,COMPUTER
 CLASSROOMS, & MODULAR PARTITIONS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-10-24 Cont ID  
Sent By vperez Date 2016-10-24 Time 16:55 Rev Time 0.00
Received By albarran Date 2016-10-24 Time 15:17 Sent To  
Notes
2016-10-24 16:56:59ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 JOB ADDRESS: 425 24TH STREET
 DESCRIPTION: ELECTRICAL REVISION PER PLANS
 MASTER PERMIT: 16030026
 REVISION TRACK: 16090634
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS TO THE
 FBC-B REQUIRES THAT THE CONSTRUCTION DOCUMENTS BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE PROPOSED WORK AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO CODE REQUIREMENTS. (CLEARLY DEFINE YOUR
 SCOPE OF WORK ON THE PLANS). SUCH DRAWINGS SHALL
 INDICATE THE APPLICABLE DESIGN CODE, AND FURTHERMORE,
 THE DRAWINGS SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. (YOUR NAME AND
 SIGNATURE SHALL APPEAR ON ALL DOCUMENTS). THE DRAWINGS
 SHALL BE SIGNED, INCLUDE THE SCOPE OF WORK AND THE
 APPLICABLE DESIGN CODE EDITION.
 2. YOU SHALL INDICATE ON THE PLANS THE LOCATION OF ALL
 SUBPANELS HAVING ANY ASSOCIATION TO THESE PREMISES.
 3. FBC-B 1006.2. EMERGENCY LIGHTING IS REQUIRED. IN
 STORAGE ROOMS 316 & 307.
 4. FBC-E 405.7.1: AT THE LEAST 50% OF ALL 125-VOLT, 15
 AND 20-AMPERE RECEPTACLES SHALL BE AUTOMATICALLY
 CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN
 OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE
 INSTALLED IN MODULAR PARTITIONS. (SEE ASHRAE STANDARD
 90.1)
 5. NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL
 BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO
 PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP
 DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH
 ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE
 LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE
 CONSIDERED ACCESSIBLE TO PEDESTRIANS.
 6. LIGHTING ION THE MECHANICAL ROOM CAN NOT BE
 CONTROLLED ONLY BY AUTOMATIC MEANS.
 7. ALL FIRE ALARM WORK SHALL BE DONE ON A SEPARATE
 PERMIT.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-10-03 Cont ID  
Sent By pleduc Date 2016-10-03 Time 15:35 Rev Time 0.00
Received By scaldero Date 2016-10-03 Time 15:29 Sent To  
Notes
2016-10-03 15:35:08PERMIT # 16090934
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED PROVISO:
  
 1) THE SOUND SYSTEM IN THE MEDIA ROOM SHALL BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET.
 PENDING RESULTS OF FIELD INSPECTION/FIRE ALARM TEST,
 ADDITIONAL REQUIREMENTS MAY BE NEEDED. IT IS
 RECOMMENDED THAT THE SOUND SYSTEM BE TIED INTO THE FIRE
 ALARM SYSTEM VIA A RELAY, SO
 THAT UPON ACTIVATION OF THE FIRE ALARM, THE SOUND WILL
 IMMEDIATELY BE SHUT OFF.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-25 Cont ID  
Sent By gjohnson Date 2016-10-25 Time 10:07 Rev Time 0.00
Received By gjohnson Date 2016-09-26 Time 16:00 Sent To  
Notes
2016-09-27 16:01:07C10

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-10-20 Cont ID  
Sent By ccole Date 2016-10-04 Time 08:04 Rev Time 0.00
Received By ccole Date 2016-10-04 Time 07:32 Sent To  
Notes
2016-10-04 08:11:121ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16090934
 10/4/16
  
 1) M-2: PROVIDE RETURN AIR FROM THE LOBBY- SECTION
 601.5.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-10-25 Cont ID  
Sent By tklarge Date 2016-10-25 Time 10:06 Rev Time 0.00
Received By gjohnson Date 2016-10-25 Time 09:16 Sent To  
Notes
***NONE***