| 2016-09-21 06:49:59 | 1) A SEPARATE PERMIT IS REQUIRED FROM A PLUMBING |
| | CONTRACTOR FOR THE INSTALLATION OF THE WATER LINES TO |
| | THE TANKLESS WATER HEATER. F.S. 489.105. |
| | 2) THE WIND LOAD ENGINEERING FOR THE ANCHORING OF THE |
| | LP TANK IS OUTDATED. THE DOCUMENTS REFER TO THE 2010 |
| | FBC. THE CODE IN EFFECT IS THE 2014 FBC. |
| | 3) THE WIND LOAD ENGINEERING SHALL BE SIGNED AND SEALED |
| | BY THE DESIGN PROFESSIONAL OF RECORD PER THE FL. ADMIN. |
| | CODE RULE 61G15-23.002. COPIES HAVE BEEN SUBMITTED. TWO |
| | COPIES ARE REQUIRED. |
| | 4) THE SUBMITTED WIND LOAD ENGINEERING IS FOR A JOB IN |
| | VERO BEACH. SUBMIT SIGNED AND SEALED ENGINEERING FOR |
| | THE ADDRESS WHERE THE WORK IS TO BE DONE. |
| | 5) THE TANKLESS WATER HEATER SHALL BE LISTED AND |
| | LABELED PER THE 2014 FL. GAS CODE. SEC.301.3, NFPA 58 |
| | SEC. 5.20.1. |
| | 6) INDICATE ON THE SURVEY THE DISTANCE OF THE TANKLESS |
| | WATER HEATER IN RELATION TO OPERABLE DOORS AND WINDOWS |
| | OF THE STRUCTURE. THE LOCATION OF THE TANKLESS WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. 2014 FGC SEC. 303.1. |
| | 7) INDICATE ON THE GAS PLAN THAT THE PE PIPE FROM THE |
| | SECOND STAGE REGULATOR TO THE TANKLESS WATER HEATER IS |
| | UNDERGROUND. |
| | 8) INDICATE THE TYPE OF PIPE AND SIZE OF THE |
| | ABOVEGROUND GAS PIPE TO THE WATER HEATER. |
| | 9) PORTIONS OF THE SUBMITTED SHEET FOR THE REGULATORS |
| | ARE ILLEGIBLE. SUBMIT LEGIBLE COPIES. WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 10) REMOVE THE PREVIOUS PERRMIT NUMBER THAT IS STAMPED |
| | ON THE SURVEY. THIS PERMIT NUMBER IS NOT APPLICABLE TO |
| | THIS INSTALLATION. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |