Plan Review Details - Permit 16090903
Plan Review Stops For Permit 16090903
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-11-22 Cont ID  
Sent By shill Date 2016-11-22 Time 12:45 Rev Time 0.00
Received By shill Date 2016-11-22 Time 12:45 Sent To  
Notes
2016-11-22 12:45:42BUILDING PROVISOS
  
 NOTE: THIS REVIEW IS FOR BUILDING# 6. BUILDING TYPE I,
 NOT FOR THE SITE PLAN, OR ANY ASSOCIATED AMENITIES.
 SURVEY AND SITE SOILS REPORT ARE FILED UNDER PERMIT
 16020377 THE RECREATION/ LEASING BUILDING.
 PLEASE NOTE : THE BUILDING OFFICIAL HAS AGREED TO THE
 BUILDING EVALUATION COST SUBMITTED TO HIM. THE 4
 SUB-PERMITS THAT ARE A NO COST IF THEY CAME IN AT THE
 TIME OF THE PRIME PERMIT ARE MECHANICAL, ELECTRICAL,
 PLUMBING & ROOFING. IF THEY COME IN AFTER THE PRIME
 PERMIT WAS CREATED THEY ARE A $80.00 SUB-PERMIT, THE
 $80.00 IS AN ADMINISTRATIVE FEE.
 THE VALUE OF THE SUB-PERMITS WHERE THE VALUE OF THE
 PERMIT IS NOT COVERED UNDER THE PRIME PERMIT NEED TO BE
 DEDUCTED FROM THE $4,000,000.00 STATED FROM BUILDING #
 3. THE PERMIT VALUE FOR BUILDING # 6 THE VALUE OF
 $3,903,245.00 IS LISTED. IT APPEARS THE VALUE OF THE
 PERMITS NOT COVERED UNDER THE MASTER HAVE THEIR VALUE
 ALREADY DELETED. PLEASE PROVIDE THE VALUE OF TOUGHS
 PERMITS. THESE PERMITS INCLUDE, FIRE SPRINKLERS, FIRE
 ALARMS, ALL LOW VOLTAGE PERMITS.
 PLEASE NOTE ALL OTHER PERMITS NOT ASSOCIATED WITH THE
 BUILDING ARE CONSIDERED PROJECT COST AND WILL BE
 PERMITTED SEPARATELY. SITE CLEARING, DEMOLITION OF
 STRUCTURES, UNDERGROUND UTILITIES, PAVING, SEAL COATING
 & STRIPING, SIDEWALKS, IRRIGATION, LANDSCAPE, POOLS,
 POOL DECK IF NOT INCLUDED IN THE POOL CONTRACT,
 FENCING, OUT BUILDINGS, SIGNAGE ETC.
 1) BUILDING PROVISO: SHORING & RESHORING PLANS TO BE
 SUBMITTED AS A DEFERRED SUBMITTAL, TO BE REVIEWED BY
 THE ENGINEER OF RECORD, APPROVED BEFORE SUBMITTAL TO
 THE BUILDING DEPARTMENT.
 2A-2E) BUILDING PROVISO: PRODUCT APPROVALS TO BE
 DEFERRED SUBMITTALS.
 2B) DEFERRED SUBMITTALS: COMPONENTS & CLADDING. 2014
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS 7 ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 2C) DEFERRED. 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 2D) DEFERRED. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING .
  
 2E) DEFERRED. FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED. IF SO
 RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A FLORIDA
 ARCHITECT OR ENGINEER.
 2F) COMPLIED. A/C STANDS.
  
 3) BUILDING PROVISO/ DEFERRED SUBMITTAL:
 3A) DEFERRED SUBMITTAL. NOTE THIS NOTE APPLIES TO
 FLOORS 2-4 ONLY. FBC-B 2014 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 3B) DEFERRED SUBMITTAL . THIS NOTE APPLIES TO WALLS AS
 WELL AS FLOORS!!! ON ALL FLOORS. WALL TYPES FOUND ON
 SHEET A8.01, THE WALL TYPES DO NOT PROVIDE THE REQUIRED
 STC RATING NOR TEST RESULTS IN ACCORDANCE WITH: FBC-B
 2014 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM
 EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45
 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90.
  
 3C) DEFERRED SUBMITTAL. THIS IS A VERY RESTRICTIVE
 REQUIREMENT!!!!!! TYPE III-TYPE V CONSTRUCTION:
 FBC-B-2014 720.2 CONCEALED INSTALLATION. INSULATING
 MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF
 ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4E) PROVISO: THE GARAGES ALL SHOW ON SHEET E1.01 &
 E5.01 CIRCUITRY TO INCLUDE A GARAGE DOOR OPENER. PLEASE
 PROVIDE COMPLIANCE WITH THE 2014 FBC-B 406.3.5
 AUTOMATIC GARAGE DOOR OPENERS. AUTOMATIC GARAGE DOOR
 OPENERS, IF PROVIDED, SHALL BE LISTED IN ACCORDANCE
 WITH UL 325. IF THERE IS A POWER FAILURE OR A
 MECHANICAL BREAKDOWN WITHOUT ANY OTHER MEANS OF EGRESS
 HOW WILL ENTRY INTO A GARAGE BE ACHIEVED. 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 5) PROVISO: THE HEIGHT OF THE SLIDING GLASS DOOR SILL
 WILL BE DETERMINED BY THE SLIDING GLASS DOOR PRODUCT
 APPROVAL AND ASSOCIATED PRESSURES. SHEET A8.02 .
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-10-26 Cont ID  
Sent By jwitmer Date 2016-10-26 Time 13:54 Rev Time  
Received By jwitmer Date 2016-10-26 Time 08:08 Sent To  
Notes
2016-10-26 13:54:17BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16090903
 ADD: 7110 OKEECHOBEE BLVD. BLDG. # 6/ BLDG. TYPE: I
 CONT: ELEV8 CONSTRUCTION CO. / STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 1ST REVIEW
 DATE: WED. OCT.26 /2016
 ACTION: DENIED
  
 1) THIS IS A THRESHOLD BUILDING AND THE THRESHOLD
 AGREEMENT WILL NEED AN ADDENDUM FOR THE ADDITIONAL
 BUILDINGS THAT ARE TO BE INSPECTED BY THE THRESHOLD
 INSPECTOR.
  
 BUILDING PROVISO
  
 NOTE: THIS REVIEW IS FOR BUILDING# 6. BUILDING TYPE I,
 NOT FOR THE SITE PLAN, OR ANY ASSOCIATED AMENITIES.
 SURVEY AND SITE SOILS REPORT ARE FILED UNDER PERMIT
 16020377 THE RECREATION/ LEASING BUILDING.
 PLEASE NOTE : THE BUILDING OFFICIAL HAS AGREED TO THE
 BUILDING EVALUATION COST SUBMITTED TO HIM. THE 4
 SUB-PERMITS THAT ARE A NO COST IF THEY CAME IN AT THE
 TIME OF THE PRIME PERMIT ARE MECHANICAL, ELECTRICAL,
 PLUMBING & ROOFING. IF THEY COME IN AFTER THE PRIME
 PERMIT WAS CREATED THEY ARE A $80.00 SUB-PERMIT, THE
 $80.00 IS AN ADMINISTRATIVE FEE.
 THE VALUE OF THE SUB-PERMITS WHERE THE VALUE OF THE
 PERMIT IS NOT COVERED UNDER THE PRIME PERMIT NEED TO BE
 DEDUCTED FROM THE $4,000,000.00 STATED FROM BUILDING #
 3. THE PERMIT VALUE FOR BUILDING # 6 THE VALUE OF
 $3,903,245.00 IS LISTED. IT APPEARS THE VALUE OF THE
 PERMITS NOT COVERED UNDER THE MASTER HAVE THEIR VALUE
 ALREADY DELETED. PLEASE PROVIDE THE VALUE OF TOUGHS
 PERMITS. THESE PERMITS INCLUDE, FIRE SPRINKLERS, FIRE
 ALARMS, ALL LOW VOLTAGE PERMITS.
 PLEASE NOTE ALL OTHER PERMITS NOT ASSOCIATED WITH THE
 BUILDING ARE CONSIDERED PROJECT COST AND WILL BE
 PERMITTED SEPARATELY. SITE CLEARING, DEMOLITION OF
 STRUCTURES, UNDERGROUND UTILITIES, PAVING, SEAL COATING
 & STRIPING, SIDEWALKS, IRRIGATION, LANDSCAPE, POOLS,
 POOL DECK IF NOT INCLUDED IN THE POOL CONTRACT,
 FENCING, OUT BUILDINGS, SIGNAGE ETC.
 1) BUILDING PROVISO: SHORING & RESHORING PLANS TO BE
 SUBMITTED AS A DEFERRED SUBMITTAL, TO BE REVIEWED BY
 THE ENGINEER OF RECORD, APPROVED BEFORE SUBMITTAL TO
 THE BUILDING DEPARTMENT.
 2A-2E) BUILDING PROVISO: PRODUCT APPROVALS TO BE
 DEFERRED SUBMITTALS.
 2B) DEFERRED SUBMITTALS: COMPONENTS & CLADDING. 2014
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS 7 ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 2C) DEFERRED. 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 2D) DEFERRED. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING .
  
 2E) DEFERRED. FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED. IF SO
 RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A FLORIDA
 ARCHITECT OR ENGINEER.
 2F) COMPLIED. A/C STANDS.
  
 3) BUILDING PROVISO/ DEFERRED SUBMITTAL:
 3A) DEFERRED SUBMITTAL. NOTE THIS NOTE APPLIES TO
 FLOORS 2-4 ONLY. FBC-B 2014 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 3B) DEFERRED SUBMITTAL . THIS NOTE APPLIES TO WALLS AS
 WELL AS FLOORS!!! ON ALL FLOORS. WALL TYPES FOUND ON
 SHEET A8.01, THE WALL TYPES DO NOT PROVIDE THE REQUIRED
 STC RATING NOR TEST RESULTS IN ACCORDANCE WITH: FBC-B
 2014 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM
 EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45
 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90.
  
 3C) DEFERRED SUBMITTAL. THIS IS A VERY RESTRICTIVE
 REQUIREMENT!!!!!! TYPE III-TYPE V CONSTRUCTION:
 FBC-B-2014 720.2 CONCEALED INSTALLATION. INSULATING
 MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF
 ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4E) PROVISO: THE GARAGES ALL SHOW ON SHEET E1.01 &
 E5.01 CIRCUITRY TO INCLUDE A GARAGE DOOR OPENER. PLEASE
 PROVIDE COMPLIANCE WITH THE 2014 FBC-B 406.3.5
 AUTOMATIC GARAGE DOOR OPENERS. AUTOMATIC GARAGE DOOR
 OPENERS, IF PROVIDED, SHALL BE LISTED IN ACCORDANCE
 WITH UL 325. IF THERE IS A POWER FAILURE OR A
 MECHANICAL BREAKDOWN WITHOUT ANY OTHER MEANS OF EGRESS
 HOW WILL ENTRY INTO A GARAGE BE ACHIEVED. 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 5) PROVISO: THE HEIGHT OF THE SLIDING GLASS DOOR SILL
 WILL BE DETERMINED BY THE SLIDING GLASS DOOR PRODUCT
 APPROVAL AND ASSOCIATED PRESSURES. SHEET A8.02 .
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-10-27 Cont ID  
Sent By vperez Date 2016-10-27 Time 14:13 Rev Time 0.00
Received By vperez Date 2016-10-27 Time 14:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-10-26 Cont ID  
Sent By vperez Date 2016-10-26 Time 16:39 Rev Time 0.00
Received By vperez Date 2016-10-26 Time 16:42 Sent To  
Notes
2016-10-26 16:43:39PLEASE NOTE THAT SHEET E503IBLG6R4-MODEL IS MISSING
 SIGN AND SEAL OF EOR. ALL OTHER SHEETS ARE VERIFIED.
  
 VAL PEREZ
 #6717

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-10-18 Cont ID  
Sent By vperez Date 2016-10-18 Time 11:36 Rev Time 0.00
Received By vperez Date 2016-10-26 Time 16:41 Sent To  
Notes
2016-10-18 12:00:14PLEASE SIGN AND SEAL PLANS
  
 VAL PEREZ
 *6717

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2016-11-04 Cont ID  
Sent By income Date 2016-11-04 Time   Rev Time 1.00
Received By mgonzale Date 2016-11-04 Time   Sent To Z
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-11-17 Cont ID  
Sent By scaldero Date 2016-11-17 Time 13:42 Rev Time 0.00
Received By scaldero Date 2016-11-17 Time 13:16 Sent To  
Notes
2016-11-17 13:34:33PERMIT #16090903
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PASSED PROVISO:
 FAILURE TO COMPLY WITH THE PROVISO COMMENTS BELOW MAY
 RESULT IN A FAILED INSPECTION.
  
 1) ENGINEERED FIRE ALARM AND FIRE SPRINKLER
 CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL
 BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT. ****THESE DOCUMENTS ARE TO
 BE SUBMITTED AS A REVISION TO THE PLAN AS SOON AS
 POSSIBLE, SO THAT THEY MAY BE REVIEWED AND APPROVED,
 PRIOR TO THE SUB-CONTRACTOR OBTAINING A PERMIT. FAILURE
 TO DO SO MAY RESULT IN THE SUBCONTRACTOR'S PERMIT
 APPLICATION BEING DENIED.*****
  
 2) PER NFPA 88A, SECTION 5.3.2: ALL ENCLOSED PARKING
 STRUCTURES SHALL BE VENTILATED BY A MECHANICAL SYSTEM
 CAPABLE OF PROVIDING A MINIMUM OF 1FT3/MIN PER FT2 OF
 FLOOR AREA. MECHANICAL VENTILATING SYSTEMS SHALL BE
 INSTALLED IN ACCORDANCE WITH NFPA 90A. DUCTWORK SHALL
 BE CONSTRUCTED OF NONCOMBUSTIBLE MATERIAL. *****THE
 ENGINEER OF RECORD SHALL SUBMIT A REVISION TO THIS
 PLAN, IN RESPONSE TO THIS COMMENT. THE RESPONSE MAY BE
 IN NARRATIVE FORM, BUT SHALL CLEARLY STATE HOW
 COMPLIANCE WITH THE ABOVE REFERENCED CAPABILITIES IS TO
 BE ACHIEVED. FAILURE TO DO SO WILL RESULT IN A FAILED
 INSPECTION.******
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2016-11-07 Cont ID  
Sent By scaldero Date 2016-11-07 Time 10:30 Rev Time 0.00
Received By scaldero Date 2016-10-27 Time 12:16 Sent To  
Notes
2016-11-07 10:31:23COMMENTS NOT YET ADDRESSED. SC

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-10-03 Cont ID  
Sent By scaldero Date 2016-10-26 Time 09:40 Rev Time 0.00
Received By scaldero Date 2016-10-03 Time 12:36 Sent To  
Notes
2016-10-03 13:00:37PERMIT # 16090903
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
 1) ENGINEERED FIRE ALARM AND FIRE SPRINKLER
 CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL
 BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT.
  
 2) ALL PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A,
 PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE,
 INCLUDING MORE SPECIFICALLY, CHAPTER 42 STORAGE
 OCCUPANCIES (PARKING STRUCTURES). THIS STANDARD SHALL
 COVER THE CONSTRUCTION AND PROTECTION OF, AS WELL AS
 THE CONTROL OF THE HAZARDS IN, OPEN AND ENCLOSED
 PARKING STRUCTURES.
  
 3) PER NFPA 88A, SECTION 5.3.2: ALL ENCLOSED PARKING
 STRUCTURES SHALL BE VENTILATED BY A MECHANICAL SYSTEM
 CAPABLE OF PROVIDING A MINIMUM OF 1FT3/MIN PER FT2 OF
 FLOOR AREA. MECHANICAL VENTILATING SYSTEMS SHALL BE
 INSTALLED IN ACCORDANCE WITH NFPA 90A. DUCTWORK SHALL
 BE CONSTRUCTED OF NONCOMBUSTIBLE MATERIAL.
  
 4) THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 5) ALL PORTABLE FIRE EXTINGUISHERS LOCATIONS SHALL BE
 CLEARLY IDENTIFIED AND INDICATED ON THE PLAN.
  
 6) ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7
 KEYWAY SYSTEM.
  
 7) ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR
 IN WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM
 TERMINAL LANDING AND THE TOP TERMINAL LANDING EXCEEDS
 25 FEET MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE
 PASSENGER ELEVATOR THAT IS OPERATIONAL AND WILL
 ACCOMMODATE AN AMBULANCE STRETCHER 76 INCHES LONG AND
 24 INCHES WIDE IN THE HORIZONTAL POSITION.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-11-22 Cont ID  
Sent By lmarchan Date 2016-11-22 Time 14:11 Rev Time 0.00
Received By lmarchan Date 2016-11-16 Time 13:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-16 Cont ID  
Sent By lmarchan Date 2016-11-16 Time 11:58 Rev Time 0.00
Received By lmarchan Date 2016-10-18 Time 14:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-18 Cont ID  
Sent By lmarchan Date 2016-10-18 Time 13:31 Rev Time 0.00
Received By lmarchan Date 2016-09-28 Time 14:44 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2016-11-09 Cont ID  
Sent By jwitmer Date 2016-11-09 Time 13:20 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2016-11-09 13:20:43P. B. COUNTY IMPACT FEES
 RECEIPT NO. 2016-1108-127
 MU-2016-027148-0000
 TOTAL: $371,636.20.
 11/07/2016 02:38:33
2016-11-09 10:50:43IMPACT FEES GIVEN TO JWITMER

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-10-26 Cont ID  
Sent By jwitmer Date 2016-10-26 Time 14:00 Rev Time 0.00
Received By jwitmer Date 2016-10-26 Time 09:17 Sent To  
Notes
2016-10-26 13:56:47BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16090903
 ADD: 7110 OKEECHOBEE BLVD. BLDG. # 6/ BLDG. TYPE: I
 CONT: ELEV8 CONSTRUCTION CO. / STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 1ST REVIEW
 DATE: WED. OCT.26 /2016
 ACTION: DENIED
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-10-27 Cont ID  
Sent By ccole Date 2016-10-27 Time 17:30 Rev Time 0.00
Received By ccole Date 2016-10-27 Time 16:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-10-17 Cont ID  
Sent By ccole Date 2016-10-17 Time 14:47 Rev Time 0.00
Received By ccole Date 2016-10-17 Time 14:46 Sent To  
Notes
2016-10-17 14:49:581ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16090903
 10/17/16
  
 1) THE MECHANICAL PLANS MUST BE DIGITALLY SIGNED AND
 SEALED BY THE ENGINEER OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2016-11-19 Cont ID  
Sent By tklarge Date 2016-11-19 Time 04:43 Rev Time 0.00
Received By tklarge Date 2016-11-19 Time 04:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2016-11-08 Cont ID  
Sent By tklarge Date 2016-11-08 Time 11:45 Rev Time 0.00
Received By tklarge Date 2016-11-08 Time 11:32 Sent To  
Notes
2016-11-08 11:32:491) SHT. A2.02 - THE ROOF PLAN IS ALMOST IMPOSSIBLE TO
 READ DUE TO THE BACKGROUND DOTS. SUBMIT A CLEAN ROOF
 PLAN FOR REVIEW. WPB AMEND. TO FBC SEC. 107.2.1. 2ND
 REQUEST.
 2) SHT. A8.04 - DETAIL # 10 - THE LOCATION OF OVERFLOW
 SCUPPERS IN THE PARAPET WALL SHALL COMPLY WITH 2014 FBC
 SEC. 1503.4.2.1.
 3) SHT. A8.03 - VANITY TOP PLAN- THERE IS A NOTE THAT
 READS "FIRST FLOOR ONLY." CLARIFY.
 4) SHT. A0.02 - THERE IS A CLOUDED NOTE AT THE TOP OF
 THE PAGE THAT READS " PROVIDE WOOD BLOCKING IN ALL
 FIRST FLOOR UNITS FOR FUTURE HANDICAP GRAB BARS". WOOD
 BLOCKING SHALL BE PROVIDED IN ALL UNITS PER THE FHA.
 5) SHT. P5.01 - RISER S/JS - THE RISER SHOWS THE MOP
 SINKS ON LEVELS #2 & #3 BUT RISER W/JS SHOWS THE WATER
 SUPPLY TO THE MOP SINKS REMOVED. CLARIFY.
 6) SHT. P1.01 - THE HUB DRAIN RECEIVING THE DISCHARGE
 FROM THE ELEVATOR SUMP SHALL BE EQUIPPED WITH A TRAP
 PRIMER PER 2014 FPC SEC.1002.4.
 7) A2.01 - REMOVE THE BACKGROUND DOTS FROM THE FLOOR
 PLAN. IT IS VERY DIFFICULT TO SE THE CLEAR FLOOR SPACE
 FOR THE FIXTURES AND COMPLIANCE WITH THE FHA.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-11-04 Cont ID  
Sent By tklarge Date 2016-11-04 Time 10:02 Rev Time 0.00
Received By tklarge Date 2016-11-02 Time 14:32 Sent To  
Notes
2016-11-04 10:05:25SHT. A2.02 - THE ROOF PLAN IS ILLEGIBLE DUE TO THE
 BACKGROUND ON THE ROOF. THE MULTIPLE DOTS ON THE ROOF
 PAN MAKES IT EXTREMELY DIFFICULT TO SEE THE ROOF
 DRAINS, NOTES, ETC. SUBMIT A CLEAN COPY OF THE ROOF
 PLAN FOR REVIEW.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-10-25 Cont ID  
Sent By tklarge Date 2016-10-25 Time 05:57 Rev Time 0.00
Received By tklarge Date 2016-10-25 Time 02:00 Sent To  
Notes
2016-10-25 05:54:411) THERE ARE ALREADY BUILDING DIVISION STAMPS ON THE
 ARCHITECTURAL PLANS WITH THE PERMIT NUMBER #15120896 ON
 THE PLANS. THESE PLANS ARE FOR AN ENTIRELY DIFFERENT
 PERMIT NUMBER. WHY IS AN EXISTING SET OF PLANS THAT HAS
 ALREADY BEEN REVIEWED AND APPROVED BEING SUBMITTED FOR
 REVIEW? CLARIFY.
 2) SHT. A4.02 - UNIT B.1 & B.1R - THE 30 X 48 INCH
 CLEAR FLOOR SPACE REQUIRED FOR THE SHOWER IN THE THE
 MASTER BATH SHALL BE FLUSH WITH THE CONTROL WALL IN
 ACCORDANCE WITH REQUIREMENT # 7 OF THE FHA GUIDELINES.
 3) SHT. A8.03 - VANITY TOP PLAN - SHOWS THE WATER
 CLOSET 1' - 6" FROM THE ADJACENT WALL AND IT IS NOTED
 THAT IT IS FOR THE FIRST FLOOR UNITS ONLY. PER THE FHA
 GUIDELINES, A WING OR PRIVACY WALL MAY OVERLAP THE
 CLEAR FLOOR SPACE FOR THE WATER CLOSET, HOWEVER IT MUST
 BE AT LEAST 33 INCHES FROM THE OPPOSITE WALL. CLARIFY
 WHY IT IS NOTED THAT IT APPLIES TO THE FIRST FLOOR
 ONLY. IT SHOULD APPLY TO ALL UNITS.
 4) SHT.A0.02 - THERE IS A CLOUDED NOTE ON THE PLANS
 THAT STATES "ALL UNITS ARE HANDICAP ACCESSIBLE
 COMPLYING WITH ...." AND STATES THAT WOOD BLOCKING WILL
 BE PROVIDED IN ALL FIRST FLOOR UNITS FOR FUTURE GRAB
 BARS. WOOD BLOCKING SHALL BE PROVIDED IN ALL COVERED
 DWELLING UNITS FOR THE FUTURE INSTALLATION OF GRAB BARS
 PER THE FHA GUIDELINES. REVISE THIS NOTE TO INCLUDDE
 ALL COVEREDD DWELLING UNITS.
 5) SHT. P6.01 - NOTE #13 STATES THAT CPVC WILL BE USED
 FOR CONDENSATE DRAIN PIPING RUNOUTS TO THE UNITS. IF
 THE A/C CLOSET IS A RETURN AIR PLENUM, THE MATERIALS
 WITHIN THE PLENUM SHALL BE NONCOMBUSTIBLE OR SHALL BE
 LISTED AS HAVING A FLAME SPREAD INDEX OF NOT MORE THAN
 25 AND A SMOKE - DEVEELOPED INDEX OFF NOT MORE THAN 50
 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723 PER
 THE 2014 FMC SEC.602.2.1. SUBMIT MANUFACTURER'S
 SPECIFICATIONS OF THE CPVC FOR REVIEW.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE OIL
 SMART PUMP SYSTEM. WPB AMEND. TO FBC SEC. 107.2.1.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2016-11-22 Cont ID  
Sent By shill Date 2016-11-22 Time 12:49 Rev Time 0.00
Received By shill Date 2016-11-22 Time 12:49 Sent To  
Notes
2016-11-22 12:50:37ROOF PRODUCT APPROVAL, ENGINEERING (IF APPLICABLE)
 REVIEWED BY DESIGNER OF RECORD REQUIRED PRIOR TO
 INSTALLATION
 REVISION FEES APPLICABLE
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-10-26 Cont ID  
Sent By jwitmer Date 2016-10-26 Time 13:57 Rev Time 0.00
Received By jwitmer Date 2016-10-26 Time 13:56 Sent To  
Notes
2016-10-26 13:58:52ROOFING PLAN REVIEW
 W. P. B. PERMIT: 16090903
 ADD: 7110 OKEECHOBEE BLVD. BLDG. # 6/ BLDG. TYPE: I
 CONT: ELEV8 CONSTRUCTION CO. / STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 1ST REVIEW
 DATE: WED. OCT.26 /2016
 ACTION: DENIED
  
 BUILDING PROVISO: PRODUCT APPROVALS TO BE DEFERRED
 SUBMITTALS. ) DEFERRED SUBMITTALS: COMPONENTS &
 CLADDING. 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS 7 ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 DEFERRED. 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED
 BY DCA RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2016-11-22 Cont ID  
Sent By shill Date 2016-11-22 Time 12:54 Rev Time 0.00
Received By shill Date 2016-11-22 Time 12:54 Sent To  
Notes
2016-10-27 17:40:22DIGITAL SIGNATURES ON MECHANICAL PLANS AND DOCUMENTS
 VERIFIED/CC
 10/27/16
2016-10-27 15:13:02HARD COPIES OF SITE SURVEY/GEO TECHNICAL REPORT/AMENDED
 THRESHOLD PLAN IN LIBRARY CP
2016-10-26 14:00:22ARCHITECTURAL & STRUCTURAL SHEETS SIGNATURE REVIEWED
 AND OK!!!! JW

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status P Date 2016-11-22 Cont ID  
Sent By shill Date 2016-11-22 Time 12:42 Rev Time 0.00
Received By shill Date 2016-11-22 Time 12:42 Sent To  
Notes
2016-11-22 12:43:16SEE THRESHOLD AGREEMENT FILED WITH 15120896
  
 A COPY SENT TO RECORDS 16090903

Review Stop Z ZONING
Rev No 1 Status P Date 2016-11-08 Cont ID  
Sent By ajones Date 2016-11-08 Time 08:55 Rev Time 0.00
Received By ajones Date 2016-11-08 Time 08:55 Sent To  
Notes
***NONE***