Plan Review Details - Permit 16090886
Plan Review Stops For Permit 16090886
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-10-18 Cont ID  
Sent By jwitmer Date 2016-10-18 Time 07:01 Rev Time 0.00
Received By jwitmer Date 2016-10-18 Time 06:40 Sent To  
Notes
2016-10-18 07:01:37BUILDING PROVISO:
 SHEET A1.00
 2014 FBC-ACCESSIBILITY CODE 703.4.
 703.4 INSTALLATION HEIGHT AND LOCATION.
 SIGNS WITH TACTILE CHARACTERS SHALL COMPLY WITH 703.4.
  
 703.4.1 HEIGHT ABOVE FINISH FLOOR OR GROUND.
 TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED 48 INCHES
 MINIMUM
 ABOVE THE FINISH FLOOR OR GROUND SURFACE, MEASURED FROM
 THE BASELINE
 OF THE LOWEST TACTILE CHARACTER AND 60 INCHES MAXIMUM
 ABOVE THE
 FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE
 BASELINE OF THE
 HIGHEST TACTILE CHARACTER.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-10-31 Cont ID  
Sent By ccole Date 2016-10-31 Time 13:56 Rev Time 0.00
Received By vperez Date 2016-10-31 Time 11:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-10-26 Cont ID  
Sent By vperez Date 2016-10-26 Time 10:21 Rev Time 0.00
Received By vperez Date 2016-10-26 Time 10:21 Sent To M
Notes
2016-10-26 10:19:542ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 PREVIOUS COMMENTS NOT ADDRESSED AND NEW DUE TO NEW
 SERVICES:
  
 1. NEW RISER SHEET SUBMITTED IS COMPLETELY NEW AND
 REQUIRES ADDITIONAL COMPLIANCE. PLEASE LABEL PER NEC
 230.2E THE TWO NEW SERVICES NOW SHOWN TO BUILDING WITH
 PERMANENT PLAQUE INDICATING PER VERBIAGE IN THE CODE. A
 NOTE WILL SUFFICE.
 2. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE
 VERBIAGE IN CODE.
 3. PER NEC 702.4B1- MANUAL TRANSFER SWITCH AND NEC
 702.7 SIGNS-SIGNAGE REQUIREMENTS TO BE MET. SEE CODE;
 ADD NOTE TO RISER.
 1. PLEASE ADD A GENERAL NOTE TO INDICATED REQUIRED
 SEPARATE PERMITS FOR LOW VOLTAGE SYSTEMS AND SITE
 LIGHTING. FBC 107.3.5
 2. PER FBC EC 405.7- A MINIMUM OF 50% OF ALL 125V, 15
 AND 20AMP RECEPTACLES SHALL BE AUTOMATICALLY CONTROLLED
 WHERE INSTALLED IN PRIVATE OR OPEN OFFICES AND COMPUTER
 CLASSROOMS. THIS INCLUDES MODULAR PARTITIONS TOO. SHOW
 COMPLIANCE ACCORDINGLY.
 3. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-09-27 Cont ID  
Sent By vperez Date 2016-09-27 Time 11:11 Rev Time 0.00
Received By vperez Date 2016-09-27 Time 10:02 Sent To  
Notes
2016-09-27 11:12:06INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
  
 1. PLEASE ADD A GENERAL NOTE TO INDICATED REQUIRED
 SEPARATE PERMITS FOR LOW VOLTAGE SYSTEMS. FBC 107.3.5
 2. PER FBC EC 405.7- A MINIMUM OF 50% OF ALL 125V, 15
 AND 20AMP RECEPTACLES SHALL BE AUTOMATICALLY CONTROLLED
 WHERE INSTALLED IN PRIVATE OR OPEN OFFICES AND COMPUTER
 CLASSROOMS. THIS INCLUDES MODULAR PARTITIONS TOO. SHOW
 COMPLIANCE ACCORDINGLY.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-10-03 Cont ID  
Sent By scaldero Date 2016-10-03 Time 15:10 Rev Time 0.00
Received By scaldero Date 2016-10-03 Time 14:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-10-31 Cont ID  
Sent By ccole Date 2016-10-31 Time 13:56 Rev Time 0.00
Received By ccole Date 2016-10-27 Time 14:48 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-26 Cont ID  
Sent By ccole Date 2016-10-26 Time 15:34 Rev Time 0.00
Received By ccole Date 2016-10-25 Time 16:14 Sent To  
Notes
2016-10-25 16:14:42VPEREZ DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-21 Cont ID  
Sent By gjohnson Date 2016-10-21 Time 16:06 Rev Time 0.00
Received By gjohnson Date 2016-09-23 Time 15:52 Sent To  
Notes
2016-09-23 15:52:52B34

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-10-18 Cont ID  
Sent By jwitmer Date 2016-10-18 Time 06:46 Rev Time 0.00
Received By jwitmer Date 2016-10-18 Time 06:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-10-31 Cont ID  
Sent By ccole Date 2016-10-31 Time 13:44 Rev Time 0.00
Received By ccole Date 2016-10-31 Time 13:43 Sent To  
Notes
2016-10-31 13:56:03 
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-10-26 Cont ID  
Sent By ccole Date 2016-10-26 Time 15:34 Rev Time 0.00
Received By ccole Date 2016-10-26 Time 15:34 Sent To  
Notes
2016-10-26 15:34:452ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16090886
 10/3/2016
  
 1) PROVIDE A CHILLED WATER PIPING PLAN SHOWING ALL NEW
 PIPING RUNS AND POINTS OF CONNECTIONS TO EXISTING
 PIPING. PLEASE INCLUDE DETAILS- TYPE AND SIZE OF PIPES,
 AND PIPE INSULATION.
  
 2) ENERGY FORM C402-2014: A) THE FORM MUST BE SIGNED BY
 THE PERSON WHO PREPARED IT, AND BY THE OWNER/AGENT. B)
 SHOW COMPLIANCE DATA FOR THE CHILLED WATER PIPING, FAN
 COIL UNITS, AND THE NEW REPLACEMENT WINDOWS- SECTION
 C101.4.3 FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-10-03 Cont ID  
Sent By ccole Date 2016-10-03 Time 09:34 Rev Time 0.00
Received By ccole Date 2016-10-03 Time 08:18 Sent To  
Notes
2016-10-03 09:43:151ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16090886
 10/3/2016
  
 1) PROVIDE A CHILLED WATER PIPING PLAN SHOWING ALL NEW
 PIPING RUNS AND POINTS OF CONNECTIONS TO EXISTING
 PIPING. PLEASE INCLUDE DETAILS- TYPE AND SIZE OF PIPES,
 AND PIPE INSULATION.
  
 2) ENERGY FORM C402-2014: A) THE FORM MUST BE SIGNED BY
 THE PERSON WHO PREPARED IT, AND BY THE OWNER/AGENT. B)
 SHOW COMPLIANCE DATA FOR THE CHILLED WATER PIPING, FAN
 COIL UNITS, AND THE NEW REPLACEMENT WINDOWS- SECTION
 C101.4.3 FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-10-21 Cont ID  
Sent By gjohnson Date 2016-10-21 Time 16:06 Rev Time 0.00
Received By gjohnson Date 2016-10-21 Time 16:06 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy