Plan Review Details - Permit 16090832
Plan Review Stops For Permit 16090832
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date 2016-10-27 Cont ID  
Sent By shill Date 2016-10-27 Time 11:26 Rev Time 0.00
Received By shill Date 2016-10-27 Time 11:26 Sent To  
Notes
2016-10-27 11:26:38PER EMAIL FROM SYBILLE WELTER
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-01-19 Cont ID  
Sent By shill Date 2017-01-19 Time 17:38 Rev Time 0.00
Received By shill Date 2017-01-17 Time 15:03 Sent To  
Notes
2017-01-19 17:39:11****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
  
 AFTER ISSUANCE, COLOR COPY ONE SET FOR THE RESIDENT
 INSPECTOR. OR, BLACK AND WHITE COPY, AND BRING TO
 BUILDING DIVISION TO BE RED STAMPED WITH THE PERMIT
 NUMBER.
  
 PER ARCHITECT, THE AREA CALLED A "STAGE" (SHEET A221,
 2ND FLOOR) IS A RAISED AREA TO PROVIDE PROTECTION TO A
 LARGE DISPLAY SCREEN (ALSO SEE SHEET A222). IT IS NOT
 USED AS A STAGE. IF USE IS CHANGED TO BE A PLATFORM FOR
 PEOPLE, VERTICAL ACCESSIBILITY IS REQUIRED.
  
 ALL REQUIRED PRODUCT APPROVALS NOT SUBMITTED AND
 REVIEWED PRIOR TO ISSUANCE ARE TO BE SUBMITTED FOR
 REVIEW PRIOR TO INSTALLATION. PRIOR TO SUBMISSION TO
 THE BUILDING DIVISION THEY ARE TO BE REVIEWED BY
 DESIGNER OF RECORD, FBC 107.
  
 SEPARATE PERMITS REQUIRED FOR SIGNS, PARKING LOT, SITE
 LIGHTING, ETC. (ALL ITEMS OUTSIDE OF THE BUILDING
 ENVELOPE).
  
 A PRE-CONSTRUCTION MEETING WITH KEN CONRAD, CHIEF
 BUILDING INSPECTOR, THE CONTRACTOR, AND THE RESIDENT OR
 SPECIAL INSPECTOR IS REQUIRED. PLEASE CONTACT KEN
 CONRAD, 561-805-6666 TO SCHEDULE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-12-09 Cont ID  
Sent By shill Date 2016-12-09 Time 06:29 Rev Time 0.00
Received By shill Date 2016-12-08 Time 07:05 Sent To  
Notes
2016-12-09 06:30:01****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. LS100, EGRESS WIDTH TABULATIONS, HAS A TYPO (BOTH
 FIRST AND SECOND FLOOR), 15SF PER PERSON FOR STORAGE,
 FBC TABLE 1004.1.2.
  
 THIS WAS REVISED, BUT RATIONALE FOR S2 RATHER THAN S1
 OCCUPANCY IS NOT CLEAR. S2 IS FOR NON COMBUSTIBLE
 STORAGE. REVISE PLAN TO STATE TYPE OF MATERIALS STORED
 IN EACH STORAGE AREA (OR ONE NOTE IF ALL ARE THE SAME),
 OR REVISE TO S1 WHICH INCLUDES COMBUSTIBLE STORAGE.
  
 2. COMMENT FROM FIRST REVIEW: LS100, REVISE TO SHOW
 COMPLIANCE WITH FBC TABLE 503, FBC 506. COMPLIANCE FOR
 THE ENTIRE BUILDING, ALL OCCUPANCIES, SHOULD BE SHOWN.
 INCREASES PER FBC 506 ARE TO BE SHOWN.
  
 FOR EXAMPLE, A101 SHOWS BUILDING AREA AS 82,003, LS100
 SHOWS BUILDING AREA AS 71,055. LS100 PROJECT SUMMARY
 DOES NOT INCLUDE S1 OCCUPANCY.
  
 2ND REVIEW, IT IS NOT CLEAR HOW THIS HAS BEEN
 ADDRESSED. THE SPRINKLER INCREASE FOR BUSINESS WAS
 SHOWN, BUT THIS IS A MIXED USE BUILDING AND BUSINESS IS
 NOT THE MOST STRINGENT CONDITION. A3 (WITH SPRINKLER
 INCREASE) HAS A LIMIT OF 28,500 AND S1 ALLOWS 52,500.
 AS BUILDING AREA DOES NOT COMPLY WITH THE MOST
 STRINGENT, EITHER OCCUPANCIES ARE TO BE SEPARATED OR
 FRONTAGE INCREASE IS NEEDED, FBC 506.2.
  
 THE SQUARE FOOT AREAS FOR ASSEMBLY AND S1 ARE NOT ON
 THE PLAN, SO COMPLIANCE WITH FBC 508.2.1 (ACCESSORY
 OCCUPANCIES) CANNOT BE DETERMINED.
  
 THE GENERATOR BUILDING WAS NOT INCLUDED, SEE FBC 703.5.
 IT IS NOT CLEAR IF THIS WILL BE INCLUDED IN THE
 BUILDING AREA CALCULATIONS OR IF COMPLIANCE WITH
 DISTANCE TO AN ASSUMED PROPERTY LINE IS REQUIRED TO BE
 SHOWN.
  
 3-6. AS DISCUSSED, THE USE OF 100 SF PER PERSON FOR AN
 OVERALL OCCUPANT LOAD IS ACCEPTABLE WITH THE EXCEPTION
 OF ASSEMBLY AREAS SUCH AS THE PRESS ROOM WHICH WILL
 SERVE OCCUPANTS FROM OUTIDE OF THE BUILDING. LS201,
 THIS AREA IS SHOWN AS 100 SF PER PERSON. AS DISCUSSED,
 THE ASSEMBLY AREAS SUCH AS THE SMALL CONFERENCE ROOMS
 CAN BE CALCULATED AT 100 SF PER PERSON IF THE OCCUPANTS
 ARE FROM THE ADJACENT OFFICE AREAS. REVISE THE MEDIA
 ROOM TO 15 SF PER PERSON AS WELL AS ANY OTHER AREAS
 INTENDED TO INCLUDE ADDITIONAL OCCUPANTS.
  
 5. OK
  
 6. CLARIFY WHICH ROOMS WERE CONSIDERED ASSEMBLY
 OCCUPANCY WHEN CALCULATING THE TOTAL SF AREA AND
 OCCUPANT LOAD IN EGRESS WIDTH TABULATIONS ON LS100,
 FBC107, FS553.
 2ND REVIEW, ALTHOUGH THE OVERALL OCCUPANT LOAD IS
 CALCULATED AT 100 SF PER PERSON GROSS, INCLUDING
 ASSEMBLY AREAS, A TOTAL ASSEMBLY OCCUPANT LOAD IS
 REQUIRED TO DETERMINE WHETHER OR NOT THIS IS A
 THRESHOLD BUILDING. PLEASE SEND THE TOTAL SQUARE FEET
 OF ASSEMBLY AREA VIA EMAIL SO THIS CAN BE DETERMINED.
  
 7-8. OK
  
 9. LS201, NO INFORMATION WAS PROVIDED REGARDING THE
 EXISTING COMMAND CENTER AND HOW EXITING WILL BE
 AFFECTED BY THE PROPOSED NEW COMMAND CENTER. PROVIDE
 INFORMATION REGARDING THE DOORS WHICH PREVIOUSLY LED
 DIRECTLY TO THE OUTDOORS WHICH WILL NOW LEAD TO THE NEW
 COMMAND CENTER. IF THESE DOORS ARE EXIT DOORS, HOW WILL
 TRAVEL DISTANCE BE AFFECTED? WHAT OCCUPANCY
 CLASSIFICATIONS DO THESE DOORS SERVE?
  
 2ND REVIEW, THE RESPONSE LETTER INFORMATION ADDRESSES
 THIS ISSUE. AS THE RESPONSE LETTER IS NOT A PART OF THE
 PERMIT RECORD (AND IS NOT SIGNED AND SEALED), REVISE
 THE PLAN TO INCLUDE THIS INFORMATION. THE PLAN
 CURRENTLY SHOWS THAT THE EXIT DOOR IS STILL BEING USED
 AS AN EXIT DOOR, SHOWS ONLY A PARTIAL TRAVEL DISTANCE,
 AND DOES NOT REFERENCE THE OTHER EXITS. REVISE TO
 INCORPORATE THE INFORMATION IN THE RESPONSE LETTER INTO
 THE PLAN.
  
 10-11. OK
  
 12. OCCUPANT LOAD TOTALS DO NOT APPEAR CORRECT. FOR
 INSTANCE, LS202 SHOWS OCCUPANT LOAD FOR THE BUSINESS
 AREA WHICH IS DIVIDED INTO ROOMS CALCULATED ON THE
 TOTAL RATHER THAN BY ROOM. FBC 107 AND FBC CHAPTER 10,
 AN ACCURATE OCCUPANT LOAD IS REQUIRED FOR C.O., TO
 CONFIRM COMPLIANCE WITH LIFE SAFETY REQUIREMENTS, AND
 FOR THRESHOLD BUILDING DETERMINATION. REVISE PLAN.
  
 13. FBC 1014.2, CLARIFY THE NUMBER OF OCCUPANTS
 CALCULATED TO TRAVEL THROUGH THE BREAK ROOM TO REACH
 THE REQUIRED EXIT. HOW WILL THE EGRESS PATH BE KEPT
 CLEAR OF TABLES AND CHAIRS? ASSEMBLY IS CONSIDERED A
 HIGHER RISK THAN BUSINESS. REVISE PLAN TO CLARIFY HOW
 COMPLIANCE WITH THE REQUIREMENT THAT A DISCERNIBLE PATH
 OF EGRESS TRAVEL TO AN EXIT WILL BE MET. FEEL FREE TO
 CONTACT ME TO DISCUSS.
  
 2ND REVIEW, THE LIFE SAFETY PLAN IS NOT CLEAR ON THE
 NUMBER OF OCCUPANTS IN EACH AREA AND THE NUMBER OF
 OCCUPANTS WHICH EACH EXIT IS TO SERVE.
  
 THIS AREA WAS REVISED TO SHOW 46 OCCUPANTS, BUT IT
 APPEARS THAT THE 98 FROM THE CONTROL THEATER WILL ALSO
 EXIT THROUGH THIS AREA. THE OCCUPANT LOAD FOR THE
 THEATER WAS NOT PROVIDED. IS IT 98 TOTAL, OR 98 TIMES
 3? IF 98 TOTAL, A THIRD SHOULD BE SHOWN AT EACH EXIT
 RATHER THAN 98.
  
 ADDING UP ALL OF THE DOOR EXIT REQUIRED NUMBERS GIVES A
 TOTAL OF 341, BUT THE TOTAL OCCUPANT LOAD FOR THE FLOOR
 IS 467 PLUS THE NUMBER OF OCCUPANTS FROM THE EXISTING
 BUILDING AND THE SECOND FLOOR, APPEARS TO BE A TOTAL OF
 APPROXIMATELY 500 FOR FIRST FLOOR OCCUPANTS. THE
 THEATER SHOWS TWO CORRIDORS AS EXITS, APPEARS TO SHOW
 98 EACH CORRIDOR, BUT IS NOT CLEAR WHERE THESE PEOPLE
 EXIT.
  
 THE TWO STAIRS ARE SHOWN AS SERVING 48 EACH, BUT THEY
 ARE BOTH USED AS EXITS FOR THE FIRST FLOOR AND THE
 SECOND FLOOR WHICH HAS AN OCCUPANT LOAD OF 244.
  
 IF EACH STAIR DOOR SERVES 48 OCCUPANTS FROM THE FIRST
 FLOOR AND 122 FROM THE SECOND, 34 INCHES OF DOOR WIDTH
 IS REQUIRED, 33 IS PROVIDED.
  
 14-18. OK
  
 19. THREE SETS OF PLANS REQUIRED; SEE THRESHOLD REVIEW.
  
 THREE SETS OF ALL PERMIT DOCUMENTS REQUIRED.
  
 20. A CONSTRUCTION TRAILER IS SHOWN ON SHEET M104. THIS
 REQUIRES A SEPARATE PERMIT AND HAS NOT BEEN REVIEWED AT
 THIS TIME.
  
 21. OK
  
 22. THE BUILDING OFFICIAL HAS REVIEWED THE LETTER
 REGARDING THE LACK OF ACCESSIBLE BATHROOMS ON THE FIRST
 FLOOR ADJACENT TO THE THEATER. AS THESE BATHROOMS ARE
 NOT NEAR THE OTHERS ON THE FLOOR, IT IS NOT CONSIDERED
 A CLUSTER. DUE TO THE DISTANCE, PROVIDING ACCESSIBLE
 BATHROOMS IN ANOTHER AREA IS NOT CONSIDERED EQUIVALENT
 FACILITATION.
  
 NOTE THAT ALL COMMENTS REGARDING ACCESSIBILITY ARE
 APPLICABLE FOR BUILDING REVIEW AND MUST BE ADDRESSED.
  
 23. THE LIFE SAFETY PAGES ARE ILLEGIBLE, FBC 107. THEY
 HAVE HATCHING OVER ALL OF THE AREAS, MAKING IT VERY
 DIFFICULT TO READ, AND NOW HAVE ADDITIONAL INFORMATION
 (CIRCLES) OVER THE FLOOR PLAN. PLEASE PROVIDE LEGIBLE
 LIFE SAFETY PLANS. FOR BUILDING REVIEW, NEITHER THE
 HATCHING NOR THE CIRCLES ARE NECESSARY. IF REQUIRED FOR
 ANOTHER TRADE, PLEASE PROVIDE THIS INFORMATION AS
 SEPARATE SHEETS.
  
 24. AS DISCUSSED, AS THE 2ND FLOOR "STAGE" IS NOT AN
 OCCUPIABLE SPACE, REVISE THE DESIGNATION FOR THIS AREA
 (ELEVATED PROTECTIVE BARRIER).
  
 25. WHEN RESUBMITTING, PLEASE CHANGE ONLY SHEETS WHICH
 HAVE CHANGED.
  
 26. THIS PERMIT WILL BE ISSUED WITH PROVISO:
  
 ALL REQUIRED PRODUCT APPROVALS NOT SUBMITTED AND
 REVIEWED PRIOR TO ISSUANCE ARE TO BE SUBMITTED FOR
 REVIEW PRIOR TO INSTALLATION. PRIOR TO SUBMISSION TO
 THE BUILDING DIVISION THEY ARE TO BE REVIEWED BY
 DESIGNER OF RECORD, FBC 107.
  
 SEPARATE PERMITS REQUIRED FOR SIGNS, PARKING LOT, SITE
 LIGHTING, ETC. (ALL ITEMS OUTSIDE OF THE BUILDING
 ENVELOPE).
  
 A PRE-CONSTRUCTION MEETING WITH KEN CONRAD, CHIEF
 BUILDING INSPECTOR, THE CONTRACTOR, AND THE RESIDENT OR
 SPECIAL INSPECTOR IS REQUIRED. PLEASE CONTACT KEN
 CONRAD, 561-805-6666 TO SCHEDULE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-10-18 Cont ID  
Sent By shill Date 2016-10-18 Time 13:24 Rev Time 0.00
Received By shill Date 2016-10-12 Time 07:18 Sent To  
Notes
2016-10-18 13:24:58****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. LS100, EGRESS WIDTH TABULATIONS, HAS A TYPO (BOTH
 FIRST AND SECOND FLOOR), 15SF PER PERSON FOR STORAGE,
 FBC TABLE 1004.1.2.
  
 2. LS100, REVISE TO SHOW COMPLIANCE WITH FBC TABLE 503,
 FBC 506. COMPLIANCE FOR THE ENTIRE BUILDING, ALL
 OCCUPANCIES, SHOULD BE SHOWN. INCREASES PER FBC 506 ARE
 TO BE SHOWN.
  
 FOR EXAMPLE, A101 SHOWS BUILDING AREA AS 82,003, LS100
 SHOWS BUILDING AREA AS 71,055. LS100 PROJECT SUMMARY
 DOES NOT INCLUDE S1 OCCUPANCY.
  
 3. LS201, MEDIUM CONFERENCE ROOM IS SHOWN AS 4,641 SF
 ON THIS PAGE, APPEARS THAT THIS IS NOT CORRECT. REVISE
 OR CLARIFY, FBC 107.
  
 4. LS201, MEDIUM CONFERENCE ROOM OCCUPANT LOAD WAS
 CALCULATED AT 100 SF PER PERSON. CONFERENCE ROOMS ARE
 TYPICALLY ASSEMBLY WITH 15 SF PER PERSON.
  
 EITHER REVISE OR SEND A LETTER VIA EMAIL WHICH EXPLAINS
 RATIONALE. SEE PREVIOUS COMMENT. IF THIS ROOM IS
 INTENDED TO BE 4,641 SF, THE OCCUPANT LOAD SHOULD BE
 310 AND REQUIRES ANOTHER EXIT. IF THIS ROOM IS 384 SF,
 AN OCCUPANT LOAD OF 4 (100 SF PER PERSON) IS NOT
 CORRECT AS TEN CHAIRS ARE SHOWN.
  
 5. LS201, 202, APPLICABLE TO ALL CONFERENCE ROOMS AND
 BREAK ROOMS, ALSO POSSIBLY ROOMS 103 AND 104 MEDIA
 ROOMS, THESE AREAS ARE TYPICALLY TREATED AS ASSEMBLY
 OCCUPANCY, 15 SF PER PERSON. REVISE PLAN OR CONTACT ME
 TO DISCUSS, FBC TABLE 1004.1.2. 100 SF PER PERSON DOES
 NOT APPEAR TO BE AN ADEQUATE DESIGN OCCUPANT LOAD FOR
 THESE SPACES.
  
 5. LS201, FITNESS ROOM OCCUPANT LOAD WAS CALCULATED AT
 100 SF PER PERSON. SEE FBC TABLE 1004.1.2, 50 SF PER
 PERSON REQUIRED.
  
 6. CLARIFY WHICH ROOMS WERE CONSIDERED ASSEMBLY
 OCCUPANCY WHEN CALCULATING THE TOTAL SF AREA AND
 OCCUPANT LOAD IN EGRESS WIDTH TABULATIONS ON LS100,
 FBC107, FS553.
  
 7. LS201, ROOM 192, FBC 1008.1.10, REVISE PLAN TO
 CLARIFY ELECTRIC ROOM FUNCTION. IF PANIC BARS ARE NOT
 REQUIRED, REVISE PLAN TO INDICATE THAT THIS ROOM DOES
 NOT CONTAIN EQUIPMENT AS DESCRIBED IN THIS SECTION. IF
 PANIC BARS ARE REQUIRED DUE TO EQUIPMENT, REVISE PLAN
 TO NOTE AND REVISE TO OUTSWING DOORS.
  
 8. LS201, ROOM 105 IS ASSEMBLY OCCUPANCY WITH AN
 OCCUPANT LOAD OVER 49. EXIT STRATEGY IS NOT CLEAR. THE
 SE AND SW DOORS APPEAR TO LEAD TO THE SAME EXIT DOOR
 AND NEITHER HAS EXIT LIGHTS. THE DOOR AT THE REAR LEADS
 TO A GREEN ROOM, PURPOSE UNKNOWN WITH NO OCCUPANT LOAD
 SHOWN, WITH AN INSWING DOOR.
  
 REVISE PLAN TO CLARIFY EXIT STRATEGY, INCLUDE EXIT
 LIGHTS AS NEEDED, NUMBER OF OCCUPANTS FOR EACH SPACE.
  
 NOTE THAT PER FBC 1008.1.10 ALL DOORS IN THE MEANS OF
 EGRESS FOR ASSEMBLY TO HAVE PANIC DEVICES, FBC 1004.6.
 THE DOOR SCHEDULE WAS NOT REVIEWED AT THIS TIME AS
 EGRESS PATH IS NOT CLEAR.
  
 9. LS201, NO INFORMATION WAS PROVIDED REGARDING THE
 EXISTING COMMAND CENTER AND HOW EXITING WILL BE
 AFFECTED BY THE PROPOSED NEW COMMAND CENTER. PROVIDE
 INFORMATION REGARDING THE DOORS WHICH PREVIOUSLY LED
 DIRECTLY TO THE OUTDOORS WHICH WILL NOW LEAD TO THE NEW
 COMMAND CENTER. IF THESE DOORS ARE EXIT DOORS, HOW WILL
 TRAVEL DISTANCE BE AFFECTED? WHAT OCCUPANCY
 CLASSIFICATIONS DO THESE DOORS SERVE?
  
 10. LS201, EXITING FOR THE UPS ROOM IS NOT CLEAR. ONE
 DOOR LEADS TO THE EXISTING COMMAND CENTER, THE OTHER
 DOOR LEADS THROUGH THE ELECTRICAL ROOM. FBC 1014.2,
 REVISE PLAN TO SHOW COMPLIANCE.
  
 11. LS202, THE WEST CONFERENCE ROOM IS NOT LABELED AND
 LACKS AN OCCUPANT LOAD, FBC 107, SEE ALSO OTHER
 COMMENTS REGARDING OCCUPANT LOAD. REVISE PLAN TO
 INCLUDE ALL OCCUPANT LOAD FOR ALL SPACES.
  
 12. OCCUPANT LOAD TOTALS DO NOT APPEAR CORRECT. FOR
 INSTANCE, LS202 SHOWS OCCUPANT LOAD FOR THE BUSINESS
 AREA WHICH IS DIVIDED INTO ROOMS CALCULATED ON THE
 TOTAL RATHER THAN BY ROOM. FBC 107 AND FBC CHAPTER 10,
 AN ACCURATE OCCUPANT LOAD IS REQUIRED FOR C.O., TO
 CONFIRM COMPLIANCE WITH LIFE SAFETY REQUIREMENTS, AND
 FOR THRESHOLD BUILDING DETERMINATION. REVISE PLAN.
  
 13. FBC 1014.2, CLARIFY THE NUMBER OF OCCUPANTS
 CALCULATED TO TRAVEL THROUGH THE BREAK ROOM TO REACH
 THE REQUIRED EXIT. HOW WILL THE EGRESS PATH BE KEPT
 CLEAR OF TABLES AND CHAIRS? ASSEMBLY IS CONSIDERED A
 HIGHER RISK THAN BUSINESS. REVISE PLAN TO CLARIFY HOW
 COMPLIANCE WITH THE REQUIREMENT THAT A DISCERNIBLE PATH
 OF EGRESS TRAVEL TO AN EXIT WILL BE MET. FEEL FREE TO
 CONTACT ME TO DISCUSS.
  
 14. REVISE PLAN TO CLARIFY PURPOSE OF THE STAGE SHOWN
 ON THE FIRST FLOOR. VERTICAL ACCESSIBILITY MAY APPLY,
 FBC 5TH EDITION ACCESSIBILITY 201.1.1, 203.9. IF
 EXCEPTIONS ARE APPLICABLE, REVISE PLAN TO INCLUDE
 EXCEPTION(S).
  
 15. A321, A322, A323, TEXT IS NOT LEGIBLE IN SEVERAL
 LOCATIONS; CHECK ALL AND PROVIDE LEGIBLE TEXT.
  
 16. A760, THE GRAB BAR IS TO BE INSTALLED 33 TO 36
 INCHES MEASURED TO THE TOP OF THE BAR, FBC 5TH EDITION
 ACCESSIBILITY 609.4. THE DETAILS DO NOT COMPLY AS THE
 BAR IS SHOWN TOO HIGH, REVISE ALL AFFECTED DETAILS.
  
 17. A800 SHOWS CARD READERS ON SOME DOORS. A SEPARATE
 PERMIT IS REQUIRED FOR ACCESS CONTROL. THIS ITEM IS NOT
 BEING REVIEWED AT THIS TIME.
  
 18. S001, TABLE 1607.1, REVISE TO INCLUDE ASSEMBLY AREA
 LIVE LOAD.
  
 19. THREE SETS OF PLANS REQUIRED; SEE THRESHOLD REVIEW.
  
 20. A CONSTRUCTION TRAILER IS SHOWN ON SHEET M104. THIS
 REQUIRES A SEPARATE PERMIT AND HAS NOT BEEN REVIEWED AT
 THIS TIME.
  
 21. SEE IMPACT FEE REVIEW. THIS IS TO BE PAID PRIOR TO
 PERMIT ISSUANCE.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-01-14 Cont ID  
Sent By vperez Date 2017-01-14 Time 14:09 Rev Time 0.00
Received By vperez Date 2017-01-14 Time 14:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-12-01 Cont ID  
Sent By vperez Date 2016-12-01 Time 12:10 Rev Time 0.00
Received By vperez Date 2016-12-01 Time 12:09 Sent To  
Notes
2016-12-01 12:09:542ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 PROVISO FOR NEW COMMENT:
  
  
 1. GFCI PROTECTION REQUIRED FOR ALL 15A-20A 125V
 RECEPTACLES PER NEC 210.8B2 IN LOCKER AREA AND DRINKING
 FOUNTAIN NEC 422.52
  
 1ST REVIEW COMMENT TO BE ADDRESSED:
 10. MAIN ELECTRICAL ROOMS MUST COMPLY WITH NEC
 110.26C2, THERE SHALL BE ONE ENTRANCE AT EACH END OF
 THE WORKING SPACE. SHOW TWO MEANS OF EGRESS THAT
 COMPLIES WITH EGRESS REQUIREMENTS, AS ONE OF THE DOOR
 OPENS INTO A HAZARD AREA AND DOES NOT HAVE THE
 CLEARANCE REQUIREMENTS. ALSO NEC 110.26C3 REQUIRES
 PERSONNEL DOORS TO BE EQUIPPED WITH PANIC HARDWARE AND
 OPEN IN THE DIRECTION OF EGRESS. DOOR MUST SWING IN THE
 DIRECTION OF EGRESS. (TO COMPLY WITH NEC 110.26C3
 DOUBLE DOORS ADJACENT TO FACP MUST BE SHIFTED TO THE
 RIGHT, LOCATION OF PANEL LDPA)
 11. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-10-11 Cont ID  
Sent By vperez Date 2016-10-11 Time 08:34 Rev Time 0.00
Received By vperez Date 2016-10-11 Time 07:58 Sent To  
Notes
2016-10-11 09:01:22INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL SITE
 LIGHTING AND ASSOCIATED EQUIPMENT, GENERATOR, ALL LOW
 VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA, WIRELESS
 SYSTEMS, HOOD SYSTEMS, LIGHTNING PROTECTION GENERATORS,
 ETC. A NOTE WILL SUFFICE.
 2. ADD A NOTE TO MAINTAIN ALL ELECTRICAL EQUIPMENT
 ABOVE THE BASELINE FLOOD ELEVATION PER STATE AND CITY
 REGULATORY AGENCIES.
 3. GFCI PROTECTION REQUIRED FOR ALL 15A-20A 125V
 RECEPTACLES PER NEC 210.8B2 IN KITCHEN AREA.
 4. RISER DIAGRAM AND PANEL SCHEDULES- PLEASE PROVIDE
 AVAILABLE FAULT CURRENT AVAILABLE AT THE FPL SERVICE.
 ATTACH TO DOCUMENTS LETTER FROM FLORIDA POWER & LIGHT
 INDICATING AIC. SHOW AIC CALCULATION BASED ON
 INFORMATION PROVIDED BY UTILITY FOR APPROVAL. NEC
 110.24 FBC 107
 5. PLEASE ADD A NOTE TO ONE-LINE SHEET TO REFLECT THE
 REQUIREMENTS OF NEC 700.7A FOR SIGNAGE
 6. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE
 VERBIAGE IN CODE.
 7. PLEASE LABEL ATS?S ON ONE-LINE TO BE SEPARATELY
 DERIVED SYSTEM AS SHOWN ON DETAIL SHEET.
 8. CLARIFY NOTE K ON RISER DIAGRAM, IF THESE ARE THE
 INTERLOCKS PLEASE ADD AS NOTE TO PLANS.
 9. PROVIDE VOLTAGE DROP CALCULATIONS NOT ONLY FOR
 FEEDERS BUT ALSO THE BRANCH CIRCUIT FBC EC 505.7
 10. MAIN ELECTRICAL ROOMS MUST COMPLY WITH NEC
 110.26C2, THERE SHALL BE ONE ENTRANCE AT EACH END OF
 THE WORKING SPACE. SHOW TWO MEANS OF EGRESS THAT
 COMPLIES WITH EGRESS REQUIREMENTS, AS ONE OF THE DOOR
 OPENS INTO A HAZARD AREA AND DOES NOT HAVE THE
 CLEARANCE REQUIREMENTS. ALSO NEC 110.26C3 REQUIRES
 PERSONNEL DOORS TO BE EQUIPPED WITH PANIC HARDWARE AND
 OPEN IN THE DIRECTION OF EGRESS. DOOR MUST SWING IN THE
 DIRECTION OF EGRESS.
 11. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2016-10-27 Cont ID  
Sent By mkhan Date 2016-11-14 Time   Rev Time 1.00
Received By mkhan Date 2016-10-27 Time   Sent To I
Notes
2016-10-27 15:59:39ENGINEERING PLANS DATED 10/18/2016 HAVE BEEN APPROVED
 THROUGH ENGINEERING SERVICES DIVISION FOR R-O-W UTILITY
 CONNECTIONS.
  
 APPLICANT IS HEREBY NOTIFIED THAT PRIOR TO COMMENCEMENT
 OF CONSTRUCTION OF PRIVATE UTILITES ON THIS SITE, A
 SEPARATE PERMIT MUST BE OBTAINED FROM THE CONSTRUCTION
 SERVICES DEPARTMENT.
  
 3:45 PM
 10-27-2016
 MOSTAQUE KHAN
 LAND DEVELOPMENT ENGINEER

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-01-17 Cont ID  
Sent By pleduc Date 2017-01-17 Time   Rev Time 0.00
Received By pleduc Date 2017-01-17 Time 15:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-11-23 Cont ID  
Sent By pleduc Date 2016-11-23 Time   Rev Time 0.00
Received By pleduc Date 2016-11-22 Time 15:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-10-03 Cont ID  
Sent By pleduc Date 2016-10-03 Time   Rev Time 0.00
Received By pleduc Date 2016-09-27 Time 16:09 Sent To  
Notes
2016-09-30 16:12:10THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET C 8 - THE PROPOSED INDICATED FDC CONFIGURATION
 IS NOT COMPLIANT. THE FDC SHAL NOT BE IN A POSITION TO
 PROVIDE PRESSURE TO THE FIRE LINE SUPPLY SYSTEM.
  
  
 PER NFPA 13
  
 8.17.2.4* ARRANGEMENT. SEE FIGURE 8.17.2.1.
 8.17.2.4.1* THE FIRE DEPARTMENT CONNECTION SHALL BE ON
 THESYSTEM SIDE OF THE WATER SUPPLY CHECK VALVE.
  
 8.17.2.4.2 FOR SINGLE SYSTEMS, THE FIRE DEPARTMENT
 CONNECTION SHALL BE INSTALLED AS FOLLOWS:
 (1) WET SYSTEM?ON THE SYSTEM SIDE OF SYSTEM CONTROL,
 CHECK, AND ALARM VALVES (SEE FIGURE A.8.16.1.1)
  
  
 A.8.17.2.4 THE CHECK VALVE SHOULD BE LOCATED TO
 MAXIMIZE ACCESSIBILITY AND MINIMIZE FREEZING POTENTIAL.
 IT IS RECOMMENDED THAT THE CHECK VALVE BE LOCATED TO
 REDUCE THE LENGTH OF NONPRESSURIZED PIPE IN THE FIRE
 DEPARTMENT CONNECTION SUPPLY LINE.
 A.8.17.2.4.1 THE FIRE DEPARTMENT CONNECTION SHOULD BE
 CONNECTED TO THE SYSTEM RISER. FOR SINGLE SYSTEMS, IT
 IS AN ACCEPTABLE ARRANGEMENT TO ATTACH THE FIRE
 DEPARTMENT CONNECTION TO ANY POINT IN THE SYSTEM,
 PROVIDED THE PIPE SIZE MEETS THE REQUIREMENTS OF
 8.17.2.3.
  
  
 2) SHEET C 8 - THE LOCATION OF THE FDC AND HYDRANT IS
 RECOMENDED TO BE PLACED CLOSER TO THE BUILDING, OR THE
 FDC ATTACHED TO THE BUILDING, CLOSER TO THE AREA OF FD
 ACCESS. THIS WAS PREVIOUSLY STATED DURING PPRC
 COMMENTS.
  
  
 3) SHEET LS 100 - THERE ARE INCORRECT REFERENCES AND
 EDITIONS TO THE FIRE CODES.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
 CLEAN AGENT SYSTEMS SHALL COMPLY WITH NFPA 2001, 2012
 EDITION.
 EMERGENCY AND STANDBY POWER SYSTEMS SHALL COMPLY WITH
 NFPA 110, 2013 EDITION.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-01-28 Cont ID  
Sent By tklarge Date 2017-01-28 Time 06:47 Rev Time 0.00
Received By tklarge Date 2017-01-05 Time 11:46 Sent To  
Notes
2017-01-05 11:46:39C33

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-01-04 Cont ID  
Sent By skennedy Date 2017-01-04 Time 10:56 Rev Time 0.00
Received By skennedy Date 2016-11-16 Time 15:35 Sent To  
Notes
2016-11-16 15:38:06C33

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-15 Cont ID  
Sent By lmarchan Date 2016-11-15 Time 14:27 Rev Time 0.00
Received By lmarchan Date 2016-11-14 Time 14:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-29 Cont ID  
Sent By tklarge Date 2016-10-29 Time 09:01 Rev Time 0.00
Received By tklarge Date 2016-09-22 Time 09:26 Sent To  
Notes
2016-09-23 09:26:38C35

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2016-12-08 Cont ID  
Sent By shill Date 2016-12-08 Time 07:34 Rev Time 0.00
Received By shill Date 2016-12-08 Time 07:34 Sent To  
Notes
2016-12-08 07:36:00MU -2016-028473-0000
 ROUTED STAMPED PLAN, RECEIPT TO RECORDS
  
2016-11-28 13:44:53SHILL'S DESK

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-10-12 Cont ID  
Sent By shill Date 2016-10-12 Time 15:12 Rev Time 0.00
Received By shill Date 2016-10-12 Time 15:12 Sent To  
Notes
2016-10-12 15:13:05****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED.
 THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING
 THAT FEES DUE WERE PAID.
  
 561-233-5025 FOR MORE INFORMATION
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-01-12 Cont ID  
Sent By ccole Date 2017-01-12 Time 11:16 Rev Time 0.00
Received By ccole Date 2017-01-12 Time 11:16 Sent To  
Notes
2017-01-12 11:58:41MECHANICAL PROVISOS:
  
 1) COMMISSIONING OF THE MECHANICAL AND ELECTRICAL
 LIGHTING SYSTEMS REQUIRED. A HOLD IS PLACED ON THE CO
 PENDING RECEIPT OF THE REPORT.
  
 2) SITE SPECIFIC WIND LOAD ENGINEERING MUST BE
 SUBMITTED TO THE BUILDING DEPAQRTMENT PRIOR TO
 INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-11-21 Cont ID  
Sent By ccole Date 2016-11-21 Time 13:59 Rev Time 0.00
Received By ccole Date 2016-11-21 Time 13:59 Sent To  
Notes
2016-11-21 14:27:352ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16090832
 11/21/16
  
 1) THE REVISED ENERGYGAUGE ASHRAE 90.1 SUBMITTAL DOES
 NOT INCLUDE COMPLIANCE DATA FOR DX-1, OR EFFICIENCY
 RATINGS OF THE CRU SYSTEMS- SEE TABLE C403.2.3(10)
 FBC-14 ENERGY CONSERVATION. CONCERNING THE AHU'S, REFER
 TO TABLE C403.2.3(1) AND PROVIDE COMPLIANCE DATA PER
 THE AHRI TEST PROCEDURE FOR WATER COOLED UNITS (IF
 APPLICABLE).
  
 2) THE REQUESTED EXHAUST VENTILATION CALCULATIONS WERE
 NOT INCLUDED IN THE ASHRAE VENTILATION SUBMITTAL.
  
 3) THE ASHRAE VENTILATION SUBMITTAL INDICATES 1165 CFMS
 OF O/A FOR AHU-3, THE SCHEDULE INDICATES THE UNIT
 PRODUCES 2100 CFMS- IS THIS CORRECT?
  
