Plan Review Details - Permit 16090832
| Plan Review Stops For Permit 16090832 |
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
1 |
Status |
P |
Date |
2016-10-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-10-27 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-10-27 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2016-10-27 11:26:38 | PER EMAIL FROM SYBILLE WELTER | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2017-01-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-01-19 |
Time |
17:38 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-01-17 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2017-01-19 17:39:11 | ****PROVISOS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | | | | AFTER ISSUANCE, COLOR COPY ONE SET FOR THE RESIDENT | | | INSPECTOR. OR, BLACK AND WHITE COPY, AND BRING TO | | | BUILDING DIVISION TO BE RED STAMPED WITH THE PERMIT | | | NUMBER. | | | | | | PER ARCHITECT, THE AREA CALLED A "STAGE" (SHEET A221, | | | 2ND FLOOR) IS A RAISED AREA TO PROVIDE PROTECTION TO A | | | LARGE DISPLAY SCREEN (ALSO SEE SHEET A222). IT IS NOT | | | USED AS A STAGE. IF USE IS CHANGED TO BE A PLATFORM FOR | | | PEOPLE, VERTICAL ACCESSIBILITY IS REQUIRED. | | | | | | ALL REQUIRED PRODUCT APPROVALS NOT SUBMITTED AND | | | REVIEWED PRIOR TO ISSUANCE ARE TO BE SUBMITTED FOR | | | REVIEW PRIOR TO INSTALLATION. PRIOR TO SUBMISSION TO | | | THE BUILDING DIVISION THEY ARE TO BE REVIEWED BY | | | DESIGNER OF RECORD, FBC 107. | | | | | | SEPARATE PERMITS REQUIRED FOR SIGNS, PARKING LOT, SITE | | | LIGHTING, ETC. (ALL ITEMS OUTSIDE OF THE BUILDING | | | ENVELOPE). | | | | | | A PRE-CONSTRUCTION MEETING WITH KEN CONRAD, CHIEF | | | BUILDING INSPECTOR, THE CONTRACTOR, AND THE RESIDENT OR | | | SPECIAL INSPECTOR IS REQUIRED. PLEASE CONTACT KEN | | | CONRAD, 561-805-6666 TO SCHEDULE. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2016-12-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-12-09 |
Time |
06:29 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-12-08 |
Time |
07:05 |
Sent To |
|
|
| Notes |
| 2016-12-09 06:30:01 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. LS100, EGRESS WIDTH TABULATIONS, HAS A TYPO (BOTH | | | FIRST AND SECOND FLOOR), 15SF PER PERSON FOR STORAGE, | | | FBC TABLE 1004.1.2. | | | | | | THIS WAS REVISED, BUT RATIONALE FOR S2 RATHER THAN S1 | | | OCCUPANCY IS NOT CLEAR. S2 IS FOR NON COMBUSTIBLE | | | STORAGE. REVISE PLAN TO STATE TYPE OF MATERIALS STORED | | | IN EACH STORAGE AREA (OR ONE NOTE IF ALL ARE THE SAME), | | | OR REVISE TO S1 WHICH INCLUDES COMBUSTIBLE STORAGE. | | | | | | 2. COMMENT FROM FIRST REVIEW: LS100, REVISE TO SHOW | | | COMPLIANCE WITH FBC TABLE 503, FBC 506. COMPLIANCE FOR | | | THE ENTIRE BUILDING, ALL OCCUPANCIES, SHOULD BE SHOWN. | | | INCREASES PER FBC 506 ARE TO BE SHOWN. | | | | | | FOR EXAMPLE, A101 SHOWS BUILDING AREA AS 82,003, LS100 | | | SHOWS BUILDING AREA AS 71,055. LS100 PROJECT SUMMARY | | | DOES NOT INCLUDE S1 OCCUPANCY. | | | | | | 2ND REVIEW, IT IS NOT CLEAR HOW THIS HAS BEEN | | | ADDRESSED. THE SPRINKLER INCREASE FOR BUSINESS WAS | | | SHOWN, BUT THIS IS A MIXED USE BUILDING AND BUSINESS IS | | | NOT THE MOST STRINGENT CONDITION. A3 (WITH SPRINKLER | | | INCREASE) HAS A LIMIT OF 28,500 AND S1 ALLOWS 52,500. | | | AS BUILDING AREA DOES NOT COMPLY WITH THE MOST | | | STRINGENT, EITHER OCCUPANCIES ARE TO BE SEPARATED OR | | | FRONTAGE INCREASE IS NEEDED, FBC 506.2. | | | | | | THE SQUARE FOOT AREAS FOR ASSEMBLY AND S1 ARE NOT ON | | | THE PLAN, SO COMPLIANCE WITH FBC 508.2.1 (ACCESSORY | | | OCCUPANCIES) CANNOT BE DETERMINED. | | | | | | THE GENERATOR BUILDING WAS NOT INCLUDED, SEE FBC 703.5. | | | IT IS NOT CLEAR IF THIS WILL BE INCLUDED IN THE | | | BUILDING AREA CALCULATIONS OR IF COMPLIANCE WITH | | | DISTANCE TO AN ASSUMED PROPERTY LINE IS REQUIRED TO BE | | | SHOWN. | | | | | | 3-6. AS DISCUSSED, THE USE OF 100 SF PER PERSON FOR AN | | | OVERALL OCCUPANT LOAD IS ACCEPTABLE WITH THE EXCEPTION | | | OF ASSEMBLY AREAS SUCH AS THE PRESS ROOM WHICH WILL | | | SERVE OCCUPANTS FROM OUTIDE OF THE BUILDING. LS201, | | | THIS AREA IS SHOWN AS 100 SF PER PERSON. AS DISCUSSED, | | | THE ASSEMBLY AREAS SUCH AS THE SMALL CONFERENCE ROOMS | | | CAN BE CALCULATED AT 100 SF PER PERSON IF THE OCCUPANTS | | | ARE FROM THE ADJACENT OFFICE AREAS. REVISE THE MEDIA | | | ROOM TO 15 SF PER PERSON AS WELL AS ANY OTHER AREAS | | | INTENDED TO INCLUDE ADDITIONAL OCCUPANTS. | | | | | | 5. OK | | | | | | 6. CLARIFY WHICH ROOMS WERE CONSIDERED ASSEMBLY | | | OCCUPANCY WHEN CALCULATING THE TOTAL SF AREA AND | | | OCCUPANT LOAD IN EGRESS WIDTH TABULATIONS ON LS100, | | | FBC107, FS553. | | | 2ND REVIEW, ALTHOUGH THE OVERALL OCCUPANT LOAD IS | | | CALCULATED AT 100 SF PER PERSON GROSS, INCLUDING | | | ASSEMBLY AREAS, A TOTAL ASSEMBLY OCCUPANT LOAD IS | | | REQUIRED TO DETERMINE WHETHER OR NOT THIS IS A | | | THRESHOLD BUILDING. PLEASE SEND THE TOTAL SQUARE FEET | | | OF ASSEMBLY AREA VIA EMAIL SO THIS CAN BE DETERMINED. | | | | | | 7-8. OK | | | | | | 9. LS201, NO INFORMATION WAS PROVIDED REGARDING THE | | | EXISTING COMMAND CENTER AND HOW EXITING WILL BE | | | AFFECTED BY THE PROPOSED NEW COMMAND CENTER. PROVIDE | | | INFORMATION REGARDING THE DOORS WHICH PREVIOUSLY LED | | | DIRECTLY TO THE OUTDOORS WHICH WILL NOW LEAD TO THE NEW | | | COMMAND CENTER. IF THESE DOORS ARE EXIT DOORS, HOW WILL | | | TRAVEL DISTANCE BE AFFECTED? WHAT OCCUPANCY | | | CLASSIFICATIONS DO THESE DOORS SERVE? | | | | | | 2ND REVIEW, THE RESPONSE LETTER INFORMATION ADDRESSES | | | THIS ISSUE. AS THE RESPONSE LETTER IS NOT A PART OF THE | | | PERMIT RECORD (AND IS NOT SIGNED AND SEALED), REVISE | | | THE PLAN TO INCLUDE THIS INFORMATION. THE PLAN | | | CURRENTLY SHOWS THAT THE EXIT DOOR IS STILL BEING USED | | | AS AN EXIT DOOR, SHOWS ONLY A PARTIAL TRAVEL DISTANCE, | | | AND DOES NOT REFERENCE THE OTHER EXITS. REVISE TO | | | INCORPORATE THE INFORMATION IN THE RESPONSE LETTER INTO | | | THE PLAN. | | | | | | 10-11. OK | | | | | | 12. OCCUPANT LOAD TOTALS DO NOT APPEAR CORRECT. FOR | | | INSTANCE, LS202 SHOWS OCCUPANT LOAD FOR THE BUSINESS | | | AREA WHICH IS DIVIDED INTO ROOMS CALCULATED ON THE | | | TOTAL RATHER THAN BY ROOM. FBC 107 AND FBC CHAPTER 10, | | | AN ACCURATE OCCUPANT LOAD IS REQUIRED FOR C.O., TO | | | CONFIRM COMPLIANCE WITH LIFE SAFETY REQUIREMENTS, AND | | | FOR THRESHOLD BUILDING DETERMINATION. REVISE PLAN. | | | | | | 13. FBC 1014.2, CLARIFY THE NUMBER OF OCCUPANTS | | | CALCULATED TO TRAVEL THROUGH THE BREAK ROOM TO REACH | | | THE REQUIRED EXIT. HOW WILL THE EGRESS PATH BE KEPT | | | CLEAR OF TABLES AND CHAIRS? ASSEMBLY IS CONSIDERED A | | | HIGHER RISK THAN BUSINESS. REVISE PLAN TO CLARIFY HOW | | | COMPLIANCE WITH THE REQUIREMENT THAT A DISCERNIBLE PATH | | | OF EGRESS TRAVEL TO AN EXIT WILL BE MET. FEEL FREE TO | | | CONTACT ME TO DISCUSS. | | | | | | 2ND REVIEW, THE LIFE SAFETY PLAN IS NOT CLEAR ON THE | | | NUMBER OF OCCUPANTS IN EACH AREA AND THE NUMBER OF | | | OCCUPANTS WHICH EACH EXIT IS TO SERVE. | | | | | | THIS AREA WAS REVISED TO SHOW 46 OCCUPANTS, BUT IT | | | APPEARS THAT THE 98 FROM THE CONTROL THEATER WILL ALSO | | | EXIT THROUGH THIS AREA. THE OCCUPANT LOAD FOR THE | | | THEATER WAS NOT PROVIDED. IS IT 98 TOTAL, OR 98 TIMES | | | 3? IF 98 TOTAL, A THIRD SHOULD BE SHOWN AT EACH EXIT | | | RATHER THAN 98. | | | | | | ADDING UP ALL OF THE DOOR EXIT REQUIRED NUMBERS GIVES A | | | TOTAL OF 341, BUT THE TOTAL OCCUPANT LOAD FOR THE FLOOR | | | IS 467 PLUS THE NUMBER OF OCCUPANTS FROM THE EXISTING | | | BUILDING AND THE SECOND FLOOR, APPEARS TO BE A TOTAL OF | | | APPROXIMATELY 500 FOR FIRST FLOOR OCCUPANTS. THE | | | THEATER SHOWS TWO CORRIDORS AS EXITS, APPEARS TO SHOW | | | 98 EACH CORRIDOR, BUT IS NOT CLEAR WHERE THESE PEOPLE | | | EXIT. | | | | | | THE TWO STAIRS ARE SHOWN AS SERVING 48 EACH, BUT THEY | | | ARE BOTH USED AS EXITS FOR THE FIRST FLOOR AND THE | | | SECOND FLOOR WHICH HAS AN OCCUPANT LOAD OF 244. | | | | | | IF EACH STAIR DOOR SERVES 48 OCCUPANTS FROM THE FIRST | | | FLOOR AND 122 FROM THE SECOND, 34 INCHES OF DOOR WIDTH | | | IS REQUIRED, 33 IS PROVIDED. | | | | | | 14-18. OK | | | | | | 19. THREE SETS OF PLANS REQUIRED; SEE THRESHOLD REVIEW. | | | | | | THREE SETS OF ALL PERMIT DOCUMENTS REQUIRED. | | | | | | 20. A CONSTRUCTION TRAILER IS SHOWN ON SHEET M104. THIS | | | REQUIRES A SEPARATE PERMIT AND HAS NOT BEEN REVIEWED AT | | | THIS TIME. | | | | | | 21. OK | | | | | | 22. THE BUILDING OFFICIAL HAS REVIEWED THE LETTER | | | REGARDING THE LACK OF ACCESSIBLE BATHROOMS ON THE FIRST | | | FLOOR ADJACENT TO THE THEATER. AS THESE BATHROOMS ARE | | | NOT NEAR THE OTHERS ON THE FLOOR, IT IS NOT CONSIDERED | | | A CLUSTER. DUE TO THE DISTANCE, PROVIDING ACCESSIBLE | | | BATHROOMS IN ANOTHER AREA IS NOT CONSIDERED EQUIVALENT | | | FACILITATION. | | | | | | NOTE THAT ALL COMMENTS REGARDING ACCESSIBILITY ARE | | | APPLICABLE FOR BUILDING REVIEW AND MUST BE ADDRESSED. | | | | | | 23. THE LIFE SAFETY PAGES ARE ILLEGIBLE, FBC 107. THEY | | | HAVE HATCHING OVER ALL OF THE AREAS, MAKING IT VERY | | | DIFFICULT TO READ, AND NOW HAVE ADDITIONAL INFORMATION | | | (CIRCLES) OVER THE FLOOR PLAN. PLEASE PROVIDE LEGIBLE | | | LIFE SAFETY PLANS. FOR BUILDING REVIEW, NEITHER THE | | | HATCHING NOR THE CIRCLES ARE NECESSARY. IF REQUIRED FOR | | | ANOTHER TRADE, PLEASE PROVIDE THIS INFORMATION AS | | | SEPARATE SHEETS. | | | | | | 24. AS DISCUSSED, AS THE 2ND FLOOR "STAGE" IS NOT AN | | | OCCUPIABLE SPACE, REVISE THE DESIGNATION FOR THIS AREA | | | (ELEVATED PROTECTIVE BARRIER). | | | | | | 25. WHEN RESUBMITTING, PLEASE CHANGE ONLY SHEETS WHICH | | | HAVE CHANGED. | | | | | | 26. THIS PERMIT WILL BE ISSUED WITH PROVISO: | | | | | | ALL REQUIRED PRODUCT APPROVALS NOT SUBMITTED AND | | | REVIEWED PRIOR TO ISSUANCE ARE TO BE SUBMITTED FOR | | | REVIEW PRIOR TO INSTALLATION. PRIOR TO SUBMISSION TO | | | THE BUILDING DIVISION THEY ARE TO BE REVIEWED BY | | | DESIGNER OF RECORD, FBC 107. | | | | | | SEPARATE PERMITS REQUIRED FOR SIGNS, PARKING LOT, SITE | | | LIGHTING, ETC. (ALL ITEMS OUTSIDE OF THE BUILDING | | | ENVELOPE). | | | | | | A PRE-CONSTRUCTION MEETING WITH KEN CONRAD, CHIEF | | | BUILDING INSPECTOR, THE CONTRACTOR, AND THE RESIDENT OR | | | SPECIAL INSPECTOR IS REQUIRED. PLEASE CONTACT KEN | | | CONRAD, 561-805-6666 TO SCHEDULE. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-10-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-10-18 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-10-12 |
Time |
07:18 |
Sent To |
|
|
| Notes |
| 2016-10-18 13:24:58 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. LS100, EGRESS WIDTH TABULATIONS, HAS A TYPO (BOTH | | | FIRST AND SECOND FLOOR), 15SF PER PERSON FOR STORAGE, | | | FBC TABLE 1004.1.2. | | | | | | 2. LS100, REVISE TO SHOW COMPLIANCE WITH FBC TABLE 503, | | | FBC 506. COMPLIANCE FOR THE ENTIRE BUILDING, ALL | | | OCCUPANCIES, SHOULD BE SHOWN. INCREASES PER FBC 506 ARE | | | TO BE SHOWN. | | | | | | FOR EXAMPLE, A101 SHOWS BUILDING AREA AS 82,003, LS100 | | | SHOWS BUILDING AREA AS 71,055. LS100 PROJECT SUMMARY | | | DOES NOT INCLUDE S1 OCCUPANCY. | | | | | | 3. LS201, MEDIUM CONFERENCE ROOM IS SHOWN AS 4,641 SF | | | ON THIS PAGE, APPEARS THAT THIS IS NOT CORRECT. REVISE | | | OR CLARIFY, FBC 107. | | | | | | 4. LS201, MEDIUM CONFERENCE ROOM OCCUPANT LOAD WAS | | | CALCULATED AT 100 SF PER PERSON. CONFERENCE ROOMS ARE | | | TYPICALLY ASSEMBLY WITH 15 SF PER PERSON. | | | | | | EITHER REVISE OR SEND A LETTER VIA EMAIL WHICH EXPLAINS | | | RATIONALE. SEE PREVIOUS COMMENT. IF THIS ROOM IS | | | INTENDED TO BE 4,641 SF, THE OCCUPANT LOAD SHOULD BE | | | 310 AND REQUIRES ANOTHER EXIT. IF THIS ROOM IS 384 SF, | | | AN OCCUPANT LOAD OF 4 (100 SF PER PERSON) IS NOT | | | CORRECT AS TEN CHAIRS ARE SHOWN. | | | | | | 5. LS201, 202, APPLICABLE TO ALL CONFERENCE ROOMS AND | | | BREAK ROOMS, ALSO POSSIBLY ROOMS 103 AND 104 MEDIA | | | ROOMS, THESE AREAS ARE TYPICALLY TREATED AS ASSEMBLY | | | OCCUPANCY, 15 SF PER PERSON. REVISE PLAN OR CONTACT ME | | | TO DISCUSS, FBC TABLE 1004.1.2. 100 SF PER PERSON DOES | | | NOT APPEAR TO BE AN ADEQUATE DESIGN OCCUPANT LOAD FOR | | | THESE SPACES. | | | | | | 5. LS201, FITNESS ROOM OCCUPANT LOAD WAS CALCULATED AT | | | 100 SF PER PERSON. SEE FBC TABLE 1004.1.2, 50 SF PER | | | PERSON REQUIRED. | | | | | | 6. CLARIFY WHICH ROOMS WERE CONSIDERED ASSEMBLY | | | OCCUPANCY WHEN CALCULATING THE TOTAL SF AREA AND | | | OCCUPANT LOAD IN EGRESS WIDTH TABULATIONS ON LS100, | | | FBC107, FS553. | | | | | | 7. LS201, ROOM 192, FBC 1008.1.10, REVISE PLAN TO | | | CLARIFY ELECTRIC ROOM FUNCTION. IF PANIC BARS ARE NOT | | | REQUIRED, REVISE PLAN TO INDICATE THAT THIS ROOM DOES | | | NOT CONTAIN EQUIPMENT AS DESCRIBED IN THIS SECTION. IF | | | PANIC BARS ARE REQUIRED DUE TO EQUIPMENT, REVISE PLAN | | | TO NOTE AND REVISE TO OUTSWING DOORS. | | | | | | 8. LS201, ROOM 105 IS ASSEMBLY OCCUPANCY WITH AN | | | OCCUPANT LOAD OVER 49. EXIT STRATEGY IS NOT CLEAR. THE | | | SE AND SW DOORS APPEAR TO LEAD TO THE SAME EXIT DOOR | | | AND NEITHER HAS EXIT LIGHTS. THE DOOR AT THE REAR LEADS | | | TO A GREEN ROOM, PURPOSE UNKNOWN WITH NO OCCUPANT LOAD | | | SHOWN, WITH AN INSWING DOOR. | | | | | | REVISE PLAN TO CLARIFY EXIT STRATEGY, INCLUDE EXIT | | | LIGHTS AS NEEDED, NUMBER OF OCCUPANTS FOR EACH SPACE. | | | | | | NOTE THAT PER FBC 1008.1.10 ALL DOORS IN THE MEANS OF | | | EGRESS FOR ASSEMBLY TO HAVE PANIC DEVICES, FBC 1004.6. | | | THE DOOR SCHEDULE WAS NOT REVIEWED AT THIS TIME AS | | | EGRESS PATH IS NOT CLEAR. | | | | | | 9. LS201, NO INFORMATION WAS PROVIDED REGARDING THE | | | EXISTING COMMAND CENTER AND HOW EXITING WILL BE | | | AFFECTED BY THE PROPOSED NEW COMMAND CENTER. PROVIDE | | | INFORMATION REGARDING THE DOORS WHICH PREVIOUSLY LED | | | DIRECTLY TO THE OUTDOORS WHICH WILL NOW LEAD TO THE NEW | | | COMMAND CENTER. IF THESE DOORS ARE EXIT DOORS, HOW WILL | | | TRAVEL DISTANCE BE AFFECTED? WHAT OCCUPANCY | | | CLASSIFICATIONS DO THESE DOORS SERVE? | | | | | | 10. LS201, EXITING FOR THE UPS ROOM IS NOT CLEAR. ONE | | | DOOR LEADS TO THE EXISTING COMMAND CENTER, THE OTHER | | | DOOR LEADS THROUGH THE ELECTRICAL ROOM. FBC 1014.2, | | | REVISE PLAN TO SHOW COMPLIANCE. | | | | | | 11. LS202, THE WEST CONFERENCE ROOM IS NOT LABELED AND | | | LACKS AN OCCUPANT LOAD, FBC 107, SEE ALSO OTHER | | | COMMENTS REGARDING OCCUPANT LOAD. REVISE PLAN TO | | | INCLUDE ALL OCCUPANT LOAD FOR ALL SPACES. | | | | | | 12. OCCUPANT LOAD TOTALS DO NOT APPEAR CORRECT. FOR | | | INSTANCE, LS202 SHOWS OCCUPANT LOAD FOR THE BUSINESS | | | AREA WHICH IS DIVIDED INTO ROOMS CALCULATED ON THE | | | TOTAL RATHER THAN BY ROOM. FBC 107 AND FBC CHAPTER 10, | | | AN ACCURATE OCCUPANT LOAD IS REQUIRED FOR C.O., TO | | | CONFIRM COMPLIANCE WITH LIFE SAFETY REQUIREMENTS, AND | | | FOR THRESHOLD BUILDING DETERMINATION. REVISE PLAN. | | | | | | 13. FBC 1014.2, CLARIFY THE NUMBER OF OCCUPANTS | | | CALCULATED TO TRAVEL THROUGH THE BREAK ROOM TO REACH | | | THE REQUIRED EXIT. HOW WILL THE EGRESS PATH BE KEPT | | | CLEAR OF TABLES AND CHAIRS? ASSEMBLY IS CONSIDERED A | | | HIGHER RISK THAN BUSINESS. REVISE PLAN TO CLARIFY HOW | | | COMPLIANCE WITH THE REQUIREMENT THAT A DISCERNIBLE PATH | | | OF EGRESS TRAVEL TO AN EXIT WILL BE MET. FEEL FREE TO | | | CONTACT ME TO DISCUSS. | | | | | | 14. REVISE PLAN TO CLARIFY PURPOSE OF THE STAGE SHOWN | | | ON THE FIRST FLOOR. VERTICAL ACCESSIBILITY MAY APPLY, | | | FBC 5TH EDITION ACCESSIBILITY 201.1.1, 203.9. IF | | | EXCEPTIONS ARE APPLICABLE, REVISE PLAN TO INCLUDE | | | EXCEPTION(S). | | | | | | 15. A321, A322, A323, TEXT IS NOT LEGIBLE IN SEVERAL | | | LOCATIONS; CHECK ALL AND PROVIDE LEGIBLE TEXT. | | | | | | 16. A760, THE GRAB BAR IS TO BE INSTALLED 33 TO 36 | | | INCHES MEASURED TO THE TOP OF THE BAR, FBC 5TH EDITION | | | ACCESSIBILITY 609.4. THE DETAILS DO NOT COMPLY AS THE | | | BAR IS SHOWN TOO HIGH, REVISE ALL AFFECTED DETAILS. | | | | | | 17. A800 SHOWS CARD READERS ON SOME DOORS. A SEPARATE | | | PERMIT IS REQUIRED FOR ACCESS CONTROL. THIS ITEM IS NOT | | | BEING REVIEWED AT THIS TIME. | | | | | | 18. S001, TABLE 1607.1, REVISE TO INCLUDE ASSEMBLY AREA | | | LIVE LOAD. | | | | | | 19. THREE SETS OF PLANS REQUIRED; SEE THRESHOLD REVIEW. | | | | | | 20. A CONSTRUCTION TRAILER IS SHOWN ON SHEET M104. THIS | | | REQUIRES A SEPARATE PERMIT AND HAS NOT BEEN REVIEWED AT | | | THIS TIME. | | | | | | 21. SEE IMPACT FEE REVIEW. THIS IS TO BE PAID PRIOR TO | | | PERMIT ISSUANCE. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2017-01-14 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2017-01-14 |
Time |
14:09 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2017-01-14 |
Time |
14:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2016-12-01 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-12-01 |
Time |
12:10 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-12-01 |
Time |
12:09 |
Sent To |
|
|
| Notes |
| 2016-12-01 12:09:54 | 2ND ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | PROVISO FOR NEW COMMENT: | | | | | | | | | 1. GFCI PROTECTION REQUIRED FOR ALL 15A-20A 125V | | | RECEPTACLES PER NEC 210.8B2 IN LOCKER AREA AND DRINKING | | | FOUNTAIN NEC 422.52 | | | | | | 1ST REVIEW COMMENT TO BE ADDRESSED: | | | 10. MAIN ELECTRICAL ROOMS MUST COMPLY WITH NEC | | | 110.26C2, THERE SHALL BE ONE ENTRANCE AT EACH END OF | | | THE WORKING SPACE. SHOW TWO MEANS OF EGRESS THAT | | | COMPLIES WITH EGRESS REQUIREMENTS, AS ONE OF THE DOOR | | | OPENS INTO A HAZARD AREA AND DOES NOT HAVE THE | | | CLEARANCE REQUIREMENTS. ALSO NEC 110.26C3 REQUIRES | | | PERSONNEL DOORS TO BE EQUIPPED WITH PANIC HARDWARE AND | | | OPEN IN THE DIRECTION OF EGRESS. DOOR MUST SWING IN THE | | | DIRECTION OF EGRESS. (TO COMPLY WITH NEC 110.26C3 | | | DOUBLE DOORS ADJACENT TO FACP MUST BE SHIFTED TO THE | | | RIGHT, LOCATION OF PANEL LDPA) | | | 11. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | | QUESTIONS REGARDING THIS PROJECT. | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-10-11 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-10-11 |
Time |
08:34 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-10-11 |
Time |
07:58 |
Sent To |
|
|
| Notes |
| 2016-10-11 09:01:22 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE | | | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE | | | PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL SITE | | | LIGHTING AND ASSOCIATED EQUIPMENT, GENERATOR, ALL LOW | | | VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE | | | ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA, WIRELESS | | | SYSTEMS, HOOD SYSTEMS, LIGHTNING PROTECTION GENERATORS, | | | ETC. A NOTE WILL SUFFICE. | | | 2. ADD A NOTE TO MAINTAIN ALL ELECTRICAL EQUIPMENT | | | ABOVE THE BASELINE FLOOD ELEVATION PER STATE AND CITY | | | REGULATORY AGENCIES. | | | 3. GFCI PROTECTION REQUIRED FOR ALL 15A-20A 125V | | | RECEPTACLES PER NEC 210.8B2 IN KITCHEN AREA. | | | 4. RISER DIAGRAM AND PANEL SCHEDULES- PLEASE PROVIDE | | | AVAILABLE FAULT CURRENT AVAILABLE AT THE FPL SERVICE. | | | ATTACH TO DOCUMENTS LETTER FROM FLORIDA POWER & LIGHT | | | INDICATING AIC. SHOW AIC CALCULATION BASED ON | | | INFORMATION PROVIDED BY UTILITY FOR APPROVAL. NEC | | | 110.24 FBC 107 | | | 5. PLEASE ADD A NOTE TO ONE-LINE SHEET TO REFLECT THE | | | REQUIREMENTS OF NEC 700.7A FOR SIGNAGE | | | 6. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO | | | INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC | | | 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE | | | VERBIAGE IN CODE. | | | 7. PLEASE LABEL ATS?S ON ONE-LINE TO BE SEPARATELY | | | DERIVED SYSTEM AS SHOWN ON DETAIL SHEET. | | | 8. CLARIFY NOTE K ON RISER DIAGRAM, IF THESE ARE THE | | | INTERLOCKS PLEASE ADD AS NOTE TO PLANS. | | | 9. PROVIDE VOLTAGE DROP CALCULATIONS NOT ONLY FOR | | | FEEDERS BUT ALSO THE BRANCH CIRCUIT FBC EC 505.7 | | | 10. MAIN ELECTRICAL ROOMS MUST COMPLY WITH NEC | | | 110.26C2, THERE SHALL BE ONE ENTRANCE AT EACH END OF | | | THE WORKING SPACE. SHOW TWO MEANS OF EGRESS THAT | | | COMPLIES WITH EGRESS REQUIREMENTS, AS ONE OF THE DOOR | | | OPENS INTO A HAZARD AREA AND DOES NOT HAVE THE | | | CLEARANCE REQUIREMENTS. ALSO NEC 110.26C3 REQUIRES | | | PERSONNEL DOORS TO BE EQUIPPED WITH PANIC HARDWARE AND | | | OPEN IN THE DIRECTION OF EGRESS. DOOR MUST SWING IN THE | | | DIRECTION OF EGRESS. | | | 11. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL | | | FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS | | | REGARDING THIS PROJECT. | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2016-10-27 |
|
|
Cont ID |
|
| Sent By |
mkhan |
Date |
2016-11-14 |
Time |
|
Rev Time |
1.00 |
| Received By |
mkhan |
Date |
2016-10-27 |
Time |
|
Sent To |
I |
|
| Notes |
| 2016-10-27 15:59:39 | ENGINEERING PLANS DATED 10/18/2016 HAVE BEEN APPROVED | | | THROUGH ENGINEERING SERVICES DIVISION FOR R-O-W UTILITY | | | CONNECTIONS. | | | | | | APPLICANT IS HEREBY NOTIFIED THAT PRIOR TO COMMENCEMENT | | | OF CONSTRUCTION OF PRIVATE UTILITES ON THIS SITE, A | | | SEPARATE PERMIT MUST BE OBTAINED FROM THE CONSTRUCTION | | | SERVICES DEPARTMENT. | | | | | | 3:45 PM | | | 10-27-2016 | | | MOSTAQUE KHAN | | | LAND DEVELOPMENT ENGINEER |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2017-01-17 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-01-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-01-17 |
Time |
15:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2016-11-23 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-11-23 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-11-22 |
Time |
15:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2016-10-03 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-10-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-09-27 |
Time |
16:09 |
Sent To |
|
|
| Notes |
| 2016-09-30 16:12:10 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) SHEET C 8 - THE PROPOSED INDICATED FDC CONFIGURATION | | | IS NOT COMPLIANT. THE FDC SHAL NOT BE IN A POSITION TO | | | PROVIDE PRESSURE TO THE FIRE LINE SUPPLY SYSTEM. | | | | | | | | | PER NFPA 13 | | | | | | 8.17.2.4* ARRANGEMENT. SEE FIGURE 8.17.2.1. | | | 8.17.2.4.1* THE FIRE DEPARTMENT CONNECTION SHALL BE ON | | | THESYSTEM SIDE OF THE WATER SUPPLY CHECK VALVE. | | | | | | 8.17.2.4.2 FOR SINGLE SYSTEMS, THE FIRE DEPARTMENT | | | CONNECTION SHALL BE INSTALLED AS FOLLOWS: | | | (1) WET SYSTEM?ON THE SYSTEM SIDE OF SYSTEM CONTROL, | | | CHECK, AND ALARM VALVES (SEE FIGURE A.8.16.1.1) | | | | | | | | | A.8.17.2.4 THE CHECK VALVE SHOULD BE LOCATED TO | | | MAXIMIZE ACCESSIBILITY AND MINIMIZE FREEZING POTENTIAL. | | | IT IS RECOMMENDED THAT THE CHECK VALVE BE LOCATED TO | | | REDUCE THE LENGTH OF NONPRESSURIZED PIPE IN THE FIRE | | | DEPARTMENT CONNECTION SUPPLY LINE. | | | A.8.17.2.4.1 THE FIRE DEPARTMENT CONNECTION SHOULD BE | | | CONNECTED TO THE SYSTEM RISER. FOR SINGLE SYSTEMS, IT | | | IS AN ACCEPTABLE ARRANGEMENT TO ATTACH THE FIRE | | | DEPARTMENT CONNECTION TO ANY POINT IN THE SYSTEM, | | | PROVIDED THE PIPE SIZE MEETS THE REQUIREMENTS OF | | | 8.17.2.3. | | | | | | | | | 2) SHEET C 8 - THE LOCATION OF THE FDC AND HYDRANT IS | | | RECOMENDED TO BE PLACED CLOSER TO THE BUILDING, OR THE | | | FDC ATTACHED TO THE BUILDING, CLOSER TO THE AREA OF FD | | | ACCESS. THIS WAS PREVIOUSLY STATED DURING PPRC | | | COMMENTS. | | | | | | | | | 3) SHEET LS 100 - THERE ARE INCORRECT REFERENCES AND | | | EDITIONS TO THE FIRE CODES. | | | | | | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE | | | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING | | | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER | | | APPLICABLE CODES OR STANDARDS. | | | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS | | | OF NFPA 13, 2010 EDITION. | | | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | | NFPA 72, 2010 EDITION. | | | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | | NFPA 241, 2009 EDITION. | | | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS | | | OF NFPA 10, 2010 EDITION. | | | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. | | | CLEAN AGENT SYSTEMS SHALL COMPLY WITH NFPA 2001, 2012 | | | EDITION. | | | EMERGENCY AND STANDBY POWER SYSTEMS SHALL COMPLY WITH | | | NFPA 110, 2013 EDITION. | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2017-01-28 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-01-28 |
Time |
06:47 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-01-05 |
Time |
11:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-01-04 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2017-01-04 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2016-11-16 |
Time |
15:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-11-15 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2016-11-15 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2016-11-14 |
Time |
14:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-10-29 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-10-29 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-09-22 |
Time |
09:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2016-12-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-12-08 |
Time |
07:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-12-08 |
Time |
07:34 |
Sent To |
|
|
| Notes |
| 2016-12-08 07:36:00 | MU -2016-028473-0000 | | | ROUTED STAMPED PLAN, RECEIPT TO RECORDS | | | | | 2016-11-28 13:44:53 | SHILL'S DESK |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2016-10-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-10-12 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-10-12 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2016-10-12 15:13:05 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED. | | | THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING | | | THAT FEES DUE WERE PAID. | | | | | | 561-233-5025 FOR MORE INFORMATION | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2017-01-12 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-01-12 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-01-12 |
Time |
11:16 |
Sent To |
|
|
| Notes |
| 2017-01-12 11:58:41 | MECHANICAL PROVISOS: | | | | | | 1) COMMISSIONING OF THE MECHANICAL AND ELECTRICAL | | | LIGHTING SYSTEMS REQUIRED. A HOLD IS PLACED ON THE CO | | | PENDING RECEIPT OF THE REPORT. | | | | | | 2) SITE SPECIFIC WIND LOAD ENGINEERING MUST BE | | | SUBMITTED TO THE BUILDING DEPAQRTMENT PRIOR TO | | | INSPECTION. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2016-11-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-11-21 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-11-21 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2016-11-21 14:27:35 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16090832 | | | 11/21/16 | | | | | | 1) THE REVISED ENERGYGAUGE ASHRAE 90.1 SUBMITTAL DOES | | | NOT INCLUDE COMPLIANCE DATA FOR DX-1, OR EFFICIENCY | | | RATINGS OF THE CRU SYSTEMS- SEE TABLE C403.2.3(10) | | | FBC-14 ENERGY CONSERVATION. CONCERNING THE AHU'S, REFER | | | TO TABLE C403.2.3(1) AND PROVIDE COMPLIANCE DATA PER | | | THE AHRI TEST PROCEDURE FOR WATER COOLED UNITS (IF | | | APPLICABLE). | | | | | | 2) THE REQUESTED EXHAUST VENTILATION CALCULATIONS WERE | | | NOT INCLUDED IN THE ASHRAE VENTILATION SUBMITTAL. | | | | | | 3) THE ASHRAE VENTILATION SUBMITTAL INDICATES 1165 CFMS | | | OF O/A FOR AHU-3, THE SCHEDULE INDICATES THE UNIT | | | PRODUCES 2100 CFMS- IS THIS CORRECT? | | | | | | 4) COMMISSSIONING IS REQUIRED FOR BOTH THE MECHANICAL | | | SYSTEMS AND THE ELECTRICAL POWER AMND LIGHTING SYSTEMS- | | | PLEASE PROVIDE A PLAN- SEE SECTION C408.1. | | | | | | 5) ADVISORY: DEFERRED SUBMITTALS ARE REQUESTED FOR THE | | | WIND LOAD ENGINEERING FOR INSTALLATION OF ALL EXTERIOR | | | MECHANICAL EQUIPMENT AND THE REQUIRED FL. PRODUCT | | | APPROVALS AND/OR MIAMI-DADE NOAS FOR LOUVERS, AC STANDS | | | ETC. PLEASE REVIEW THE FOLLOWING SECTION FROM THE WPB | | | AMENDMENTS AND PROVIDE A LIST OF EQUIPMENT AND | | | COMPONENTS TO BE DEFERRED. | | | | | | A) DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS. | | | FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS | | | ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE | | | NOT SUBMITTED AT THE TIME OF THE | | | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE | | | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL | | | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF | | | THE BUILDING OFFICIAL. THE REGISTERED DESIGN | | | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE | | | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR | | | REVIEW BY THE BUILDING OFFICIAL. | | | | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | B) DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT | | | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE | | | DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-09-29 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-09-29 |
Time |
17:01 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-09-29 |
Time |
17:01 |
Sent To |
|
|
| Notes |
| 2016-09-29 17:02:24 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16090832 | | | 9/29/16 | | | | | | 1) PROVIDE VENTILATION CALCULATIONS FOR O/A AND EXHAUST | | | FOR ALL ROOMS AND SPACES USING THE DESIGN PARAMETERS | | | SHOWN IN TABLE 403.3 FBC-14 MECHANICAL. PROVIDE A | | | SCHEDULE INDICATING THE REQUIRED AND PROVIDED CFMS OF | | | O/A AND EXHAUST. THE DESIGN CRITERIA TABLE ON M-101 | | | DOES NOT APPEAR TO BE CONSISTENT WITH TABLE 403.3, AND | | | DOES NOT SHOW ANY EXHAUST CALCULATIONS. | | | | | | 2) DESIGN EFFICIENCIES AND CRITERIA FOR THE AHU'S ARE | | | NOT LISTED IN THE ENERGYGAUGE SUBMITTAL OR IN THE AHU | | | SCHEDULE ON SHEET M-102. | | | | | | 3) THE ENERGYGAUGE SUBMITTAL SHOWS COMPLIANCE DATA FOR | | | CRU'S 12, 34, & 56, HOWEVER THE SCHEDULE INDICATES | | | CRU'S 1, 2, 3, 4, 5, & 6. | | | | | | 4) PROVIDE PIPING SYSTEM COMPLIANCE DATA IN THE | | | ENERGYGAUGE SUBMITTAL. | | | | | | 5) THE AC CALCULATIONS AND SCHEDULE FOR THE COMPUTER | | | SYSTEMS DO NOT MATCH IN SYSTEM IDENTIFICATIONS, NUMBER | | | OF SYSTEMS, AND CAPACITIES OF SYSTEMS. | | | | | | 6) THE HEATING CAPACITIES OF THE AHU-3 TERMINAL BOXES | | | ARE EXCEEDING THE CALCULATED HEATING COIL LOADS. | | | | | | 7) M-103: PLEASE PROVIDE THE CHILLED WATER DATA IN THE | | | CHILLER SCHEDULE. | | | | | | 8) SHEET M-104: PROVIDE AN EQUIPMENT SCHEDULE FOR THE | | | TEMPORARY AIR HANDLER AND INDICATE HOW THE DUCTWORK | | | WILL BE SUPPORTED, PROTECTED, AND SEALED AT THE | | | BUILDING PENETRATION | | | | | | 9) M-201 & M-202: THE TEMPORARY AC SYSTEMS ARE LISTED | | | AS BOTH AC-TEMP AND RTU-TEMP- PLEASE CLARIFY. INDICATE | | | HOW THE AC EQUIPMENT WILL BE MOUNTED (EQUIPMENT IS NOT | | | SHOWN ON A TRAILER) AND HOW THE DUCTWORK WILL BE | | | SUPPORTED, PROTECTED, AND SEALED AT THE PENETRATION OF | | | THE BUILDING. A) PLEASE NOTE THAT A GAS PIPING PLAN AND | | | ISOMETRIC WILL BE REQUIRED FOR THE HEAT. | | | | | | 10) M-211: FIRE DAMPERS, OR SYMBOLS FOR FIRE DAMPERS, | | | APPEAR TO BE MISSING AT THE DUCT PENETRATIONS ALONG THE | | | EAST WALL OF THE CONTROL THEATER- SECTION 607.5.2. | | | | | | 11) M-211: PLEASE CLARIFY THE PURPOSE OF EF-1-1 & | | | EF-2-1 AND HOW THESE FANS WERE SIZED. | | | | | | 12) M-212: SEE COMMENT #9 CONCERNING MISSING FIRE | | | DAMPERS FOR DUCTS PENETRATING THE FIRE-RATED WALL. IT | | | APPEARS THAT MANY OTHER DAMPERS ARE MISSING WHERE DUCTS | | | PENETRATE FIRE-RATED CORRIDOR AND OTHER SEPARATION | | | WALLS. PLEASE OVERLAY THE LIFE SAFETY PLANS ON THE | | | MECHANICAL LAYOUT PAGES SO THAT RATED WALLS ARE CLEARLY | | | SHOWN. | | | | | | 13) M-212: EF 4-1 AND TG-1 ARE UNDERSIZED FOR THE | | | MINIMUM REQUIRED EXHAUST CFMS FROM THE MENS RESTROOM | | | 180 PER TABLE 403.3- 250 CFMS. | | | | | | 14) M-212: PROVIDE AN EXHAUST VENTILATION CALCULATION | | | FOR THE LOCKER ROOM- TABLE 403.3. | | | | | | 15) M-211- M222: PLEASE LABEL OR TAG ALL TB ACCESS | | | PANELS, AND PROVIDE ACCESS TO ABOVE CEILING EXHAUST | | | FANS- SECTION 306.1. | | | | | | 16) PROVIDE CHILLED WATER PIPING DETAILS- TYPE OF | | | PIPING, JOINERY, INSULATION. | | | | | | 17) PROVIDE ENGINEERED STRUCTURAL DETAILS AND THE WIND | | | LOAD DESIGN CRITERIA FOR INSTALLATION OF THE CHILLERS | | | AND THE PUMPS- SECTION 301.15. | | | | | | 18) SUBMIT FL. PRODUCT APPROVALS AND/OR MIAMI-DADE | | | NOA'S FOR ALL AIR INTAKE AND EXHAUST LOUVERS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
N |
Date |
2016-10-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-10-12 |
Time |
17:10 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-10-12 |
Time |
17:10 |
Sent To |
|
|
| Notes |
| 2016-10-12 17:12:08 | ALTHOUGH A PORTION OF THE PARCEL IS LOCATED IN SFHA | | | ZONE AH, THE EXISTING STRUCTURE AND PROPOSED ADDITION | | | IS LOCATED ENTIRELY WITHIN FLOOD ZONE B PER SURVEY AND | | | SITE PLAN PREPARED BY ARCHITECT WHICH BOTH DEPICT THE | | | LINE BETWEEN ZONES A AH AND B. | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2017-01-28 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-01-28 |
Time |
06:46 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-01-26 |
Time |
12:08 |
Sent To |
|
|
| Notes |
| 2017-01-28 04:18:24 | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | ****PROVISOS**** | | | THE FOLLOWING ITEMS WILL BE CONSIDERED DEFERRED | | | SUBMITTALS PER THE CITY OF WEST PALM AMENDMENTS TO THE | | | FLORIDA BUILDING CODE SEC.107.3.4.2. | | | DOCUMENTATION SHALL BE SUBMITTED TO THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE FOR REVIEW | | | WITH A NOTATION INDICATING THE | | | DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND | | | FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF THE | | | BUILDING PRIOR TO SUBMITTAL | | | FOR REVIEW BY THE BUILDING DIVISION. | | | | | | 1) MANUFACTURER'S SPECIFICATIONS FOR THE WATER TANK. | | | 2) MANUFACTURER'S SPECIFICATIONS FOR THE BLADDER TANK | | | AND SIZE OF THE BLADDER TANK. | | | 3) DETAILS AND DDIMENSIONS FOR THE ANCHORING OF THE | | | WATER TANK, SIZE AND TYPE OF HOLD DOWN STRAPS, TRAFFIC | | | PROTECTION FOR THE PUMPS, SPECS ON THE PUMPS, AND ALL | | | OTHER RELATED EQUIPMENT. | | | 4) MANUFACTURER'S SPECIFICATIONS FOR THE GENERATORS | | | LOCATED IN THE EQUIPMENT CORRAL. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2016-12-15 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-12-15 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-12-08 |
Time |
05:40 |
Sent To |
|
|
| Notes |
| 2016-12-15 12:03:06 | 1) SUBMIT FACTORY SIZING CALCULATIONS CREATED BY SCHIER | | | FOR THE GREASE INTERCEPTOR IN ACCORDANCE WITH 2014 FPC | | | SEC. 1003.2. THE SIZE, TYPE AND LOCATION OF EACH | | | INTERCEPTOR SHALL BE APPROVED BY THE PLUMBING | | | OFFFICIAL. CONTACT LEE SCHNEEWEISS OF SCHIER AT | | | 1-800-538-4792 FOR ASSISTANCE. | | | 2) PLEASE PROVIDE A SEQUENCE OF OPEREATIONS FOR THE | | | SANITARY HOLDING TANKS. A RESPONSE WAS SUPPLIED IN THE | | | NARRATIVE BUT THE INFORMATION NEEDS TO BE ON THE PLANS. | | | WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) SHT. A-761, DETAIL 04 - RESTROOMS #183 & #184 SHALL | | | CONTAIN A HANDICAPPED ACCESSIBLE TOILET COMPARTMENT | | | WITHIN EACH RESTROOM. 2014 FBC-ACCESS. SEC.213.3.1. THE | | | REQUEST FOR RELIEF HAS BEEN FORWARDED TO ROBERT BROWN, | | | BUILDING OFFICIAL. | | | 4) SHT. LS-201 - THE FITNESS ROOM SHALL BE CALCULATED | | | AT 50 SQUARE FEET PER PERSON PER TABLE1004.1.2.THE | | | RESPONSE NARRATIVE REFERS TO SHT. LS-201 BUT I COULD | | | NOT FIND THIS REVISED INFORMATION ON THE SHEET. | | | CLARIFY. | | | 5) SHT. P302 - INCLUDE THE EMERGENCY (OVERFLOW) STORM | | | DRAINS ON THE STORM DRAIN RISER. SHOW THE PITCH OF THE | | | HORIZONTAL DRAIN. | | | 6) SHT. A401 - SHOW THE LOCATION OF THE ROOF DRAINS AND | | | OVERFLOW DRAINS ON THE PLAN. | | | 7) SHT. P202 - FLOOR DRAINS ARE SHOWN IN ROOMS #109, | | | #190, #1191, #193, #233 & #290. THESE DRAINS ARE | | | CONNECTED TO THE SANITARY AND WILL REQUIRE TRAP PRIMERS | | | PER 2014 FPC SEC.1002.4. | | | 8) SHT. P302 - THERE ARE STILL SECTIONS OF THE SANITARY | | | SYSTEM (VENTS, BUILDING DRAIN,..) THAT ARE NOT SIZED. | | | WPB AMEND. TO FBC SEC. 107.2.1. | | | 9) SHT. A-761 - CLEARLY SHOW THE CONTROL WALL IN THE | | | HANDICAPPED ACCESSIBLE TRANSFER SHOWERS. THE GRAPHICS | | | ARE SO LIGHT THAT THE CONTROL WALL IS DIFFICULT TO | | | DETERMINE. WPB AMEND. TO FBC SEC. 107.2.1. | | | 10) SUBMIT DETAILS FOR THE GENERATORS IN THE EQUIPMENT | | | CORRAL. SUBMIT INFORMATION ON THE FUEL SOURCE FOR THE | | | GENERATORS, PIPING DETAILS (IF APPLICABLE) ETC.WPB | | | AMEND. TO FBC SEC. 107.2.1.2ND REQUEST.THE NARRATIVE | | | REFERS TO THE ELECTRICAL PLANS FOR INFORMATION. I COULD | | | NOT FIND ANY INFORMATION ON THE GENERATOR IN THE | | | ELECTRICAL PLANS. CLARIFY. | | | 11) SHT. A-701 - DETAIL 01- G6 ACCESSIBLE SHOWER - THE | | | SHOWER CONTROLS, FAUCET AND SHOWER SPRAY UNIT IN THE | | | ACCESSIBLE TRANSFER SHOWERS SHALL BE LOCATED ON THE | | | SIDE WALL OPPOSITE THE SEAT 38 INCHES MINIMUM AND 48 | | | INCHES MAXIMUM ABOVE THE SHOWER FLOOR AND SHALL BE | | | LOCATED ON THE CONTRL WALL 15 INCHES MAXIMUM FROM THE | | | CENTERLINE OF THE SEAT TOWARD THE SHOWER OPENING.2014 | | | FAC SEC.608.5.1. THE DETAIL SHOWS THIS AS AN "OPTIONAL | | | SHOWER HEAD AND CONTROL LOCATION." THIS IS NOT | | | OPTIONAL. CLEARLY SHOW COMPLIANCE WITH THIS CODE | | | SECTION. | | | 12) GRAB BARS IN THE ACCESSIBLE TRANSFER SHOWERS SHALL | | | COMPLY WITH 2014 FAC SEC.608.3.1. CLEARLY SHOW | | | COMPLIANCE WITH THIS CODE SECTION ON THE PLANS. | | | 13) NOTE: THE FINISHED CLEAR INSIDE DIMENSIONS OF THE | | | ACCESSIBLE TRANSFER SHOWERS SHALL BE 36 INCHES BY 36 | | | INCHES MEASURED AT THE CENTER POINTS OF OPPOSING SIDES. | | | FINISHED DIMENSIONS OTHER THAN THIS IS NON-COMPLIANT. | | | 14) SHT. P-201 - WHERE IS THE SANITARY LINE FOR ROOM | | | #187? 2ND REQUEST. | | | 15) CLEARLY SHOW THE LOCATION OF GRAB BARS IN THE | | | HANDICAPPED ACCESSIBLE TRANSFER SHOWERS. COMPLY WITH | | | 2015 FBC SEC.608.3.1 AND FIGURE 608.3.1. | | | 15) THE FOLLOWING ITEMS WILL BE CONSIDERED DEFERRED | | | SUBMITTALS. DOCUMENTATION SHALL BE SUBMITTED FOR REVIEW | | | PRIOR TO WORK STARTING ON THESE ITEMS. | | | | | | 1) MANUFACTURER'S SPECIFICATIONS FOR THE WATER TANK. | | | 2) MANUFACTURER'S SPECIFICATIONS FOR THE BLADDER TANK | | | AND SIZE OF THE BLADDER TANK. | | | 3) DETAILS AND DIMENSIONS FOR THE ANCHORING OF THE | | | WATER TANK, SIZE AND TYPE OF STRAPS, TRAFFIC PROTECTION | | | FOR THE PUMPS, SPECS ON THE PUMPS, ETC. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2016-10-29 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-10-29 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-10-18 |
Time |
13:31 |
Sent To |
|
|
| Notes |
| 2016-10-21 14:44:52 | 1) PROVIDE A SECTION DETAIL OF THE 2 SANITARY HOLDING | | | TANKS SHOWING THE CONSTRUCTION OF THE TANK IN DETAIL. | | | ARE THEY DESIGNED AS SEPTIC TANKS ON THE INTERIOR? | | | CLARIFY.WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) SUBMIT A BRIEF NARRATIVE AS TO THE | | | OPERATION/SEQUENCING OF THE TANKS WHEN THEY ARE PUT | | | INTO OPERATION. AS PIPED, IT IS CONFUSING TO DETERMINE | | | HOW THEY WILL WORK.WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) A GREASE INTERCEPTOR IS REQUIRED FOR THE KITCHEN PER | | | THE 2014 FBC- PLUMBING, SEC.1003.1, 1003.3.1. | | | 4) SUBMIT SIZING CALCULATIONS FOR THE GREASE | | | INTERCEPTOR.THE SIZE, TYPE AND LOCATION OF EACH | | | INTERCEPTOR SHALL BE APPROVED BY THE PLUMBING OFFICIAL. | | | FPC SEC.1003.2. | | | 5) THE BREAKROOM SINK & COUNTER SHALL COMPLY WITH 2014 | | | FBC-ACCESSIBILITY SECS.212, 606.SEE SHT. A-741. | | | 6) 2ND FLOOR RESTROOM # 280 REQUIRES AN ACCCESSIBLE | | | AMBULATORY COMPARTMENT THAT COMPLIES WITH FAC | | | SEC.213.3.1 & SEC.604.8.2 PER 2014 FBC-ACCESS. | | | 7) SHT. A401 - THE STORM DRAINAGE TABLE ON THIS SHEET | | | DOES NOT SEEM TO INCLUDE ONE-HALF THE AREA OF VERTICAL | | | WALLS THAT CAN DIVERT RAINWATER TO THE ROOF. SEE 2014 | | | FPC SEC.1106.4. | | | 8) SHT. A 401 - THE CODED NOTES REFER TO SHTS. A-450 | | | AND A-451 FOR SCUPPER AND ROOF DRAIN DETAILS AND THERE | | | IS NO ROOF DRAIN DETAIL ON A-450. MOST OF THE DETAILS | | | ARE ON SHT. A- 452 .PLEASE REVISE THE NOTES. ALSO, THE | | | PLANS SHOW ROOF DRAIN DETAILS BUT THERE ARE SCUPPERS | | | SHOWN ON THE PLANS.CLARIFY. | | | 9) SHT.A-760 - THE GRAB BARS SHALL BE MEASURED FROM | | | FINISH FLOOR TO THE TOP OF THE GRIPPING SURFACE. FAC | | | SEC.609.4. | | | 10) SHT. A-761 - SHOW THE CLEAR INSIDE DIMENSIONS OF | | | THE STANDARD AND HANDICAPPED ACCESSIBLE SHOWERS ON SHT. | | | A-761 | | | 11) AT LEAST ONE LAVATORY IN THE RESTROOMS SHAL COMPLY | | | WITH 2014 FAC SEC.606 AND SHALL NOT BE LOCATED IN A | | | TOILET COMPARTMENT. FAC SEC.213.3.4. | | | 12) RESTROOMS #183 & 184 SHALL CONTAIN A HANDICAPPED | | | ACCESSIBLE TOILET COMPARTMENT WITHIN EACH RESTROOM. | | | 2014 FAC SEC. 213.3.1. | | | 13) WHERE MORE THAN ONE URINAL IS PROVIDED, AT LEAST | | | ONE SHALL COMPLY WITH FAC SEC. 605. IDENTIFY THE | | | HANDICAPPED URINALS IN THE RESTROOMS AND SHOW | | | COMPLIANCE W/ FAC SEC. 605. | | | 14) SHT. LS-201 - THE FITNESS ROOM IS CALCULATED AT 100 | | | SQUARE FEET PER PERSON BUT SHOULD BE CALCULATED AT 50 | | | SQUARE FEET PER PERSON PER 2014 FBC TABLE 1004.1.2. | | | 15) SHT. LS-100 - PROJECT SUMMARY DOES NOT INCLUDE THE | | | STORAGE OCCUPANCY OR THE SQUARE FOOTAGE. CLARIFY. | | | 16) SHT.P201 - WHERE IS THE SANITARY LINE FOR ROOM | | | #187? | | | 17) THE KITCHEN (ROOM #124) WASTE SHALL DISCHARGE | | | THROUGH A GREASE INTERCEPTOR PER 2014 FPC SEC.1003.3.1. | | | 18) SUBMIT A CONDENSATE RISER DIAGRAM FOR REVIEW. WPB | | | AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3. | | | 19) SUBMIT A STORM WATER RISER IF ROOF DRAINS ARE GOING | | | TO BE INSTALLED. WPB AMEND. TO FBC SEC.107.2.1.THE | | | STRUCTURE SHALL BE PROVIDED WITH EMERGENCY (OVERFLOW) | | | ROOF DRAINS OR SCUPPERS PER FPC SEC. 1108. | | | 20) SHT. P202 - FLOOR DRAINS ARE SHOWN IN ROOMS #109, | | | #190, #191, #193, #233, & # 290.WHAT WILL BE | | | DISCHARGING INTO THESE FLOOR DRAINS? CONDENSATE WASTE | | | SHALL NOT DISCHARGE INTO THE SANITARY SYSTEM PER CITY | | | OF WPB CODE OF ORDINANCES CHAPT. 90, ART. III, SEC. | | | 90-126 (B) (5). TRAP PRIMERS MAY BE REQUIRED ON THESE | | | FLOOR DRAINS PER FPC SEC.1002.4. | | | 21) SHT. P-222 - THE PLAN SHOWS A 3 INCH WASTE & 3 INCH | | | CONDENSATE DRAIN DOWN IN CORRIDOR #026. CLARIFY. | | | 22) SHT.P-301 - THE MOP SINK IN ROOM #230 IS NOT DHOWN | | | ON THE SANITARY OR WATER RISER DIAGRAMS. CLARIFY. | | | 23) SHT. P-302 - SIZE ALL VENTS, STACKS, ALL WET | | | SECTIONS OF THE WASTE STACKS, & ALL SECTIONS OF THE | | | BUILDING DRAIN. WPB AMEND. TO FBC SEC.107.2.1. | | | 24) SHT. P-302 - PLEASE IDENTIFY THE RISERS ON SHTS. | | | P-302 & P-303 AS TO THEIR SPECIFIC AREAS IN THE | | | BUILDING. THIS WILL HELP EXPEDITE THE RE-REVIEW. WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 25) SIZE THE WATER RISERS IN THEIR ENTIRETY. LABEL THE | | | RISERS TO CORRELATE WITH THEIR LOCATION ON THE FLOOR | | | PLAN.WPB AMEND. TO FBC SEC. 107.2.1. | | | 25) SUBMIT A COMPLETE WATER RISER FOR REVIEW THAT | | | BEGINS AT THE SOURCE TO THE END POINT. WPB AMEND. TO | | | FBC SEC. 107.2.1, 107.3.5.1.3.3. | | | 26) SUBMIT A COMPLETE SANITARY RISER DIAGRAM FOR | | | REVIEW. THE RISER SHALL INCLUDE THE COMPLETE | | | UNDERGROUND SYSTEM AND ALL BRANCHES FROM THE POINT | | | WHERE THE BUILDING DRAIN EXITS THE BUILDING TO THE END | | | POINT.WPB AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.3. | | | 27) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER | | | TANK. WPB AMEND. TO FBC SEC. 107.2.1. | | | 28) SUBMIT DETAILS/ MANUF. SPECIFICATIONS FOR THE | | | BLADDER TANK AND INDICATE THE SIZE OF THE BLADDER TANK | | | ON SHT. P-402. | | | 29) SUBMIT DETAILS AND DIMENSIONS OF THE ANCHOR PAD FOR | | | THE WATER TANK.SUPPLY INFORMATION FOR THE ANCHORING OF | | | THE TANK, SIZE AND TYPE OF STRAPS, TRAFFIC PROTECTION | | | FOR THE PUMPS, ANCHORING DETAILS FOR THE WATER TANK ( | | | TYPE, LENGTH OF FASTENERS, ETC.) | | | 30) SHT. P-402 - WATER HEATER DETAIL "A" - THE HOT | | | WATER/ TEMPERED WATER RETURN LINE SHALL BE ROUTED TO | | | THE COLD WATER INLET PIPE OF THE HOT WATER HEATER AND | | | THE COLD WATER INLET PIPE OR THE HOT WATER RETURN | | | CONNECTION OF THE THERMOSTATIC MIXING VALVE 2014 FPC | | | SEC.607.2.2. | | | 31) THERE SHALL BE A BACKFLOW PREVENTER INSTALLED ON | | | THE WATER SUPPLY TO THE WATER TANK. 2014 FPC SEC. | | | 608.12, 608.13. | | | 31) SUBMIT DETAILS FOR THE GENERATORS IN THE EQUIPMENT | | | CORRAL. SUBMIT INFORMATION ON THE FUEL SOURCE FOR THE | | | GENERATORS, PIPING DETAILS ( IF APPLICABLE), ETC.WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 32) INDICATE ON THE PLAN IF ANY LP OR NATURAL GAS WILL | | | BE INSTALLED FOR THIS PROJECT. IF SO, SUBMIT COMPLETE | | | DETAILS ON THE SYSTEM ( PIPING RISER, TYPE OF FUEL, | | | LOCATION OF METER OR TANK), ETC. | | | 33) A CLEAR FLOOR SPACE OF 30 INCHES WIDE MINIMUM BY 48 | | | INCHES LONG MINIMUM MEASURED FROM THE CONTROL WALL | | | SHALL BE PROVIDED FOR THE HANDICAPPED ACCESSIBLE | | | TRANSFER SHOWERS PER 2014 FAC SEC.608.2.1. | | | 34) THE TRANSFER SHOWERS SHALL BE 36 INCHES BY 36 | | | INCHES CLEAR INSIDE DIMENSIONS MEASURED AT THE CENTER | | | POINTS OF OPPOSING SIDES.2014 FAC SEC.608.2.1. | | | 35) THE SHOWER CONTROLS, FAUCET AND SHOWER SPRAY UNIT | | | IN THE ACCESSIBLE SHOWERS SHALL BE LOCATED ON THE SIDE | | | WALL OPPOSITE THE SEAT 38 INCHES MINIMUM AND 48 INCHES | | | MAXIMUM ABOVE THE SHOWER FLOOR AND SHALL BE LOCATED ON | | | THE CONTROL WALL 15 INCHES MAXIMUM FROM THE CENTERLINE | | | OF THE SEAT TOWARD THE SHOWER OPENING.2014 FAC | | | SEC.608.5.1. | | | 36) GRAB BARS IN THE ACCESSIBLE TRANSFER SHOWERS SHALL | | | COMPLY WITH 2014 FAC SEC.608.3.1. | | | 37) THE COUNTER IN THE BREAK ROMM SHALL BE A MAXIMUM OF | | | 34 INCHES FROM THE FINISH FLOOR TO THE TOP OF THE | | | COUNTER PER 2014 FAC SEC. 212 & 606. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2017-07-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-07-10 |
Time |
12:04 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-07-10 |
Time |
12:04 |
Sent To |
|
|
| Notes |
| 2017-07-10 12:05:31 | SEE ROOF SUB PERMIT (17070205) FOR ROOF REVIEW AND NEW | | | PRODUCT APPROVAL SUBMITTED (FL17013) | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2016-10-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-10-18 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-10-18 |
Time |
12:53 |
Sent To |
|
|
| Notes |
| 2016-10-18 12:59:47 | PRODUCT APPROVAL FL2948-R9 WAS SUBMITTED. USE OF A | | | DIFFERENT PRODUCT APPROVAL REQUIRES APPROVAL BY | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL AS A REVISION. | | | PRIOR TO INSTALLATION, A SEPARATE ROOF PERMIT IS | | | REQUIRED. THE APPLICANT IS TO SUBMIT THE APPROVED | | | ASSEMBLY PROPOSED WITH ANY REQUIRED ENGINEERING. | | | | | | ROOF COVERING TO COMPLY WITH THE DESIGN PRESSURES SHOWN | | | ON S003: | | | | | | VULT | | | ZONE 1, -129/+52 | | | ZONE 2, -216/+52 | | | ZONE 3, -161 | | | | | | PLAN VIEW "ZONE 2" (NOT ZONE 2 PER ASCE7-10) IS ENTIRE | | | PERIMITER (ASCE7 ZONE 2 & 3). PLAN VIEW "ZONE 3" | | | APPEARS TO BE 1ST STORY ASCE 7 ZONES 2 & 3. | | | SEE PLAN ON SHEET S003 FOR FURTHER CLARIFICATION. | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
3 |
Status |
P |
Date |
2017-02-03 |
|
|
Cont ID |
|
| Sent By |
kconrad |
Date |
2017-02-03 |
Time |
08:34 |
Rev Time |
0.00 |
| Received By |
kconrad |
Date |
2017-02-03 |
Time |
08:34 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
2 |
Status |
F |
Date |
2016-12-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-12-09 |
Time |
07:07 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-12-09 |
Time |
07:07 |
Sent To |
|
|
| Notes |
| 2017-01-31 12:45:17 | 1/31/17 ADDITIONAL SIGNATURES (3) REQUIRED ON SPECIAL | | | INSPECTOR AGREEMENT, NOTIFIED INSPECTOR, CONTRACTOR, | | | AND OWNER VIA EMAIL. UPON RECEIPT, NOTIFY ME OR | | | SAMANTHA. SAK | | 2016-12-09 07:16:04 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | THIS PROJECT IS EITHER THRESHOLD (REQUIRES SPECIAL | | | INSPECTOR, STATUTORY STATEMENT ON ALL PLANS PER FS | | | 553.79(7)(D), OR IT REQUIRES A RESIDENT INSPECTOR. SEE | | | PREVIOUS REVIEW REGARDING REQUIREMENTS (RESUMES, | | | AGREEMENT, ETC.). | | | | | | ASSEMBLY OCCUPANT LOAD MUST BE ON THE PLANS IN ORDER TO | | | DEMONSTRATE WHETHER OR NOT THIS IS A THRESHOLD JOB. | | | | | | THREE SETS OF ALL PERMIT DOCUMENTS ARE REQUIRED: | | | | | | 1. CITY | | | 2. JOB (ON SITE FOR INSPECTIONS) | | | 3. SPECIAL INSPECTOR OR RESIDENT INSPECTOR | | | | | | FAILURE TO PROVIDE THREE SETS AT TIME OF RESUBMITTAL | | | MAY RESULT IN PERMIT ISSUANCE DELAYS AS A THIRD SET | | | SUBMITTED AFTER REVIEWS HAVE BEEN DONE MAY REQUIRE THAT | | | THE THIRD SET BE ROUTED TO TRADES FOR STAMPING AND/ OR | | | THAT SOMEONE BE ASSIGNED THE RESPONSIBILITY TO VERIFY | | | THIRD SET COMPLETENESS AND ACCURACY AND ADD STAMPS, | | | PROVISOS, REDLINES AS NEEDED. | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
1 |
Status |
F |
Date |
2016-10-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-10-18 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-10-18 |
Time |
13:25 |
Sent To |
|
|
| Notes |
| 2016-10-18 13:27:40 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | GOVERNING CODE: FBC 5TH EDITION (FBC 2014) | | | | | | THIS BUILDING REQUIRES EITHER A SPECIAL INSPECTOR (IF | | | DETERMINED TO BE A THRESHOLD BUILDING) OR A RESIDENT | | | INSPECTOR. | | | | | | ASSEMBLY OCCUPANT LOAD NOT YET DETERMINED, BUT IT IS | | | LIKELY THAT A RESIDENT INSPECTOR WILL BE REQUIRED. SEE | | | POLICY AND AGREEMENT SENT VIA EMAIL. | | | | | | | | | 1. FLORIDA STATUTE 553.71; ANY BUILDING WHICH IS | | | GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH | | | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN | | | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SF IN | | | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 | | | PERSONS. | | | | | | 2. IF A THRESHOLD BUILDING, THE FOLLOWING IS REQUIRED: | | | | | | A. THRESHOLD INSPECTION PLAN; FS 553.79(5)(A), CITY OF | | | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1. THE | | | ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO | | | PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING | | | PURSUANT TO A STRUCTURAL INSPECTION PLAN PREPARED BY | | | THE ENGINEER OR ARCHITECT OF RECORD. THE STRUCTURAL | | | INSPECTION PLAN MUST BE SUBMITTED TO AND APPROVED BY | | | THE ENFORCING AGENCY BEFORE THE ISSUANCE OF A BUILDING | | | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. | | | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO | | | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO | | | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR | | | COMPLIANCE WITH THE PERMITTED DOCUMENTS. | | | | | | B. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. | | | CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD | | | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FS | | | 553.79(5)(A) TO THE MINIMUM INSPECTIONS REQUIRED BY | | | THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED | | | TO BE FILED OUT BY ALL PARTIES, NOTARIZED AND RETURNED | | | TO THIS OFFICE, REVIEWED AND APPROVED PRIOR TO PERMIT | | | ISSUANCE. CONTACT KEN CONRAD, MANAGER OF THE SPECIAL | | | INSPECTOR PROGRAM, AT 561-805-6666 FOR ADDITIONAL | | | INFORMATION. | | | FORMS WERE SENT TO: [email protected] ON 10/18/16. | | | | | | **RESIDENT INSPECTOR FORMS REQUIRED IF BUILDING IS NOT | | | THRESHOLD. | | | | | | C. SPECIAL INSPECTOR OR RESIDENT INSPECTOR RESUME': | | | PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS | | | PROJECTS FOR REVIEW BY THE BUILDING OFFICIAL OR HIS | | | DESIGNEE. AFTER THE RESUME' IS REVIEWED, AN INTERVIEW | | | WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES WILL AN | | | INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST MEETING | | | THE ABOVE CRITERIA. THE RESUME' IS TO BE SUBMITTED TO | | | KEN CONRAD (AND COPY SAMANTHA HILL), 561-805-6666, | | | [email protected], [email protected] | | | | | | ALL PROSPECTIVE INSPECTORS ARE TO BE APPROVED BY THE | | | CHIEF BUILDING INSPECTOR AND ALL ARE REQUIRED TO SIGN | | | THE SPECIAL INSPECTOR AGREEMENT OR RESIDENT INSPECTOR | | | AGREEMENT AS APPLICABLE. | | | | | | D. CONTRACTOR RESUME': PROVIDE A JOB SUMMARY OR HISTORY | | | FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO | | | KEN CONRAD, (PLEASE COPY SAMANTHA HILL) VIA E-MAIL | | | ([email protected], [email protected]). | | | | | | E. PERMIT DOCUMENTS: PAPER SUBMITTALS REQUIRE THREE | | | SIGNED AND SEALED (IF APPLICABLE) ORIGINAL SETS OF ALL | | | DOCUMENTS. | | | | | | F. FS553.79(7)(D)ALL PLANS FOR THE BUILDING WHICH ARE | | | REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR | | | ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE | | | BEST OF THE ARCHITECT?S OR ENGINEER?S KNOWLEDGE, THE | | | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE | | | MINIMUM BUILDING CODES AND THE APPLICABLE FIRESAFETY | | | STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN | | | ACCORDANCE WITH THIS CHAPTER AND CHAPTER 633. | | | (THRESHOLD BUILDING ONLY) | | | | | | 3. ADVISORY ONLY; PER FS 553.79, ALL SHORING/RE-SHORE | | | ENGINEERING IS TO BE REVIEWED BY ENGINEER OF RECORD | | | AND THREE SIGNED AND SEALED ORIGINAL SETS ARE TO BE | | | SUBMITTED FOR PLAN REVIEW. THE SHORING/RESHORE | | | ENGINEERING IS TO BE REVIEWED AND APPROVED PRIOR TO | | | INSPECTION. THE CITY APPROVED (CITY STAMPED) | | | SHORING/RE-SHORE ENGINEERING IS TO BE AVAILABLE ON THE | | | JOB AT THE TIME OF INSPECTION. | | | | | | 4. ADVISORY ONLY; PRIOR TO INSTALLATION, A GUARD RAIL | | | DETAIL IS TO BE SUBMITTED FOR PLAN REVIEW. THIS SHOULD | | | BE SUBMITTED WITH THE SHORING/RESHORE ENGINEERING. THIS | | | MAY BE PROVIDED IN THE FIELD SUBJECT TO THE INSPECTOR'S | | | DISCRETION. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2017-01-27 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2017-01-27 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2017-01-27 |
Time |
14:46 |
Sent To |
|
|
| Notes |
| 2017-01-27 14:46:27 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 01.27.2017 | | | PERMIT NO.: 16090832 | | | ADDRESS: 4217 UP THE GROVE LANE | | | CONTRACTOR/CONTACT: | | | TELEPHONE NO.: | | | SCOPE OF REVIEW: NEW FPL COMMAND CENTER. | | | ___________________________________________ | | | | | | REVIEW STATUS: PASSED WITH PROVISOS | | | ___________________________________________ | | | | | | THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING | | | PROVISOS: | | | | | | 1. THE LANDSCAPE ISLAND ALONG THE SOUTH SIDE OF THE | | | PARKING LOT, CONTAINING THE WATER TANK PUMP ENCLOSURE | | | SHALL BE MODIFIED TO PROVIDE THE REQUIRED SHADE TREE. | | | ALL PERMITS/APPROVALS SHALL BE AMENDED TO REFLECT ANY | | | MODIFICATIONS NECESSARY TO ACCOMMODATE SUCH | | | REQUIREMENT. | | | | | | 2. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY | | | (CO) ALL INVASIVE EXOTIC SPECIES SHALL BE REMOVED FROM | | | THE ENTIRE SITE (AS REQUIRED BY RESOLUTION NO 231-16). | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2016-12-15 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2016-12-15 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2016-12-15 |
Time |
15:06 |
Sent To |
|
|
| Notes |
| 2016-12-15 15:08:26 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 12.15.2016 | | | PERMIT NO.: 16090832 | | | ADDRESS: 4217 UP THE GROVE LANE | | | CONTRACTOR/CONTACT: JON ROSENTHAL | | | TELEPHONE NO.: 561.694.4274 | | | SCOPE OF REVIEW: COMMAND CENTER EXPANSION | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. ALL PLANS SHALL MATCH THOSE APPROVED BY THE | | | DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION ON | | | OCTOBER 31, 2016, AS PART OF PLANNING BOARD CASE NO. | | | 1702A (MINOR DSI AMENDMENT). ADDITIONALLY, THERE ARE | | | INCONSISTENCIES BETWEEN THE CIVIL, SITE, AND LANDSCAPE | | | PLANS...SPECIFICALLY WITH REGARD TO THE SIZE AND | | | LOCATION OF THE LANDSCAPE ISLANDS IN THE PARKING ROW | | | ADJACENT TO UP THE GROVE LANE. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2016-10-28 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2016-10-28 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2016-10-28 |
Time |
10:36 |
Sent To |
|
|
| Notes |
| 2016-10-28 10:52:52 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 10.28.2016 | | | PERMIT NO.: 16090832 | | | ADDRESS: 4217 UP THE GROVE LANE | | | CONTRACTOR/CONTACT: JON ROSENTHAL | | | TELEPHONE NO.: 561.694.4274 | | | SCOPE OF REVIEW: COMMAND CENTER EXPANSION | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. ALL PLANS SHALL MATCH THOSE SUBMITTED TO THE | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION ON | | | OCTOBER 18, 2016, AS PART OF PLANNING BOARD CASE NO. | | | 1702A (MINOR DSI AMENDMENT). | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |