Plan Review Details - Permit 16090809
Plan Review Stops For Permit 16090809
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-06-06 Cont ID  
Sent By jwitmer Date 2017-06-06 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2017-06-06 Time 06:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-03-22 Cont ID  
Sent By jwitmer Date 2017-03-22 Time 09:31 Rev Time 0.00
Received By jwitmer Date 2017-03-22 Time 08:51 Sent To  
Notes
2017-03-22 09:32:03BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16090809
 ADD: 2201 45TH ST.
 CONT: KNIGHT ELECTRIC CO.
 TEL: 561-689-3500
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. MARCH 22/ 2017
 ACTION: DENIED
  
 1) COMPLIED. SHEET D304 NOTE # 3 MIAMI-DADE NOA
 16-0330.11.
  
 2) SEMI- COMPLIED. PLEASE NOTE IT IS ASSUMED THERE WERE
 2 BINDERS SUBMITTED FOR REVIEW WITH WRITTEN RESPONSE
 COMMENT, PRODUCT APPROVALS, GENERATOR SPECS AND
 ADDITIONAL INFORMATION. TO DATE ONLY 1 BINDER HAS BEEN
 LOCATED. FOR THE NEXT REVIEW (2) BINDERS WILL BE
 REQUIRED FOR REVIEW. 2014 FLORIDA BUILDING CODE W 2014
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.1 SUBMITTAL
 DOCUMENTS CONSISTING OF CONSTRUCTION DOCUMENTS,
 STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH
 PERMIT APPLICATION.
  
 1ST REVIEW COMMENTS. PLEASE PROVIDE COMPLIANCE WITH
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION / 2014 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. HIGHLIGHT PRESSURES FOR USE
 WITH PANIC HARDWARE!!!!!
 (C) PANEL WALLS: WALL LOUVERS (NEW COMMENT)
  
 LOUVERS: NOA 16-0209.03 & NOA 16-0519.10 NO TECHNICAL
 SHEETS WERE SUBMITTED IN THIS REVIEW.
  
 3) SEMI-COMPLIED. FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 4) COMPLIED. (NEED 2ND COPY OF BINDERS). WIND DESIGN
 CRITERIA.
  
 5) SEMI- COMPLIED NEED THE 2ND BINDER. SHEET D304 NOTE
 # 2 INDICATES THIS DOOR IS A NEW OUT SWING DOOR AND
 FRAME, IT APPEARS TO BE AN EXTERIOR DOOR. PLEASE
 PROVIDE COMPLIANCE WITH 2014 FLORIDA BUILDING CODE W
 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION / 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (31)(A) EXTERIOR DOORS. HIGHLIGHT PRESSURES
 FOR USE WITH PANIC HARDWARE!!!!!
  
 6) 2ND REQUEST, NO RESPONSE COMMENTS. NOTICE ONLY,
 SHEET D321 SHOWS THE REPLACEMENT OF AN EXISTING
 GENERATOR, THIS BUILDING IS LOCATED IN AN A8 FLOOD ZONE
 WITH REQUIRED BFE OF 14.0 FT. NGVD. SEPT. 12/2016 THE
 CITY?S FREEBOARD WAS CHANGED TO AN ADDITIONAL 1-0 FOOT.
 THIS BUILDING WAS BUILT IN 1975 PRE-FIRM AND IS NOT
 SUBSTANTIAL IMPROVEMENT. CURRENTLY NO ADDITIONAL
 INFORMATION IS REQUIRED.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-10-24 Cont ID  
Sent By jwitmer Date 2016-10-24 Time 11:16 Rev Time 0.00
Received By jwitmer Date 2016-10-24 Time 08:41 Sent To  
Notes
2016-10-24 11:16:20BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16090809
 ADD: 2201 45TH ST.
 CONT: KNIGHT ELECTRIC CO.
 TEL: 561-689-3500
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. OCT. 24/ 2016
 ACTION: DENIED
  
 1) SHEET D304 NOTE # 3 INDICATES THE REPLACEMENT OF
 DOOR & FRAME WITH A MIAMI-DADE NOA 16-0330.11 OR EQUAL.
 CANNOT SAY EQUAL. 2014 FLORIDA BUILDING CODE W 2014
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 2) PLEASE PROVIDE COMPLIANCE WITH 2014 FLORIDA BUILDING
 CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION / 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. HIGHLIGHT PRESSURES FOR USE
 WITH PANIC HARDWARE!!!!!
  
 3) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 4) PLEASE PROVIDE COMPLIANCE WITH WIND DESIGN, NOTE
 HOSPITALS HAVE A RISK CATEGORY IV OR A 180 VULT WIND
 DESIGN SEE TABLE 1604.5 & FIGURE 1609B. 2014 FBC-B
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 4.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 4.2. RISK CATEGORY.
  
 4.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 4.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 4.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 5) SHEET D304 NOTE # 2 INDICATES THIS DOOR IS A NEW OUT
 SWING DOOR AND FRAME, IT APPEARS TO BE AN EXTERIOR
 DOOR. PLEASE PROVIDE COMPLIANCE WITH 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION / 2014
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS: (31)(A) EXTERIOR DOORS. HIGHLIGHT
 PRESSURES FOR USE WITH PANIC HARDWARE!!!!!
  
 6) NOTICE ONLY, SHEET D321 SHOWS THE REPLACEMENT OF AN
 EXISTING GENERATOR, THIS BUILDING IS LOCATED IN AN A8
 FLOOD ZONE WITH REQUIRED BFE OF 14.0 FT. NGVD. SEPT.
 12/2016 THE CITY?S FREEBOARD WAS CHANGED TO AND
 ADDITIONAL 1-0 FOOT. THIS BUILDING WAS BUILT IN 1975
 PRE-FIRM AND IS NOT SUBSTANTIAL IMPROVEMENT. CURRENTLY
 NO ADDITIONAL INFORMATION IS REQUIRED.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2017-07-17 Cont ID  
Sent By jleahy Date 2017-07-17 Time 14:32 Rev Time 0.00
Received By jleahy Date 2017-07-13 Time 17:11 Sent To  
Notes
2017-07-17 14:34:21FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED SIGNED SEALED PLANS PRIOR TO FIRST ELECTRICAL
 INSPECTION 7/17/17
 PAGES D330, 331, 340, 341

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2017-06-20 Cont ID  
Sent By rlecky Date 2017-06-20 Time 14:49 Rev Time 0.00
Received By rlecky Date 2017-06-08 Time 10:56 Sent To  
Notes
2017-06-20 14:53:4616090809
 2201 45TH STREET
 HOSPITAL ELECTRIC UPGRADE
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 TEMPORARY FEEDERS ARE UNDERSIZED BASED ON THE PROPOSED
 SIZE OF CONDUCTORS WITH OVERCURRENT PROTECTION.
 ADDITIONAL INFORMATION IS NEEDED REGARDING CONDUCTOR
 PROPERTIES, PHYSICAL PROTECTION, BUNDLING, ETC. NEC
 310.10
  
 VERIFY THAT ALL REQUIRED EGRESS DOORS FROM THE
 ELECTRICAL EQUIPMENT ROOMS SWING IN THE APPROPRIATE
 DIRECTION AND ARE THE PROPER HEIGHT AND WIDTH. NEC
 110.26
  
 THE FOLLOWING ITEMS REQUIRE SOME CLARIFICATION:
  
 HAVE THEN NOTED EXISTING PANELS BEEN INCLUDED OR
 ABANDONED WITH THE NEW PLANS? PANELS ECB, ELS, PNA,
 PNB, RMI, H1ECRDP, H1ELSA, CHLRRAD.
  
 VERIFY OR INDICATE THE CORRECT VOLTAGE FOR PANEL NPB
 AND TRANSFORMER T-PB WHICH IS FED FROM SECTION 3 OF THE
 NEW MSB.
  
 PANEL RZA1 IS LISTED TWICE AND SHOWN AT 80 AND AT
 90AMPS. IT IS SHOWN AS FED FROM BOTH CRPD2 AND LSDP2.
  
 HAS THE EXISTING ATS 4 BEEN INCLUDED OR ABANDONDED?
  
  
 ROBERT LECKY
 PLANS EXAMINER
 561-805-6654
 561-373-3701
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-03-06 Cont ID  
Sent By vperez Date 2017-03-06 Time 13:44 Rev Time 0.00
Received By vperez Date 2017-03-06 Time 13:44 Sent To  
Notes
2017-03-06 13:49:37INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. HAVE CONTACTED DESIGNER OF RECORD DUE TO ELECTRICAL
 DESIGN AS SHOWN ON PLANS. THEY WILL CONTACT US BACK TO
 MEET AND CLARIFY.
 2. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-10-13 Cont ID  
Sent By mvaldes Date 2016-10-13 Time 12:47 Rev Time 0.00
Received By mvaldes Date 2016-10-12 Time 11:51 Sent To  
Notes
2016-10-13 11:37:27JOB PERMIT NUMBER: 16090809
 JOB ADDRESS: 2201 45TH ST
 WEST PALM BEACH FLORIDA
 DATE: OCTOBER 13, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. BELOW IS A LIST OF ITEMS THAT HAVE BEEN
 NOTED.
  
 1] PROVIDE A FIRE PENETRATION DETAIL FOR FIRE WALLS,
 SMOKE BARRIERS, AND FIRE PARTITIONS. SHOW THROUGH
 PENETRATION DETAILS FOR ALL NEWLY INSTALLED RUNS.
 FBC-714
  
 2] IDENTIFY FIRE & SMOKE RATING OF ANY WALLS TO BE
 PENETRATED OR HAVE PENETRATIONS REMOVED WITHIN THE WORK
 AREAS. FBC-704
  
 3] PROVIDE FPL LINE TO LINE AVAILABLE FAULT CURRENT TO
 VERIFY AIC RATINGS AND SHORT-CIRCUIT CALCULATIONS OF
 THE PROPOSED ELECTRICAL SYSTEM. NEC 110.9, 110.10, &
 110.24
  
 4] PROVIDE DOCUMENTATION OF SELECTIVE COORDINATION TIME
 CURRENT CHARACTERISTICS CHARTS OF THE SERIES
 COMBINATION. ENSURE GFP EQUIPMENT SHALL BE COORDINATED
 IN A MATTER THAT THE LOAD SIDE SHALL REMAIN PASSIVE
 DURING INTERRUPTION OF THE LINE SIDE CURRENT LIMITING
 DEVICE. NEC 240.86, 517.17
  
 5] SHOW GFP PROTECTION OF EQUIPMENT ON THE ONE-LINE
 DIAGRAMS FOR EACH DISCONNECT RATED 1000 AMPERES OR MORE
 ON WYE SYSTEMS OF MORE THAN 150 VOLTS TO GROUND. NEC
 215.9,230.95, & 240.13
  
 6] ADD NOTES FOR DEDICATED EQUIPMENT SPACE EXTENDING
 FROM THE FLOOR TO 6' ABOVE THE EQUIPMENT OR STRUCTURE
 CEILINGS. NO FOREIGN SYSTEM PIPING ALLOWED IN THIS
 ZONE. NEC 110.26(E)(1)
  
 7] ADD NOTES FOR ELECT ROOMS WITH EQUIPMENT RATED OVER
 1200 AMPERES ENTRANCE & EGRESS DOORS SHALL BE MINIMUM
 24'' WIDE 6'6'' HIGH WITH PANIC HARDWARE DEVICES.
 DEMOLITIONS OF WALLS IN ORDER TO INSTALL EQUIPMENT WILL
 REQUIRE A BUILDING PERMIT. NEC 110.26(C)(2)(3
  
 8] NEC 110.16 ARC-FLASH HAZARD WARNING: ELECTRICAL
 EQUIPMENT IN OTHER THAN DWELLING UNITS LIKELY TO
 REQUIRE SERVICED WHILE ENERGIZED SHALL BE FIELD MARKED
 TO WARN AGAINST POTENTIAL ARC-FAULT HAZARDS.
  
 9] SHOW COMPLIANCE WITH NEC 110.22 A NOTE WILL
 SUFFICE.TESTED OR ENGINEERED SERIES COMBINATION SYSTEMS
 SHALL BE LEGIBLY MARKED IN THE FIELD TO INDICATE THE
 EQUIPMENT HAS BEEN APPLIED WITH SERIES COMBO RATING.
 THE IDENTIFICATION SHOULD BE READILY ACCESSIBLE AND
 SUITABLE FOR THE ENVIRONMENT INVOLVED.
  
 10] SINCE MULTIPLE SERVICES ARE INVOLVED FOR SPECIAL
 CONDITIONS AND CAPACITY REQUIREMENTS APPLY A PERMANENT
 PLAQUE WITH A DIRECTORY DENOTING ALL OTHER SERVICE
 DISCONNECTS SUPPLYING THE BUILDING. NEC 230.2(E)
  
 11] CLARIFY WHY GENERATOR ROOM DOESN'T HAVE A FIRE
 SUPPRESSION SYSTEM PER NEC 700.12 (GENERAL
 REQUIREMENTS)
  
 12] FEEDER 400N CANNOT EXCEED 2 % VOLTAGE DROP IN
 ACCORDANCE WITH FBC-E SEC C405.7.3
  
 13] NEW T-GEN HAS WRONG SIZE PRIMARY CONDUCTORS FOR THE
 TRANSFORMER, # 8 AWG CONDUCTOR IS ONLY GOOD FOR 50 AMP
 PLEASE CORRECT ACCORDINGLY.
  
 14] TAPS FROM COPPER TO ALUMINUM SHALL USE PROPERLY
 IDENTIFIED SPLICING CONNECTION RATED FOR DISSIMILAR
 METALS. ALL TERMINAL LUGS SHALL BE TIGHTENED TO LISTED
 TORQUE AND MARKED VISIBLY TO THE FIELD INSPECTOR. NEC
 110.14
  
 15] SHOW TEMPORARY GUTTER SIZE TO COMPLY WITH NEC
 366,376,378 AND ALL TEMP CABLE WITH FINE STRANDED
 CONDUCTORS SHALL BE TERMINATED PROPERLY AND APPROVED BY
 INSPECTOR PER NEC 110.14
  
 16] PRIOR TO THE COMMENCEMENT OF ANY WORK ITS HIGHLY
 RECOMMENDED TO CONTRACTOR TO REQUEST A MEETING WITH ALL
 PARTIES INVOLVED AND THE BUILDING DEPARTMENT TO DISCUSS
 CONSTRUCTION PHASING.
  
 17] FIRE PUMPS SHALL BE SUBMITTED UNDER A SEPARATE
 PERMIT IF BEING WORKED ON.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS.WHEN RESUBMITTING, FOR A QUICKER RETURN
 ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. IF
 YOU HAVE FURTHER QUESTIONS, PLEASE DON'T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-06-01 Cont ID  
Sent By pleduc Date 2017-06-01 Time   Rev Time 0.00
Received By pleduc Date 2017-05-31 Time 16:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-02-27 Cont ID  
Sent By pleduc Date 2017-02-27 Time   Rev Time 0.00
Received By pleduc Date 2017-02-24 Time 15:51 Sent To  
Notes
2017-02-27 12:35:46THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) REGARDING THE NEW DAY TANK, THERE IS INSUFFICIENT
 DETAIL INDICATED TO DETERMINE OR ENSURE COMPLIANCE OF
 THE DAY TANK WITH NFPA 30 AND OTHER APPLICABLE CODES.
  
 PLEASE COMPLETE A REVIEW AND PROVIDE AN DETAILED
 NOTE/NARRATIVE.
  
  
  
  
 2) REGARDING THE MAIN GENERATOR, THERE IS INSUFFICIENT
 DETAIL INDICATED TO DETERMINE OR ENSURE COMPLIANCE OF
 ANY PROPOSED ACESSORY FULE TANK WITH NFPA 30 AND OTHER
 APPLICABLE CODES.
  
 PLEASE COMPLETE A REVIEW AND PROVIDE AN DETAILED
 NOTE/NARRATIVE.
  
  
  
  
 3) REGARDING THE MAIN GENERATOR LOCATION AND EXISTING
 VAULT, THERE IS INSUFFICIENT DETAIL INDICATED TO
 DETERMINE OR ENSURE COMPLIANCE WITH NFPA 110 AND OTHER
 APPLICBALE CODES.
  
 IF THIS IS AN FP&L VAULT, DOES/WILL FP&L ALLOW THE
 GENERATOR THIS CLOSE ? PLEASE PROVIDE AND APPLICABLE
 REVIEW AND DETAILED NOTE/NARRATIVE.
  
 DOES THIS INSTALLATION MEET THE REQUIREMENTS OF NFPA
 110? PLEASE PROVIDE APPLICABLE DETAIL, INCLUDING
 DIMENSIONS.
  
 DOES THE MANUFACTURES SPEC'S PROVIDE A MINIMUM
 DIMENSION TO THE NEAREST STRUCTURE?
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-10-18 Cont ID  
Sent By pleduc Date 2016-10-18 Time   Rev Time 0.00
Received By pleduc Date 2016-10-18 Time 13:37 Sent To  
Notes
2016-10-18 14:56:43THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET D100 - THERE IS AN INCORRECT YEAR REFERENCE TO
 THE FFPC 5TH EDITION, IT SHOULD INDICATE 2012.
  
 PLEASE CORRECT AND ENSURE COMPLIANCE.
  
  
  
 2) SHEET D101 - THERE IS NO INDICATIONS AND IT IS
 UNCLEAR HOW THE LIFE SAFETY FIRE ALARM SYSTEM WILL BE
 MAINTAINED THROUGHOUT THE CONSTRUCTION PERIOD.
  
 PLEASE PROVIDE A NOTE OR SHORT NARRATIVE IF AND HOW THE
 FIRE ALARM WILL BE MAINTAINED THROUGHOUT THE HOSPITAL.
  
 PER NFPA 101, CHAPTER 9 A FIRE WATCH SHALL BE
 MAINTAINED ANY TIME A SYSTEM IS DOWN FOR MORE THAN 4
 HOURS.
  
 9.6.1.6* WHERE A REQUIRED FIRE ALARM SYSTEM IS OUT OF
 SERVICE FOR MORE THAN 4 HOURS IN A 24-HOUR PERIOD, THE
 AUTHORITY HAVING JURISDICTION SHALL BE NOTIFIED, AND
 THE BUILDING SHALL BE EVACUATED, OR AN APPROVED FIRE
 WATCH SHALL BE PROVIDED FOR ALL
 PARTIES LEFT UNPROTECTED BY THE SHUTDOWN UNTIL THE FIRE
 ALARM SYSTEM HAS BEEN RETURNED TO SERVICE.
  
  
  
 3) SHEET D 301 - THERE IS AN INDICATION OF A NEW
 GENERATOR. ANY NEW GENERATOR INSTALLATION IS NOT
 APPROVED UNDER THIS PERMIT.
  
 PLEASE PROVIDE A NOTE INDICATING THAT THE NEW GENERATOR
 SHALL BE UNDER SEPARATE PERMIT.
  
  
  
 4) SHEET D304 - THERE IS FIRE ALARM WORK INDICATED IN
 THE NOTES SECTION. ANY FIRE ALARM WORK SHALL BE
 COMPLETED BY QUALIFIED LIOFE SAFETY CONTRACTORS UNDER
 SEPARATE SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE INDICATING AND ACKNOWLEDGING THE
 ABOVE.
  
  
  
 5) SHEET D 306 - THERE IS FIRE SPRINKLER WORK
 INDICATED. ANY FIRE SPRINKLER WORK SHALL BE COMPLETED
 BY QUALIFIED LIFE SAFETY CONTRACTORS UNDER SEPARATE
 SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE INDICATING AND ACKNOWLEDGING THE
 ABOVE.
  
  
  
 6) SHEET 307 - THERE IS AN INDICATION OF A NEW
 GENERATOR. ANY NEW GENERATOR INSTALLATION IS NOT
 APPROVED UNDER THIS PERMIT.
  
 PLEASE PROVIDE A NOTE INDICATING THAT THE NEW GENERATOR
 SHALL BE UNDER SEPARATE PERMIT.
  
  
  
 7) SHEET 310, D322 AND OTHER APPLICABLE GENERATOR
 EXHAUST SHEETS - THE NEW GENERATOR(S) EXHAUST APPEARS
 TO IN AN AREA OF MULTIPLE WINDOWS AND INHABITABLE
 AREAS.
  
 PLEASE PROVIDE A DETAILED REVIEW INDICATING COMPLIANCE
 WITH NFPA 110. CHAPTER 7
  
 7.10 EXHAUST SYSTEM.
 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION,
 INCLUDING PIPING, MUFFLER, AND RELATED ACCESSORIES,
 SHALL BE IN ACCORDANCE WITH NFPA37, STANDARD FOR THE
 INSTALLATION AND USE OF STATIONARY COMBUSTION ENGINES
 AND GAS TURBINES, AND OTHER APPLICABLE STANDARDS.
  
 7.10.2 EXHAUST SYSTEM INSTALLATION SHALL BE GASTIGHT TO
 PREVENT EXHAUST GAS FUMES FROM ENTERING INHABITED ROOMS
 OR BUILDINGS AND TERMINATE IN SUCH A MANNER THAT TOXIC
 FUMES CANNOT REENTER A BUILDING OR STRUCTURE,
 PARTICULARLY THROUGH WINDOWS,
 AIR VENTILATION INLETS, OR THE ENGINE AIR-INTAKE
 SYSTEM.
  
  
  
 8) PLEASE PROVIDE PLAN SHEET REVISION CLOUDS OR
 NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
  
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status F Date 2017-06-20 Cont ID  
Sent By rlecky Date 2017-06-20 Time 14:55 Rev Time 0.00
Received By rlecky Date 2017-05-24 Time 14:04 Sent To  
Notes
2017-05-25 14:05:04C34

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-03-22 Time   Rev Time 0.00
Received By lmarchan Date 2017-02-16 Time 13:16 Sent To  
Notes
2017-02-17 13:19:20C33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-24 Cont ID  
Sent By eschneid Date 2016-10-24 Time 16:55 Rev Time 0.00
Received By eschneid Date 2016-09-21 Time 10:02 Sent To  
Notes
2016-09-22 10:02:4610/13/16 - C03
 ROUTED TO ELECTRICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-05-31 Cont ID  
Sent By ccole Date 2017-05-31 Time 09:58 Rev Time 0.00
Received By ccole Date 2017-05-31 Time 07:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-02-23 Cont ID  
Sent By ccole Date 2017-02-23 Time 08:10 Rev Time 0.00
Received By ccole Date 2017-02-23 Time 08:10 Sent To  
Notes
2017-02-23 09:04:351ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16090809
 2/23/17
  
 1) DWG NO 500: IDENTIFY THE DAY TANK ON THE DRAWINGS
 AND SHOW THE VENT PIPING RUNS AND DISCHARGE LOCATIONS-
 SEE SECTION 1305.7 . PLEASE PROVIDE THE TYPES AND SIZES
 OF VENT PIPES.
  
 2) DWG NO 500: PROVIDE THE CLEARANCE DISTANCE
 MEASUREMENTS FOR THE GENERATOR COMBUSTION AND RADIATOR
 EXHAUST OUTLETS TO GRADE- SEE SECTION 501.3.1
  
 3) CLARIFY THE SCOPE OF WORK PERTAINING TO THE LARGE
 INDOOR GENERATOR FUEL TANKS. IT APPEARS FROM THE
 DRAWINGS THAT EITHER ONE OR TWO NEW TANKS ARE BEING
 INSTALLED IN THE EQUIPMENT ROOM ADJACENT TO THE
 GENERATOR ROOM. PROVIDE SPECIFICATIONS ON THE PLAN AND
 SUBMIT PRODUCT DATA SHEETS FOR THE TANKS. REVIEW
 CHAPTER 9 NFPA 30 AND SHOW COMPLIANCE WITH ALL
 APPLICABLE SECTIONS FOR INDOOR STORAGE OF FLAMMABLE AND
 COMBUSTIBLE LIQUIDS.
  
 4) THE SUBMITTED NOA'S FOR THE AIR INTAKE AND THE
 EXHAUST LOUVERS DO NOT INCLUDE THE INSTALLATION
 DRAWINGS- PLEASE PROVIDE COMPLETE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-10-13 Cont ID  
Sent By ccole Date 2016-10-13 Time 14:07 Rev Time 0.00
Received By ccole Date 2016-10-13 Time 14:07 Sent To  
Notes
2016-10-13 14:46:391ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16090809
 10/13/16
  
 1) DWG NO. D500: PROVIDE AC COOLING AND HEATING
 CALCULATIONS FOR THE NEW MINI-SPLIT SYSTEMS.
  
 2) D500: CLARIFY THE SCOPE OF WORK FOR THE GENERATOR-
 NEW OR RELOCATED? A) PROVIDE AN EQUIPMENT SCHEDULE THAT
 INDICATES THE MAKE AND MODEL OF THE GNERATOR,
 ELECTRICAL DATA, FUEL TYPE, ETC. B) PROVIDE AN ENLARGED
 DIMENSIONED DRAWING AND SCHEMATIC, WITH DETAILS AND
 NOTES IDENTIFYING THE TYPE AND SIZE OF EXHAUST VENTING,
 AND FUEL PIPING. CLARIFY HOW FUEL IS BEING STORED AND
 SUPPLIED TO THE GENERATOR AND WHAT THE TYPE OF FUEL IS-
 DIESEL, GAS, BOTH? C) REFER TO SECTION 501.3.1 AND SHOW
 ALL REQUIRED CLEARANCE DISTANCE MEASUREMENTS FOR THE
 SIDEWALL RADIATOR AND GENERATOR EXHAUST OUTLETS. D)
 SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR
 WITH SHOP DRAWING APPROVAL SIGNATURE BY THE ENGINEER OF
 RECORD.
  
 3) D500: THE WIND LOAD CALCULATIONS AND FASTENING NOTES
 FOR A ROOFTOP AC STAND DO NOT CORRELATE WITH THE
 PROPOSED GROUND MOUNTED CONDENSER INSTALLATIONS- PLEASE
 PROVIDE CORRECT THE CALCULATIONS AND NOTES.
  
 4) SUBMIT FL. PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S
 FOR THE GREENHECK AIR INTAKE LOUVER, AND THE RUSKIN
 EXHAUST LOUVER.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
2016-10-13 12:57:22PLEASE DETERMIN IF THIS NEEDS A BUILDING STOP, IF SO
 ADD AND MOVE IT ON.

Review Stop Z ZONING
Rev No 4 Status P Date 2017-08-01 Cont ID  
Sent By eschneid Date 2017-08-01 Time 15:47 Rev Time 0.50
Received By eschneid Date 2017-08-01 Time 15:27 Sent To  
Notes
2017-08-01 15:48:26REPLACEMENT SHRUBS REQUIRED - 24 INCHES TALL, 24 ON
 CENTER, RECOMMEND COCOPLUM

Review Stop Z ZONING
Rev No 3 Status F Date 2017-06-07 Cont ID  
Sent By eschneid Date 2017-06-07 Time 11:42 Rev Time 0.25
Received By eschneid Date 2017-06-07 Time 11:42 Sent To  
Notes
2017-06-07 11:42:09FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) REPEAT COMMENT: THE DEMOLITION OF THE EXISTING
 GENERATOR AND THE CONSTRUCTION OF A NEW GENERATOR PAD
 AND LOCATING A 1,000 KW GENERATOR ON THE PAD REQUIRES
 AN AMENDMENT TO THE WEST PALM HOSPITAL COMMUNITY
 SERVICE PLANNED DEVELOPMENT SITE PLAN. A MINOR PLANNED
 DEVELOPMENT APPLICATION SHALL BE FILED WITH THE
 PLANNING DIVISION AND RECEIVE APPROVAL, PRIOR TO THE
 ZONING APPROVAL OF THIS PERMIT.
  
 2) THE EXISTING SHRUBS ARE STILL REQUIRED TO BE
 RELOCATED AND MAY NOT BE REMOVED FROM THE SITE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2017-03-07 Cont ID  
Sent By eschneid Date 2017-03-07 Time 14:26 Rev Time 0.50
Received By eschneid Date 2017-03-07 Time 14:26 Sent To  
Notes
2017-03-07 14:59:32FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) REPEAT COMMENT: THE DEMOLITION OF THE EXISTING
 GENERATOR AND THE CONSTRUCTION OF A NEW GENERATOR PAD
 AND LOCATING A 1,000 KW GENERATOR ON THE PAD REQUIRES
 AN AMENDMENT TO THE WEST PALM HOSPITAL COMMUNITY
 SERVICE PLANNED DEVELOPMENT SITE PLAN. A MINOR PLANNED
 DEVELOPMENT APPLICATION SHALL BE FILED WITH THE
 PLANNING DIVISION AND RECEIVE APPROVAL, PRIOR TO THE
 ZONING APPROVAL OF THIS PERMIT.
  
 2) WHILE THE GENERATOR ITSELF IS ENCLOSED IN A HOUSING,
 THE FUELING ASSEMBLY IS EXPOSED ON THE END OF THE
 GENERATOR, WHICH REQUIRES THAT THERE BE A SCREEN WALL
 WITH HEDGES CONSTRUCTED ON THE NORTH AND WEST SIDES OF
 THE GENERATOR (THE EAST AND SOUTH ARE SCREENED BY THE
 EXISTING BUILDING WALLS). A PERMIT FOR THE SCREEN WALL
 AND HEDGES SHALL BE SUBMITTED, APPROVED AND CONSTRUCTED
 PRIOR TO THE FINAL PERMIT INSPECTION FOR THE GENERATOR.
 THE SCREENING NEEDS TO BE INCLUDED ON THE MINOR PLANNED
 DEVELOPMENT AMENDMENT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2016-10-24 Cont ID  
Sent By eschneid Date 2016-10-24 Time 14:31 Rev Time 1.00
Received By eschneid Date 2016-10-24 Time 14:30 Sent To  
Notes
2016-10-24 16:55:31FAILED
  
 1) THE DEMOLITION OF THE EXISTING GENERATOR AND THE
 CONSTRUCTION OF A NEW GENERATOR PAD AND LOCATING A
 1,000 KW GENERATOR ON THE PAD REQUIRES AN AMENDMENT TO
 THE WEST PALM HOSPITAL COMMUNITY SERVICE PLANNED
 DEVELOPMENT SITE PLAN. A MINOR PLANNED DEVELOPMENT
 APPLICATION SHALL BE FILED WITH THE PLANNING DIVISION
 AND RECEIVE APPROVAL, PRIOR TO THE ZONING APPROVAL OF
 THIS PERMIT.
  
 2) COMPARING THE PROPOSED GENERATOR PAD LAYOUT AND THE
 EXISTING SITE CONDITIONS INDICATE THAT THERE WILL BE
 SHRUBS AND POSSIBLE A TREE IMPACTED BY THE PROPOSED
 PAD. LANDSCAPE MITIGATION SHALL BE INCLUDED WITH THE
 MINOR PLANNED DEVELOPMENT AMENDMENT.
  
 3) PROVIDE THE FULL HEIGHT OF THE GENERATOR.
  
 4) PROVIDE HOW THE FULL HEIGHT OF THE GENERATOR WILL BE
 SCREENED.
  
 5) PLEASE PROVIDE DETAILS ON HOW CU-2 SHOWN ON DRAWING
 D500 WILL BE SCREENED FROM VIEW.
  
 6) PLEASE VERIFY THAT THE FOUR FOOT EIGHT INCH HEIGHT
 OF THE PROTECTIVE SCREEN WALL FOR CU-1 SHOWN ON DRAWING
 D500 WILL BE OF SUFFICIENT HEIGHT TO SCREEN THE FULL
 HEIGHT OF CU-1.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.