 4) COMMISSSIONING IS REQUIRED FOR BOTH THE MECHANICAL
 SYSTEMS AND THE ELECTRICAL POWER AMND LIGHTING SYSTEMS-
 PLEASE PROVIDE A PLAN- SEE SECTION C408.1.
  
 5) ADVISORY: DEFERRED SUBMITTALS ARE REQUESTED FOR THE
 WIND LOAD ENGINEERING FOR INSTALLATION OF ALL EXTERIOR
 MECHANICAL EQUIPMENT AND THE REQUIRED FL. PRODUCT
 APPROVALS AND/OR MIAMI-DADE NOAS FOR LOUVERS, AC STANDS
 ETC. PLEASE REVIEW THE FOLLOWING SECTION FROM THE WPB
 AMENDMENTS AND PROVIDE A LIST OF EQUIPMENT AND
 COMPONENTS TO BE DEFERRED.
  
 A) DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
 B) DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-09-29 Cont ID  
Sent By ccole Date 2016-09-29 Time 17:01 Rev Time 0.00
Received By ccole Date 2016-09-29 Time 17:01 Sent To  
Notes
2016-09-29 17:02:241ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16090832
 9/29/16
  
 1) PROVIDE VENTILATION CALCULATIONS FOR O/A AND EXHAUST
 FOR ALL ROOMS AND SPACES USING THE DESIGN PARAMETERS
 SHOWN IN TABLE 403.3 FBC-14 MECHANICAL. PROVIDE A
 SCHEDULE INDICATING THE REQUIRED AND PROVIDED CFMS OF
 O/A AND EXHAUST. THE DESIGN CRITERIA TABLE ON M-101
 DOES NOT APPEAR TO BE CONSISTENT WITH TABLE 403.3, AND
 DOES NOT SHOW ANY EXHAUST CALCULATIONS.
  
 2) DESIGN EFFICIENCIES AND CRITERIA FOR THE AHU'S ARE
 NOT LISTED IN THE ENERGYGAUGE SUBMITTAL OR IN THE AHU
 SCHEDULE ON SHEET M-102.
  
 3) THE ENERGYGAUGE SUBMITTAL SHOWS COMPLIANCE DATA FOR
 CRU'S 12, 34, & 56, HOWEVER THE SCHEDULE INDICATES
 CRU'S 1, 2, 3, 4, 5, & 6.
  
 4) PROVIDE PIPING SYSTEM COMPLIANCE DATA IN THE
 ENERGYGAUGE SUBMITTAL.
  
 5) THE AC CALCULATIONS AND SCHEDULE FOR THE COMPUTER
 SYSTEMS DO NOT MATCH IN SYSTEM IDENTIFICATIONS, NUMBER
 OF SYSTEMS, AND CAPACITIES OF SYSTEMS.
  
 6) THE HEATING CAPACITIES OF THE AHU-3 TERMINAL BOXES
 ARE EXCEEDING THE CALCULATED HEATING COIL LOADS.
  
 7) M-103: PLEASE PROVIDE THE CHILLED WATER DATA IN THE
 CHILLER SCHEDULE.
  
 8) SHEET M-104: PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 TEMPORARY AIR HANDLER AND INDICATE HOW THE DUCTWORK
 WILL BE SUPPORTED, PROTECTED, AND SEALED AT THE
 BUILDING PENETRATION
  
 9) M-201 & M-202: THE TEMPORARY AC SYSTEMS ARE LISTED
 AS BOTH AC-TEMP AND RTU-TEMP- PLEASE CLARIFY. INDICATE
 HOW THE AC EQUIPMENT WILL BE MOUNTED (EQUIPMENT IS NOT
 SHOWN ON A TRAILER) AND HOW THE DUCTWORK WILL BE
 SUPPORTED, PROTECTED, AND SEALED AT THE PENETRATION OF
 THE BUILDING. A) PLEASE NOTE THAT A GAS PIPING PLAN AND
 ISOMETRIC WILL BE REQUIRED FOR THE HEAT.
  
 10) M-211: FIRE DAMPERS, OR SYMBOLS FOR FIRE DAMPERS,
 APPEAR TO BE MISSING AT THE DUCT PENETRATIONS ALONG THE
 EAST WALL OF THE CONTROL THEATER- SECTION 607.5.2.
  
 11) M-211: PLEASE CLARIFY THE PURPOSE OF EF-1-1 &
 EF-2-1 AND HOW THESE FANS WERE SIZED.
  
 12) M-212: SEE COMMENT #9 CONCERNING MISSING FIRE
 DAMPERS FOR DUCTS PENETRATING THE FIRE-RATED WALL. IT
 APPEARS THAT MANY OTHER DAMPERS ARE MISSING WHERE DUCTS
 PENETRATE FIRE-RATED CORRIDOR AND OTHER SEPARATION
 WALLS. PLEASE OVERLAY THE LIFE SAFETY PLANS ON THE
 MECHANICAL LAYOUT PAGES SO THAT RATED WALLS ARE CLEARLY
 SHOWN.
  
 13) M-212: EF 4-1 AND TG-1 ARE UNDERSIZED FOR THE
 MINIMUM REQUIRED EXHAUST CFMS FROM THE MENS RESTROOM
 180 PER TABLE 403.3- 250 CFMS.
  
 14) M-212: PROVIDE AN EXHAUST VENTILATION CALCULATION
 FOR THE LOCKER ROOM- TABLE 403.3.
  
 15) M-211- M222: PLEASE LABEL OR TAG ALL TB ACCESS
 PANELS, AND PROVIDE ACCESS TO ABOVE CEILING EXHAUST
 FANS- SECTION 306.1.
  
 16) PROVIDE CHILLED WATER PIPING DETAILS- TYPE OF
 PIPING, JOINERY, INSULATION.
  
 17) PROVIDE ENGINEERED STRUCTURAL DETAILS AND THE WIND
 LOAD DESIGN CRITERIA FOR INSTALLATION OF THE CHILLERS
 AND THE PUMPS- SECTION 301.15.
  
 18) SUBMIT FL. PRODUCT APPROVALS AND/OR MIAMI-DADE
 NOA'S FOR ALL AIR INTAKE AND EXHAUST LOUVERS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2016-10-12 Cont ID  
Sent By shill Date 2016-10-12 Time 17:10 Rev Time 0.00
Received By shill Date 2016-10-12 Time 17:10 Sent To  
Notes
2016-10-12 17:12:08ALTHOUGH A PORTION OF THE PARCEL IS LOCATED IN SFHA
 ZONE AH, THE EXISTING STRUCTURE AND PROPOSED ADDITION
 IS LOCATED ENTIRELY WITHIN FLOOD ZONE B PER SURVEY AND
 SITE PLAN PREPARED BY ARCHITECT WHICH BOTH DEPICT THE
 LINE BETWEEN ZONES A AH AND B.
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-01-28 Cont ID  
Sent By tklarge Date 2017-01-28 Time 06:46 Rev Time 0.00
Received By tklarge Date 2017-01-26 Time 12:08 Sent To  
Notes
2017-01-28 04:18:24TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
 ****PROVISOS****
 THE FOLLOWING ITEMS WILL BE CONSIDERED DEFERRED
 SUBMITTALS PER THE CITY OF WEST PALM AMENDMENTS TO THE
 FLORIDA BUILDING CODE SEC.107.3.4.2.
 DOCUMENTATION SHALL BE SUBMITTED TO THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE FOR REVIEW
 WITH A NOTATION INDICATING THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND
 FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF THE
 BUILDING PRIOR TO SUBMITTAL
 FOR REVIEW BY THE BUILDING DIVISION.
  
 1) MANUFACTURER'S SPECIFICATIONS FOR THE WATER TANK.
 2) MANUFACTURER'S SPECIFICATIONS FOR THE BLADDER TANK
 AND SIZE OF THE BLADDER TANK.
 3) DETAILS AND DDIMENSIONS FOR THE ANCHORING OF THE
 WATER TANK, SIZE AND TYPE OF HOLD DOWN STRAPS, TRAFFIC
 PROTECTION FOR THE PUMPS, SPECS ON THE PUMPS, AND ALL
 OTHER RELATED EQUIPMENT.
 4) MANUFACTURER'S SPECIFICATIONS FOR THE GENERATORS
 LOCATED IN THE EQUIPMENT CORRAL.

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-12-15 Cont ID  
Sent By tklarge Date 2016-12-15 Time 13:50 Rev Time 0.00
Received By tklarge Date 2016-12-08 Time 05:40 Sent To  
Notes
2016-12-15 12:03:061) SUBMIT FACTORY SIZING CALCULATIONS CREATED BY SCHIER
 FOR THE GREASE INTERCEPTOR IN ACCORDANCE WITH 2014 FPC
 SEC. 1003.2. THE SIZE, TYPE AND LOCATION OF EACH
 INTERCEPTOR SHALL BE APPROVED BY THE PLUMBING
 OFFFICIAL. CONTACT LEE SCHNEEWEISS OF SCHIER AT
 1-800-538-4792 FOR ASSISTANCE.
 2) PLEASE PROVIDE A SEQUENCE OF OPEREATIONS FOR THE
 SANITARY HOLDING TANKS. A RESPONSE WAS SUPPLIED IN THE
 NARRATIVE BUT THE INFORMATION NEEDS TO BE ON THE PLANS.
 WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHT. A-761, DETAIL 04 - RESTROOMS #183 & #184 SHALL
 CONTAIN A HANDICAPPED ACCESSIBLE TOILET COMPARTMENT
 WITHIN EACH RESTROOM. 2014 FBC-ACCESS. SEC.213.3.1. THE
 REQUEST FOR RELIEF HAS BEEN FORWARDED TO ROBERT BROWN,
 BUILDING OFFICIAL.
 4) SHT. LS-201 - THE FITNESS ROOM SHALL BE CALCULATED
 AT 50 SQUARE FEET PER PERSON PER TABLE1004.1.2.THE
 RESPONSE NARRATIVE REFERS TO SHT. LS-201 BUT I COULD
 NOT FIND THIS REVISED INFORMATION ON THE SHEET.
 CLARIFY.
 5) SHT. P302 - INCLUDE THE EMERGENCY (OVERFLOW) STORM
 DRAINS ON THE STORM DRAIN RISER. SHOW THE PITCH OF THE
 HORIZONTAL DRAIN.
 6) SHT. A401 - SHOW THE LOCATION OF THE ROOF DRAINS AND
 OVERFLOW DRAINS ON THE PLAN.
 7) SHT. P202 - FLOOR DRAINS ARE SHOWN IN ROOMS #109,
 #190, #1191, #193, #233 & #290. THESE DRAINS ARE
 CONNECTED TO THE SANITARY AND WILL REQUIRE TRAP PRIMERS
 PER 2014 FPC SEC.1002.4.
 8) SHT. P302 - THERE ARE STILL SECTIONS OF THE SANITARY
 SYSTEM (VENTS, BUILDING DRAIN,..) THAT ARE NOT SIZED.
 WPB AMEND. TO FBC SEC. 107.2.1.
 9) SHT. A-761 - CLEARLY SHOW THE CONTROL WALL IN THE
 HANDICAPPED ACCESSIBLE TRANSFER SHOWERS. THE GRAPHICS
 ARE SO LIGHT THAT THE CONTROL WALL IS DIFFICULT TO
 DETERMINE. WPB AMEND. TO FBC SEC. 107.2.1.
 10) SUBMIT DETAILS FOR THE GENERATORS IN THE EQUIPMENT
 CORRAL. SUBMIT INFORMATION ON THE FUEL SOURCE FOR THE
 GENERATORS, PIPING DETAILS (IF APPLICABLE) ETC.WPB
 AMEND. TO FBC SEC. 107.2.1.2ND REQUEST.THE NARRATIVE
 REFERS TO THE ELECTRICAL PLANS FOR INFORMATION. I COULD
 NOT FIND ANY INFORMATION ON THE GENERATOR IN THE
 ELECTRICAL PLANS. CLARIFY.
 11) SHT. A-701 - DETAIL 01- G6 ACCESSIBLE SHOWER - THE
 SHOWER CONTROLS, FAUCET AND SHOWER SPRAY UNIT IN THE
 ACCESSIBLE TRANSFER SHOWERS SHALL BE LOCATED ON THE
 SIDE WALL OPPOSITE THE SEAT 38 INCHES MINIMUM AND 48
 INCHES MAXIMUM ABOVE THE SHOWER FLOOR AND SHALL BE
 LOCATED ON THE CONTRL WALL 15 INCHES MAXIMUM FROM THE
 CENTERLINE OF THE SEAT TOWARD THE SHOWER OPENING.2014
 FAC SEC.608.5.1. THE DETAIL SHOWS THIS AS AN "OPTIONAL
 SHOWER HEAD AND CONTROL LOCATION." THIS IS NOT
 OPTIONAL. CLEARLY SHOW COMPLIANCE WITH THIS CODE
 SECTION.
 12) GRAB BARS IN THE ACCESSIBLE TRANSFER SHOWERS SHALL
 COMPLY WITH 2014 FAC SEC.608.3.1. CLEARLY SHOW
 COMPLIANCE WITH THIS CODE SECTION ON THE PLANS.
 13) NOTE: THE FINISHED CLEAR INSIDE DIMENSIONS OF THE
 ACCESSIBLE TRANSFER SHOWERS SHALL BE 36 INCHES BY 36
 INCHES MEASURED AT THE CENTER POINTS OF OPPOSING SIDES.
 FINISHED DIMENSIONS OTHER THAN THIS IS NON-COMPLIANT.
 14) SHT. P-201 - WHERE IS THE SANITARY LINE FOR ROOM
 #187? 2ND REQUEST.
 15) CLEARLY SHOW THE LOCATION OF GRAB BARS IN THE
 HANDICAPPED ACCESSIBLE TRANSFER SHOWERS. COMPLY WITH
 2015 FBC SEC.608.3.1 AND FIGURE 608.3.1.
 15) THE FOLLOWING ITEMS WILL BE CONSIDERED DEFERRED
 SUBMITTALS. DOCUMENTATION SHALL BE SUBMITTED FOR REVIEW
 PRIOR TO WORK STARTING ON THESE ITEMS.
  
 1) MANUFACTURER'S SPECIFICATIONS FOR THE WATER TANK.
 2) MANUFACTURER'S SPECIFICATIONS FOR THE BLADDER TANK
 AND SIZE OF THE BLADDER TANK.
 3) DETAILS AND DIMENSIONS FOR THE ANCHORING OF THE
 WATER TANK, SIZE AND TYPE OF STRAPS, TRAFFIC PROTECTION
 FOR THE PUMPS, SPECS ON THE PUMPS, ETC.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-10-29 Cont ID  
Sent By tklarge Date 2016-10-29 Time 09:01 Rev Time 0.00
Received By tklarge Date 2016-10-18 Time 13:31 Sent To  
Notes
2016-10-21 14:44:521) PROVIDE A SECTION DETAIL OF THE 2 SANITARY HOLDING
 TANKS SHOWING THE CONSTRUCTION OF THE TANK IN DETAIL.
 ARE THEY DESIGNED AS SEPTIC TANKS ON THE INTERIOR?
 CLARIFY.WPB AMEND. TO FBC SEC. 107.2.1.
 2) SUBMIT A BRIEF NARRATIVE AS TO THE
 OPERATION/SEQUENCING OF THE TANKS WHEN THEY ARE PUT
 INTO OPERATION. AS PIPED, IT IS CONFUSING TO DETERMINE
 HOW THEY WILL WORK.WPB AMEND. TO FBC SEC. 107.2.1.
 3) A GREASE INTERCEPTOR IS REQUIRED FOR THE KITCHEN PER
 THE 2014 FBC- PLUMBING, SEC.1003.1, 1003.3.1.
 4) SUBMIT SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTOR.THE SIZE, TYPE AND LOCATION OF EACH
 INTERCEPTOR SHALL BE APPROVED BY THE PLUMBING OFFICIAL.
 FPC SEC.1003.2.
 5) THE BREAKROOM SINK & COUNTER SHALL COMPLY WITH 2014
 FBC-ACCESSIBILITY SECS.212, 606.SEE SHT. A-741.
 6) 2ND FLOOR RESTROOM # 280 REQUIRES AN ACCCESSIBLE
 AMBULATORY COMPARTMENT THAT COMPLIES WITH FAC
 SEC.213.3.1 & SEC.604.8.2 PER 2014 FBC-ACCESS.
 7) SHT. A401 - THE STORM DRAINAGE TABLE ON THIS SHEET
 DOES NOT SEEM TO INCLUDE ONE-HALF THE AREA OF VERTICAL
 WALLS THAT CAN DIVERT RAINWATER TO THE ROOF. SEE 2014
 FPC SEC.1106.4.
 8) SHT. A 401 - THE CODED NOTES REFER TO SHTS. A-450
 AND A-451 FOR SCUPPER AND ROOF DRAIN DETAILS AND THERE
 IS NO ROOF DRAIN DETAIL ON A-450. MOST OF THE DETAILS
 ARE ON SHT. A- 452 .PLEASE REVISE THE NOTES. ALSO, THE
 PLANS SHOW ROOF DRAIN DETAILS BUT THERE ARE SCUPPERS
 SHOWN ON THE PLANS.CLARIFY.
 9) SHT.A-760 - THE GRAB BARS SHALL BE MEASURED FROM
 FINISH FLOOR TO THE TOP OF THE GRIPPING SURFACE. FAC
 SEC.609.4.
 10) SHT. A-761 - SHOW THE CLEAR INSIDE DIMENSIONS OF
 THE STANDARD AND HANDICAPPED ACCESSIBLE SHOWERS ON SHT.
 A-761
 11) AT LEAST ONE LAVATORY IN THE RESTROOMS SHAL COMPLY
 WITH 2014 FAC SEC.606 AND SHALL NOT BE LOCATED IN A
 TOILET COMPARTMENT. FAC SEC.213.3.4.
 12) RESTROOMS #183 & 184 SHALL CONTAIN A HANDICAPPED
 ACCESSIBLE TOILET COMPARTMENT WITHIN EACH RESTROOM.
 2014 FAC SEC. 213.3.1.
 13) WHERE MORE THAN ONE URINAL IS PROVIDED, AT LEAST
 ONE SHALL COMPLY WITH FAC SEC. 605. IDENTIFY THE
 HANDICAPPED URINALS IN THE RESTROOMS AND SHOW
 COMPLIANCE W/ FAC SEC. 605.
 14) SHT. LS-201 - THE FITNESS ROOM IS CALCULATED AT 100
 SQUARE FEET PER PERSON BUT SHOULD BE CALCULATED AT 50
 SQUARE FEET PER PERSON PER 2014 FBC TABLE 1004.1.2.
 15) SHT. LS-100 - PROJECT SUMMARY DOES NOT INCLUDE THE
 STORAGE OCCUPANCY OR THE SQUARE FOOTAGE. CLARIFY.
 16) SHT.P201 - WHERE IS THE SANITARY LINE FOR ROOM
 #187?
 17) THE KITCHEN (ROOM #124) WASTE SHALL DISCHARGE
 THROUGH A GREASE INTERCEPTOR PER 2014 FPC SEC.1003.3.1.
 18) SUBMIT A CONDENSATE RISER DIAGRAM FOR REVIEW. WPB
 AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.
 19) SUBMIT A STORM WATER RISER IF ROOF DRAINS ARE GOING
 TO BE INSTALLED. WPB AMEND. TO FBC SEC.107.2.1.THE
 STRUCTURE SHALL BE PROVIDED WITH EMERGENCY (OVERFLOW)
 ROOF DRAINS OR SCUPPERS PER FPC SEC. 1108.
 20) SHT. P202 - FLOOR DRAINS ARE SHOWN IN ROOMS #109,
 #190, #191, #193, #233, & # 290.WHAT WILL BE
 DISCHARGING INTO THESE FLOOR DRAINS? CONDENSATE WASTE
 SHALL NOT DISCHARGE INTO THE SANITARY SYSTEM PER CITY
 OF WPB CODE OF ORDINANCES CHAPT. 90, ART. III, SEC.
 90-126 (B) (5). TRAP PRIMERS MAY BE REQUIRED ON THESE
 FLOOR DRAINS PER FPC SEC.1002.4.
 21) SHT. P-222 - THE PLAN SHOWS A 3 INCH WASTE & 3 INCH
 CONDENSATE DRAIN DOWN IN CORRIDOR #026. CLARIFY.
 22) SHT.P-301 - THE MOP SINK IN ROOM #230 IS NOT DHOWN
 ON THE SANITARY OR WATER RISER DIAGRAMS. CLARIFY.
 23) SHT. P-302 - SIZE ALL VENTS, STACKS, ALL WET
 SECTIONS OF THE WASTE STACKS, & ALL SECTIONS OF THE
 BUILDING DRAIN. WPB AMEND. TO FBC SEC.107.2.1.
 24) SHT. P-302 - PLEASE IDENTIFY THE RISERS ON SHTS.
 P-302 & P-303 AS TO THEIR SPECIFIC AREAS IN THE
 BUILDING. THIS WILL HELP EXPEDITE THE RE-REVIEW. WPB
 AMEND. TO FBC SEC. 107.2.1.
 25) SIZE THE WATER RISERS IN THEIR ENTIRETY. LABEL THE
 RISERS TO CORRELATE WITH THEIR LOCATION ON THE FLOOR
 PLAN.WPB AMEND. TO FBC SEC. 107.2.1.
 25) SUBMIT A COMPLETE WATER RISER FOR REVIEW THAT
 BEGINS AT THE SOURCE TO THE END POINT. WPB AMEND. TO
 FBC SEC. 107.2.1, 107.3.5.1.3.3.
 26) SUBMIT A COMPLETE SANITARY RISER DIAGRAM FOR
 REVIEW. THE RISER SHALL INCLUDE THE COMPLETE
 UNDERGROUND SYSTEM AND ALL BRANCHES FROM THE POINT
 WHERE THE BUILDING DRAIN EXITS THE BUILDING TO THE END
 POINT.WPB AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.3.
 27) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER
 TANK. WPB AMEND. TO FBC SEC. 107.2.1.
 28) SUBMIT DETAILS/ MANUF. SPECIFICATIONS FOR THE
 BLADDER TANK AND INDICATE THE SIZE OF THE BLADDER TANK
 ON SHT. P-402.
 29) SUBMIT DETAILS AND DIMENSIONS OF THE ANCHOR PAD FOR
 THE WATER TANK.SUPPLY INFORMATION FOR THE ANCHORING OF
 THE TANK, SIZE AND TYPE OF STRAPS, TRAFFIC PROTECTION
 FOR THE PUMPS, ANCHORING DETAILS FOR THE WATER TANK (
 TYPE, LENGTH OF FASTENERS, ETC.)
 30) SHT. P-402 - WATER HEATER DETAIL "A" - THE HOT
 WATER/ TEMPERED WATER RETURN LINE SHALL BE ROUTED TO
 THE COLD WATER INLET PIPE OF THE HOT WATER HEATER AND
 THE COLD WATER INLET PIPE OR THE HOT WATER RETURN
 CONNECTION OF THE THERMOSTATIC MIXING VALVE 2014 FPC
 SEC.607.2.2.
 31) THERE SHALL BE A BACKFLOW PREVENTER INSTALLED ON
 THE WATER SUPPLY TO THE WATER TANK. 2014 FPC SEC.
 608.12, 608.13.
 31) SUBMIT DETAILS FOR THE GENERATORS IN THE EQUIPMENT
 CORRAL. SUBMIT INFORMATION ON THE FUEL SOURCE FOR THE
 GENERATORS, PIPING DETAILS ( IF APPLICABLE), ETC.WPB
 AMEND. TO FBC SEC. 107.2.1.
 32) INDICATE ON THE PLAN IF ANY LP OR NATURAL GAS WILL
 BE INSTALLED FOR THIS PROJECT. IF SO, SUBMIT COMPLETE
 DETAILS ON THE SYSTEM ( PIPING RISER, TYPE OF FUEL,
 LOCATION OF METER OR TANK), ETC.
 33) A CLEAR FLOOR SPACE OF 30 INCHES WIDE MINIMUM BY 48
 INCHES LONG MINIMUM MEASURED FROM THE CONTROL WALL
 SHALL BE PROVIDED FOR THE HANDICAPPED ACCESSIBLE
 TRANSFER SHOWERS PER 2014 FAC SEC.608.2.1.
 34) THE TRANSFER SHOWERS SHALL BE 36 INCHES BY 36
 INCHES CLEAR INSIDE DIMENSIONS MEASURED AT THE CENTER
 POINTS OF OPPOSING SIDES.2014 FAC SEC.608.2.1.
 35) THE SHOWER CONTROLS, FAUCET AND SHOWER SPRAY UNIT
 IN THE ACCESSIBLE SHOWERS SHALL BE LOCATED ON THE SIDE
 WALL OPPOSITE THE SEAT 38 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE SHOWER FLOOR AND SHALL BE LOCATED ON
 THE CONTROL WALL 15 INCHES MAXIMUM FROM THE CENTERLINE
 OF THE SEAT TOWARD THE SHOWER OPENING.2014 FAC
 SEC.608.5.1.
 36) GRAB BARS IN THE ACCESSIBLE TRANSFER SHOWERS SHALL
 COMPLY WITH 2014 FAC SEC.608.3.1.
 37) THE COUNTER IN THE BREAK ROMM SHALL BE A MAXIMUM OF
 34 INCHES FROM THE FINISH FLOOR TO THE TOP OF THE
 COUNTER PER 2014 FAC SEC. 212 & 606.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2017-07-10 Cont ID  
Sent By shill Date 2017-07-10 Time 12:04 Rev Time 0.00
Received By shill Date 2017-07-10 Time 12:04 Sent To  
Notes
2017-07-10 12:05:31SEE ROOF SUB PERMIT (17070205) FOR ROOF REVIEW AND NEW
 PRODUCT APPROVAL SUBMITTED (FL17013)
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2016-10-18 Cont ID  
Sent By shill Date 2016-10-18 Time 12:53 Rev Time 0.00
Received By shill Date 2016-10-18 Time 12:53 Sent To  
Notes
2016-10-18 12:59:47PRODUCT APPROVAL FL2948-R9 WAS SUBMITTED. USE OF A
 DIFFERENT PRODUCT APPROVAL REQUIRES APPROVAL BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL AS A REVISION.
 PRIOR TO INSTALLATION, A SEPARATE ROOF PERMIT IS
 REQUIRED. THE APPLICANT IS TO SUBMIT THE APPROVED
 ASSEMBLY PROPOSED WITH ANY REQUIRED ENGINEERING.
  
 ROOF COVERING TO COMPLY WITH THE DESIGN PRESSURES SHOWN
 ON S003:
  
 VULT
 ZONE 1, -129/+52
 ZONE 2, -216/+52
 ZONE 3, -161
  
 PLAN VIEW "ZONE 2" (NOT ZONE 2 PER ASCE7-10) IS ENTIRE
 PERIMITER (ASCE7 ZONE 2 & 3). PLAN VIEW "ZONE 3"
 APPEARS TO BE 1ST STORY ASCE 7 ZONES 2 & 3.
 SEE PLAN ON SHEET S003 FOR FURTHER CLARIFICATION.
  
  
  
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status P Date 2017-02-03 Cont ID  
Sent By kconrad Date 2017-02-03 Time 08:34 Rev Time 0.00
Received By kconrad Date 2017-02-03 Time 08:34 Sent To I
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2016-12-09 Cont ID  
Sent By shill Date 2016-12-09 Time 07:07 Rev Time 0.00
Received By shill Date 2016-12-09 Time 07:07 Sent To  
Notes
2017-01-31 12:45:171/31/17 ADDITIONAL SIGNATURES (3) REQUIRED ON SPECIAL
 INSPECTOR AGREEMENT, NOTIFIED INSPECTOR, CONTRACTOR,
 AND OWNER VIA EMAIL. UPON RECEIPT, NOTIFY ME OR
 SAMANTHA. SAK
2016-12-09 07:16:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THIS PROJECT IS EITHER THRESHOLD (REQUIRES SPECIAL
 INSPECTOR, STATUTORY STATEMENT ON ALL PLANS PER FS
 553.79(7)(D), OR IT REQUIRES A RESIDENT INSPECTOR. SEE
 PREVIOUS REVIEW REGARDING REQUIREMENTS (RESUMES,
 AGREEMENT, ETC.).
  
 ASSEMBLY OCCUPANT LOAD MUST BE ON THE PLANS IN ORDER TO
 DEMONSTRATE WHETHER OR NOT THIS IS A THRESHOLD JOB.
  
 THREE SETS OF ALL PERMIT DOCUMENTS ARE REQUIRED:
  
 1. CITY
 2. JOB (ON SITE FOR INSPECTIONS)
 3. SPECIAL INSPECTOR OR RESIDENT INSPECTOR
  
 FAILURE TO PROVIDE THREE SETS AT TIME OF RESUBMITTAL
 MAY RESULT IN PERMIT ISSUANCE DELAYS AS A THIRD SET
 SUBMITTED AFTER REVIEWS HAVE BEEN DONE MAY REQUIRE THAT
 THE THIRD SET BE ROUTED TO TRADES FOR STAMPING AND/ OR
 THAT SOMEONE BE ASSIGNED THE RESPONSIBILITY TO VERIFY
 THIRD SET COMPLETENESS AND ACCURACY AND ADD STAMPS,
 PROVISOS, REDLINES AS NEEDED.
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2016-10-18 Cont ID  
Sent By shill Date 2016-10-18 Time 13:25 Rev Time 0.00
Received By shill Date 2016-10-18 Time 13:25 Sent To  
Notes
2016-10-18 13:27:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 GOVERNING CODE: FBC 5TH EDITION (FBC 2014)
  
 THIS BUILDING REQUIRES EITHER A SPECIAL INSPECTOR (IF
 DETERMINED TO BE A THRESHOLD BUILDING) OR A RESIDENT
 INSPECTOR.
  
 ASSEMBLY OCCUPANT LOAD NOT YET DETERMINED, BUT IT IS
 LIKELY THAT A RESIDENT INSPECTOR WILL BE REQUIRED. SEE
 POLICY AND AGREEMENT SENT VIA EMAIL.
  
  
 1. FLORIDA STATUTE 553.71; ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SF IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2. IF A THRESHOLD BUILDING, THE FOLLOWING IS REQUIRED:
  
 A. THRESHOLD INSPECTION PLAN; FS 553.79(5)(A), CITY OF
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1. THE
 ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO
 PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING
 PURSUANT TO A STRUCTURAL INSPECTION PLAN PREPARED BY
 THE ENGINEER OR ARCHITECT OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO AND APPROVED BY
 THE ENFORCING AGENCY BEFORE THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 B. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FS
 553.79(5)(A) TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES, NOTARIZED AND RETURNED
 TO THIS OFFICE, REVIEWED AND APPROVED PRIOR TO PERMIT
 ISSUANCE. CONTACT KEN CONRAD, MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM, AT 561-805-6666 FOR ADDITIONAL
 INFORMATION.
 FORMS WERE SENT TO: [email protected] ON 10/18/16.
  
 **RESIDENT INSPECTOR FORMS REQUIRED IF BUILDING IS NOT
 THRESHOLD.
  
 C. SPECIAL INSPECTOR OR RESIDENT INSPECTOR RESUME':
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECTS FOR REVIEW BY THE BUILDING OFFICIAL OR HIS
 DESIGNEE. AFTER THE RESUME' IS REVIEWED, AN INTERVIEW
 WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES WILL AN
 INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST MEETING
 THE ABOVE CRITERIA. THE RESUME' IS TO BE SUBMITTED TO
 KEN CONRAD (AND COPY SAMANTHA HILL), 561-805-6666,
 [email protected], [email protected]
  
 ALL PROSPECTIVE INSPECTORS ARE TO BE APPROVED BY THE
 CHIEF BUILDING INSPECTOR AND ALL ARE REQUIRED TO SIGN
 THE SPECIAL INSPECTOR AGREEMENT OR RESIDENT INSPECTOR
 AGREEMENT AS APPLICABLE.
  
 D. CONTRACTOR RESUME': PROVIDE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO
 KEN CONRAD, (PLEASE COPY SAMANTHA HILL) VIA E-MAIL
 ([email protected], [email protected]).
  
 E. PERMIT DOCUMENTS: PAPER SUBMITTALS REQUIRE THREE
 SIGNED AND SEALED (IF APPLICABLE) ORIGINAL SETS OF ALL
 DOCUMENTS.
  
 F. FS553.79(7)(D)ALL PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT?S OR ENGINEER?S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRESAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS CHAPTER AND CHAPTER 633.
 (THRESHOLD BUILDING ONLY)
  
 3. ADVISORY ONLY; PER FS 553.79, ALL SHORING/RE-SHORE
 ENGINEERING IS TO BE REVIEWED BY ENGINEER OF RECORD
 AND THREE SIGNED AND SEALED ORIGINAL SETS ARE TO BE
 SUBMITTED FOR PLAN REVIEW. THE SHORING/RESHORE
 ENGINEERING IS TO BE REVIEWED AND APPROVED PRIOR TO
 INSPECTION. THE CITY APPROVED (CITY STAMPED)
 SHORING/RE-SHORE ENGINEERING IS TO BE AVAILABLE ON THE
 JOB AT THE TIME OF INSPECTION.
  
 4. ADVISORY ONLY; PRIOR TO INSTALLATION, A GUARD RAIL
 DETAIL IS TO BE SUBMITTED FOR PLAN REVIEW. THIS SHOULD
 BE SUBMITTED WITH THE SHORING/RESHORE ENGINEERING. THIS
 MAY BE PROVIDED IN THE FIELD SUBJECT TO THE INSPECTOR'S
 DISCRETION.
  
  
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2017-01-27 Cont ID  
Sent By jroach Date 2017-01-27 Time 14:46 Rev Time 0.00
Received By jroach Date 2017-01-27 Time 14:46 Sent To  
Notes
2017-01-27 14:46:27ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 01.27.2017
 PERMIT NO.: 16090832
 ADDRESS: 4217 UP THE GROVE LANE
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW FPL COMMAND CENTER.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. THE LANDSCAPE ISLAND ALONG THE SOUTH SIDE OF THE
 PARKING LOT, CONTAINING THE WATER TANK PUMP ENCLOSURE
 SHALL BE MODIFIED TO PROVIDE THE REQUIRED SHADE TREE.
 ALL PERMITS/APPROVALS SHALL BE AMENDED TO REFLECT ANY
 MODIFICATIONS NECESSARY TO ACCOMMODATE SUCH
 REQUIREMENT.
  
 2. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 (CO) ALL INVASIVE EXOTIC SPECIES SHALL BE REMOVED FROM
 THE ENTIRE SITE (AS REQUIRED BY RESOLUTION NO 231-16).
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2016-12-15 Cont ID  
Sent By jroach Date 2016-12-15 Time 15:06 Rev Time 0.00
Received By jroach Date 2016-12-15 Time 15:06 Sent To  
Notes
2016-12-15 15:08:26ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 12.15.2016
 PERMIT NO.: 16090832
 ADDRESS: 4217 UP THE GROVE LANE
 CONTRACTOR/CONTACT: JON ROSENTHAL
 TELEPHONE NO.: 561.694.4274
 SCOPE OF REVIEW: COMMAND CENTER EXPANSION
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. ALL PLANS SHALL MATCH THOSE APPROVED BY THE
 DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION ON
 OCTOBER 31, 2016, AS PART OF PLANNING BOARD CASE NO.
 1702A (MINOR DSI AMENDMENT). ADDITIONALLY, THERE ARE
 INCONSISTENCIES BETWEEN THE CIVIL, SITE, AND LANDSCAPE
 PLANS...SPECIFICALLY WITH REGARD TO THE SIZE AND
 LOCATION OF THE LANDSCAPE ISLANDS IN THE PARKING ROW
 ADJACENT TO UP THE GROVE LANE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-10-28 Cont ID  
Sent By jroach Date 2016-10-28 Time 10:50 Rev Time 0.00
Received By jroach Date 2016-10-28 Time 10:36 Sent To  
Notes
2016-10-28 10:52:52ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 10.28.2016
 PERMIT NO.: 16090832
 ADDRESS: 4217 UP THE GROVE LANE
 CONTRACTOR/CONTACT: JON ROSENTHAL
 TELEPHONE NO.: 561.694.4274
 SCOPE OF REVIEW: COMMAND CENTER EXPANSION
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. ALL PLANS SHALL MATCH THOSE SUBMITTED TO THE
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION ON
 OCTOBER 18, 2016, AS PART OF PLANNING BOARD CASE NO.
 1702A (MINOR DSI AMENDMENT).
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved