Plan Review Details - Permit 16090638
Plan Review Stops For Permit 16090638
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-01-19 Cont ID  
Sent By shill Date 2017-01-19 Time 08:15 Rev Time 0.00
Received By shill Date 2017-01-19 Time 08:15 Sent To  
Notes
2017-01-19 08:20:38****PROVISOS****
 ****ISSUED AT APPLICANT'S RISK****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC 5TH EDITION, BUILDING
  
 1. FBC 503.1, FBC EXISTING BUILDING 1012.5; COMPLIANCE
 NOT CLEAR; REVISE PAGE.
 REFER TO EMAILS; MOST STRINGENT OCCUPANCY WAS NOT
 UTILIZED, INCREASE FOR 1 STORY RATHER THAN 2 STORY
 USED. OPTIONS ARE: SEPARATED USE, NON SEPARATED MIXED
 USE SHOWING COMPLIANCE FOR A3, USE FRONTAGE INCREASE,
 DIFFERENT BUILDING TYPE - IT APPEARS THAT BUILDING
 COMPLIES; A REVISION IS REQUIRED, ISSUED AT APPLICANT'S
 RISK
  
 2. FBC 1006, MEANS OF EGRESS ILLUMINATION, REAR EXIT,
 REQUIRES ILLUMINATION IN THE EXIT DISCHARGE TO THE
 PUBLIC WAY.
 ILLUMINATION NOT SHOWN BUT IS REQUIRED. SITE LIGHTING
 IS UNDER A SEPARATE PERMIT AND SHOULD INCLUDE
 PHOTOMETRICS TO SHOW COMPLIANCE. THIS MAY BE EITHER
 DEMONSTRATED VIA A REVISION, SITE LIGHTING PERMIT, OR
 FIELD VERIFIED BY THE INSPECTOR.
  
 4. FBC ACCESSIBILITY 405.6, RAMP RISE NOT TO EXCEED 30
 INCHES.
 THE DETAIL ON A 2.0.1 SHOWS A RISE OF 33". THIS ITEM
 HAS BEEN REDLINED. THE RISE LIMITATION OF 30" WILL BE
 FIELD VERIFIED BY THE INSPECTOR. IF A SIGNIFICANT
 DESIGN CHANGE IS REQUIRED, A REVISION IS REQUIRED.
  
 5. CHECK OUT AISLES, SALES AND SERVICE COUNTERS, TO
 COMPLY WITH FBC ACCESSIBILITY 904.
  
 6. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109.
  
 FLOOD / NFIP PROVISO:
  
 ABBREVIATIONS USED (SEE ALSO FBC 1612):
  
 BFE, BASE FLOOD ELEVATION
 DFE, DESIGN FLOOD ELEVATION (BFE PLUS FREEBOARD AND
 OTHER REQUIREMENTS)
 FFE, FINISHED FLOOR ELEVATION
 FIRM, FLOOD INSURANCE RATE MAP
 SFHA, SPECIAL FLOOD HAZARD AREA
  
 THIS STRUCTURE IS LOCATED IN SFHA ZONE A8, BFE 13 FEET
 NGVD29 PER FIRM. BASED ON PROJECT VALUE AND PROPERTY
 APPRAISER VALUE OF THE STRUCTURE, THIS IS CONSIDERED A
 SUBSTANTIAL IMPROVEMENT.
  
 PRIOR TO CONCRETE POUR, A FORM BOARD SURVEY WITH
 ELEVATIONS WILL BE REQUIRED. ALL IMPROVEMENTS ARE TO BE
 AT OR ABOVE DFE OR BE DESIGNED TO RESIST FLOOD LOADS,
 FBC 1612.
  
 7. PROVISO, PRIOR TO FINAL INSPECTION, THE FOLLOWING IS
 TO BE SUBMITTED:
  
 A. COMPLETED ELEVATION CERTIFICATE. ALL EQUIPMENT AND
 IMPROVEMENTS TO BE ABOVE DFE (14 FEET NGVD29).
 B. PHOTOGRAPHS OF ALL SIDES OF THE STRUCTURE
 C. PHOTOGRAPHS OF ALL MECHANICAL AND UTILITY EQUIPMENT
 LOCATED OUTSIDE THE BUILDING SHOWING ITS RELATION TO
 THE BUILDING AND GROUND AND ITS REQUIRED ANCHORING.
  
 NOTE THAT ROOFTOP EQUIPMENT IS NOT EXEMPTED FROM
 PHOTOGRAPH REQUIREMENTS.
  
 THESE REQUIREMENTS ARE FROM CRS ACTIVITY RA3 TO
 DOCUMENT COMPLIANCE WITH FBC 1612.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-12-09 Cont ID  
Sent By shill Date 2016-12-09 Time 11:43 Rev Time 0.00
Received By shill Date 2016-12-09 Time 09:34 Sent To  
Notes
2016-12-09 11:46:12****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC 5TH EDITION, BUILDING
  
 PLEASE SEE PREVIOUS PLAN REVIEW. THE RESPONSE LETTER
 ADDRESSES ONLY THE FIRST TWO, THEN THE NFIP REVIEW.
 THEREFORE, AS IT IS NOT CLEAR HOW THESE ITEMS WERE
 ADDRESSED, OR IF THEY WERE ADDRESSED, SOME OF THE SAME
 COMMENTS REMAIN:
  
 1-4. OK
  
 5. SEE IMPACT FEE REVIEW. IMPACT FEE ASSESSMENT BY PALM
 BEACH COUNTY IS REQUIRED PRIOR TO PERMIT ISSUANCE.
 PLEASE CONTACT THEM DIRECTLY TO COORDINATE.
  
 6. OK
  
 7. ALS1.1, PLAN STATES THAT THIS IS BUILDING TYPE VB
 AND IIB. BUILDING AREA HAS NOT BEEN REVIEWED AS IT IS
 NOT CLEAR WHICH ONE APPLIES TO THIS PROJECT, FBC 503.1,
 FBC EXISTING BUILDING 1012.5.
  
 8. ALS1.1, LIFE SAFETY PLAN, COMPLIANCE WITH THE
 REQUIREMENTS OF FBC CHAPTER 10 NOT CLEAR.
  
 FOR INSTANCE, LIFE SAFETY REQUIREMENTS PROVIDES AN
 OVERALL SQUARE FOOT AREA WITH ONE OCCUPANT LOAD FOR THE
 MERCANTILE AREA, BUT ALL OF THE MERCANTILE OCCUPANTS
 ARE DISTRIBUTED THROUGHOUT DIFFERENT AREAS AND DO NOT
 USE THE SAME EXITS AS THEY ARE IN DIFFERENT PORTIONS OF
 THE BUILDING.
  
 FOR INSTANCE, THREE DIFFERENT AREAS UTILIZE ONE MEANS
 OF EGRESS COMPONENT (RAMP) BUT IT IS NOT CLEAR HOW MANY
 OCCUPANTS WILL USE THIS COMPONENT.
  
 REVISE PLAN TO INCLUDE THE FOLLOWING:
  
 SQUARE FOOT AREA OF EACH SPACE
 MEANS OF EGRESS WIDTH FOR EACH COMPONENT
  
 9. PROVIDE AN OCCUPANCY CLASSIFICATION, OCCUPANT LOAD,
 SQUARE FOOT AREA FOR THE FRONT PATIO, ENTRY DECK, REAR
 PATIO, FBC 1004.
  
 10. FBC 303.4, A3 OCCUPANCY INCLUDES GYMNASIUMS, PLAN
 PROPOSES BUSINESS FOR THE SPIN AREAS. EXPLAIN RATIONALE
 OR REVISE PLAN. IF PLAN IS NOT REVISED TO A3, PLEASE
 EMAIL RATIONALE PRIOR TO RESUBMITTING.
  
 11. PROVIDE INFORMATION REGARDING THE USE OF THE FRONT
 PATIO AREA FOR SEATING, VENDING, AND EXIT DISCHARGE. IT
 IS NOT CLEAR HOW MANY OCCUPANTS WILL BE SEATED IN THIS
 AREA, HOW MANY OCCUPANTS WILL BE FORCED TO TRAVEL
 THROUGH THIS AREA AS A REQUIRED EXIT DISCHARGE. HOW
 WILL THE REQUIRED EXIT PATH BE KEPT CLEAR? NO SEATING
 PLAN WAS SHOWN, BUT MY UNDERSTANDING IS THAT THIS AREA
 WILL BE USED FOR DINING AND EVENTS. FBC 107.
  
 12. AN OCCUPANT LOAD OF 30 SF PER PERSON FOR MERCANTILE
 DOES NOT APPEAR TO BE A REASONABLE OCCUPANT LOAD
  
 13. FBC 303.1.2, IT APPEARS THAT THE FOOD AND DRINK
 VENDORS SHOULD BE CLASSIFIED AS BUSINESS OCCUPANCY OR
 A2 RATHER THAN MERCANTILE. REVISE OR PROVIDE
 CLARIFICATION.
  
 14. CLARIFY DESIGN INTENT REGARDING HARDWARE FOR EXIT
 DOORS A1.1.1. HARDWARE SET 1 IS SPECIFIED FOR THE EXIT
 DOORS AND INCLUDE A PUSH BAR. IS THE "PUSH BAR" A PANIC
 DEVICE OR FIRE EXIT HARDWARE IN COMPLIANCE WITH
 FBC1008.1.10?
  
 IT APPEARS THAT THE FOOD AND DRINK VENDING AREAS WITH
 THEIR SHARED SEATING AREA (REAR PATIO) WILL HAVE AN
 OCCUPANT LOAD WHICH EXCEEDS 50, SO PANIC BARS WOULD BE
 REQUIRED, FBC 1008.1.10 (IF ASSEMBLY OCCUPANCY). IT
 APPEARS THAT THIS IS DESIGNER?S INTENT. REVISE PLAN TO
 SPECIFY PANIC BARS FOR HARDWARE SET 1 OR CONTACT ME TO
 DISCUSS.
  
 NOTE THAT 30 SF PER PERSON FOR MERCANTILE IS FOR USES
 OF MERCANTILE TYPE SPACES; STORES WITH DISPLAYS AND ONE
 OR TWO CHECK OUT AREAS. THE SPACE PROPOSED INCLUDES
 ONLY THE CONCENTRATED CHECK OUT AREA TYPE OF SPACE, SO
 30 SF PER PERSON DOES NOT APPEAR TO BE A NUMBER
 CONSISTENT WITH THE USE.
  
 NOTE ALSO THAT, WITH PANIC DEVICES, SPACE COMPLIES WITH
 A2 OCCUPANCY FOR FBC BUILDING.
  
 15. FBC 107, MINIMUM 1/8 INCH SCALE REQUIRED, ALS1.1,
 A1.1.1.
  
 16. SHOW THE EXIT DISCHARGE FROM THE REAR STAIRS TO THE
 PUBLIC WAY, FBC 1027.
  
 17. E6 DOES NOT SHOW AN EXIT SIGN AT THE REAR EXIT, FBC
 1011.1.
  
 18. ALS1.1, BUILDING DIAGONAL TO SHOW THAT TWO REQUIRED
 EXITS ARE REMOTELY LOCATED SHOULD MEASURE SPACE WHICH
 IS SERVED BY THE TWO EXITS. THE DIAGONAL INCLUDES A
 LARGE SPACE WHICH HAS A SEPARATE EXIT. THE DIMENSION
 BETWEEN THE TWO EXITS SHOULD MEASURE THE TWO EXITS
 WHICH SERVE THE SPACE REQUIRING TWO EXITS, FBC
 1015.2.1. THE DIMENSION SHOWN MEASURES TWO EXITS
 SERVING TWO DIFFERENT PORTIONS OF THE BUILDING.
  
 19. REVISE PLAN TO SHOW COMPLIANCE WITH FBC 1006, MEANS
 OF EGRESS ILLUMINATION, REAR EXIT AND, IF APPLICABLE,
 THE SECOND EXIT FOR ROOM 134. E6.0, PHM1, DO NOT SHOW
 ANY LIGHTING FOR THE REAR EXIT AND EXIT DISCHARGE TO
 THE PUBLIC WAY.
  
 20. REQUIRED FIRE RATED WALLS ARE NOT SHOWN. AT LEAST
 TWO SIDES OF THE BUILDING LIKELY HAVE FIRE RATING
 REQUIREMENTS AS THEY SIT IN CLOSE PROXIMITY TO THE
 PROPERTY LINE. REVISE PLAN TO SHOW ALL FIRE RATED
 WALLS, FBC TABLE 705.8, FBC EXISTING BUILDING 1012.6.
  
 21. FBC ACCESSIBILITY 207.1, REVISE PLAN TO INDICATE
 WHICH METHOD OF COMPLIANCE IS ELECTED.
  
 22. THE APPLICATION SUBMITTED IS FOR 1401 CLARE AVENUE,
 BUT THE PARCEL ID AND SITE ARE CONSISTENT WITH 1301
 CLARE AVENUE PER PROPERTY APPRAISER. REVISE PLAN AND
 APPLICATION OR CLARIFY. IF APPLICANT WOULD LIKE THE
 ADDRESS CHANGED TO 1401 CLARE AVENUE, PLEASE ADVISE. AT
 THIS TIME IT APPEARS THAT THE LEGAL ADDRESS FOR THIS
 PARCEL IS 1301 CLARE AVENUE.
  
 23. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL, FBC 107. THE PRODUCT
 APPROVALS SUBMITTED WERE REVIEWED BY SOMEONE OTHER THAN
 ARCHITECT OF RECORD. PER BUILDING OFFICIAL, A DESIGN
 PROFESSIONAL OTHER THAN THE ARCHITECT OF RECORD BUT
 FROM THE SAME OFFICE MAY REVIEW ON BEHALF OF THE
 ARCHITECT OF RECORD. THAT LICENSED INDIVIDUAL IS TO
 INCLUDE THEIR FULL NAME AND LICENSE NUMBER ON THE
 REVIEW STAMP.
  
 THE 3100 RESISTOR STOREFRONT IS REFERENCED ON SHEET
 A1.1.1, BUT I WAS UNABLE TO LOCATE A REFERENCE TO THE
 DOOR. EITHER HAVE ARCHITECT SIGN THE SHOP DRAWING
 REVIEW STAMP FOR THE DOOR, OR INCORPORATE A REFERENCE
 IN THE PLAN. FYI, IF ARCHITECT?S REVIEW IS DONE VIA A
 REFERENCE IN THE PLAN, A CHANGE OF PRODUCT WOULD
 REQUIRE A REVISION TO THE PLAN AS WELL AS A NEW PRODUCT
 APPROVAL TO BE SUBMITTED.
  
 24. PROVIDE A DETAIL FOR THE RAMP WHICH SHOWS
 COMPLIANCE WITH FBC ACCESSIBILITY 405.7, LANDINGS AT
 THE TOP AND BOTTOM OF THE RAMP.
  
 25. PROVIDE A DETAIL FOR THE RAMP WHICH SHOWS
 COMPLIANCE WITH FBC ACCESSIBILITY 405.6, RAMP RISE NOT
 TO EXCEED 30 INCHES. A SECTION IS SUGGESTED.
  
 26. A2.01, DETAIL A, SHOWS A RAIN LEADER AND HOSE BIBB
 AT THE BOTTOM OF THE RAMP. EITHER REVISE TO A DIFFERENT
 LOCATION OR PROVIDE A DETAIL TO SHOW HOW THIS WILL NOT
 AFFECT THE WALKING SURFACE STABILITY FBC ACCESSIBILITY
 302.1 AND HOW THIS WILL NOT PROTRUDE INTO THE MEANS OF
 EGRESS.
  
 27. A2.02, COUNTERTOP HEIGHT NOT CLEAR. DETAIL A SHOWS
 A DIMENSION OF 2 FT FOR COUNTER BAR TOP, BUT THE NOTE
 SPECS 42 INCHES.
  
 REVISE PLAN TO SHOW SEATING AREAS AND SHOW COMPLIANCE
 WITH FBC ACCESSIBILITY 902.
  
 28. FBC ACCESSIBILITY, REVISE PLAN TO SHOW LOCATION OF
 CHECK OUT AISLES, SALES AND SERVICE COUNTERS, FBC
 ACCESSIBILITY 904.
 . A2.02 DETAIL 5 DEPICTS A WALL WITH WINDOWS AND DOORS,
 CLARIFY LOCATION.
  
 29. PROVIDE A DETAIL FOR THE MEANS OF EGRESS STAIR FROM
 THE FRONT PATIO TO REAR OF BUILDING, FBC 107. S2.0
 APPEARS TO SHOW THIS AS EXISTING, A1.1.1 SPECS STEEL
 STAIRS.
  
 30. WHEN A CONTRACTOR IS ASSIGNED, PROVIDE A COPY OF
 THE CONTRACT FOR THIS JOB, FBC 109. THE VALUE ON THE
 PERMIT APPLICATION IS TO INCLUDE LABOR, MATERIALS,
 OVERHEAD, PROFIT, EVEN IF PROVIDED BY OTHERS.
  
 THIS ITEM SHOULD NOT DELAY RESUBMITTAL (MAY BE DEALT
 WITH AT A LATER DATE, PRIOR TO ISSUANCE).
  
 NEW COMMENT:
  
 ANY COMMENTS MADE BY OTHER TRADES WHICH ARE ALSO
 REQUIRED BY THE FBC B ARE APPLICABLE FOR BUILDING
 REVIEW (ROOF EQUIPMENT GUARDRAIL AND ACCESS, FIRE
 SPRINKLERS, PLUMBING COMMENTS REGARDING ACCESSIBLITY,
 ZONING COMMENT RE LOADING ZONE).
  
 REGARDING THE LOADING ZONE, WHEN ADDRESSING ZONING'S
 COMMENT, PLEASE CLARIFY WHETHER THIS IS A PASSENGER
 LOADING ZONE (AND SUBJECT TO ACCESSIBILITY).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-10-26 Cont ID  
Sent By shill Date 2016-10-26 Time 08:59 Rev Time 0.00
Received By shill Date 2016-10-26 Time 08:49 Sent To  
Notes
2016-10-26 08:59:42****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC 5TH EDITION, BUILDING
  
 1. THIS APPEARS TO BE A CHANGE OF OCCUPANCY IN ADDITION
 TO A LEVEL II ALTERATION. SHEET ALS1.1, REVISE
 CLASSIFICATION OF WORK AND REVISE PLAN TO SHOW
 COMPLIANCE WITH FBC 5TH EDITION EXISTING BUILDING
 CHAPTER 10 (ALL SECTIONS).
  
 2. FBC EXISTING BUILDING 505, THIS APPEARS TO BE A
 LEVEL THREE ALTERATION AS THE ENTIRE SPACE IS BEING
 RECONFIGURED, REVISE PLAN.
  
 3. SEE FBC CHAPTER 2, DEFINITION OF COVERED MALL. IT
 APPEARS THAT THIS BUILDING MAY FALL UNDER THIS
 CLASSIFICATION. SEE ALSO FBC 402.1 EXCEPTION 2. REVISE
 PLAN ACCORDINGLY, OR CONTACT ME TO DISCUSS.
  
 4. SEE NFIP REVIEW. THIS PERMIT WILL BE ISSUED WITH
 PROVISOS FOR THE DOCUMENTS REQUIRED PRIOR TO CONCRETE
 POUR AND PRIOR TO FINAL INSPECTION.
  
 5. SEE IMPACT FEE REVIEW. IMPACT FEE ASSESSMENT BY PALM
 BEACH COUNTY IS REQUIRED PRIOR TO PERMIT ISSUANCE.
 PLEASE CONTACT THEM DIRECTLY TO COORDINATE.
  
 6. SHEET M5.0, A1.1.1 SHOW THE SECOND FLOOR AS STORAGE.
 ALS1.1 PROPOSES MERCANTILE FOR THE SECOND FLOOR. FBC
 107, CHAPTER 3, PROVIDE PROPOSED OCCUPANCY
 CLASSIFICATION, TO BE THE SAME ON ALL SHEETS.
  
 IF THIS IS DESIGNATED AS STORAGE, PROVIDE INFORMATION
 REGARDING THE USE OF THE STORAGE AREA. THE PERMIT WILL
 BE ISSUED WITH PROVISO THAT THIS AREA CANNOT BE USED
 FOR BUSINESS OR MERCANTILE WITHOUT A PERMIT TO APPLY
 FOR A CHANGE OF OCCUPANCY.
  
 IF THIS IS MERCANTILE, COMPLIANCE WITH ACCESSIBLE ROUTE
 SHOULD BE SHOWN ON THE PLAN.
  
 7. ALS1.1, PLAN STATES THAT THIS IS BUILDING TYPE VB
 AND IIB. BUILDING AREA HAS NOT BEEN REVIEWED AS IT IS
 NOT CLEAR WHICH ONE APPLIES TO THIS PROJECT, FBC 503.1,
 FBC EXISTING BUILDING 1012.5.
  
 8. ALS1.1, LIFE SAFETY PLAN, COMPLIANCE WITH THE
 REQUIREMENTS OF FBC CHAPTER 10 NOT CLEAR.
  
 FOR INSTANCE, LIFE SAFETY REQUIREMENTS PROVIDES AN
 OVERALL SQUARE FOOT AREA WITH ONE OCCUPANT LOAD FOR THE
 MERCANTILE AREA, BUT ALL OF THE MERCANTILE OCCUPANTS
 ARE DISTRIBUTED THROUGHOUT DIFFERENT AREAS AND DO NOT
 USE THE SAME EXITS AS THEY ARE IN DIFFERENT PORTIONS OF
 THE BUILDING.
  
 FOR INSTANCE, THREE DIFFERENT AREAS UTILIZE ONE MEANS
 OF EGRESS COMPONENT (RAMP) BUT IT IS NOT CLEAR HOW MANY
 OCCUPANTS WILL USE THIS COMPONENT.
  
 REVISE PLAN TO INCLUDE THE FOLLOWING:
  
 SQUARE FOOT AREA OF EACH SPACE
 MEANS OF EGRESS WIDTH FOR EACH COMPONENT
  
 9. PROVIDE AN OCCUPANCY CLASSIFICATION, OCCUPANT LOAD,
 SQUARE FOOT AREA FOR THE FRONT PATIO, ENTRY DECK, REAR
 PATIO, FBC 1004.
  
 10. FBC 303.4, A3 OCCUPANCY INCLUDES GYMNASIUMS, PLAN
 PROPOSES BUSINESS FOR THE SPIN AREAS. EXPLAIN RATIONALE
 OR REVISE PLAN. IF PLAN IS NOT REVISED TO A3, PLEASE
 EMAIL RATIONALE PRIOR TO RESUBMITTING.
  
 11. PROVIDE INFORMATION REGARDING THE USE OF THE FRONT
 PATIO AREA FOR SEATING, VENDING, AND EXIT DISCHARGE. IT
 IS NOT CLEAR HOW MANY OCCUPANTS WILL BE SEATED IN THIS
 AREA, HOW MANY OCCUPANTS WILL BE FORCED TO TRAVEL
 THROUGH THIS AREA AS A REQUIRED EXIT DISCHARGE. HOW
 WILL THE REQUIRED EXIT PATH BE KEPT CLEAR? NO SEATING
 PLAN WAS SHOWN, BUT MY UNDERSTANDING IS THAT THIS AREA
 WILL BE USED FOR DINING AND EVENTS. FBC 107.
  
 12. AN OCCUPANT LOAD OF 30 SF PER PERSON FOR MERCANTILE
 DOES NOT APPEAR TO BE A REASONABLE OCCUPANT LOAD
  
 13. FBC 303.1.2, IT APPEARS THAT THE FOOD AND DRINK
 VENDORS SHOULD BE CLASSIFIED AS BUSINESS OCCUPANCY OR
 A2 RATHER THAN MERCANTILE. REVISE OR PROVIDE
 CLARIFICATION.
  
 14. CLARIFY DESIGN INTENT REGARDING HARDWARE FOR EXIT
 DOORS A1.1.1. HARDWARE SET 1 IS SPECIFIED FOR THE EXIT
 DOORS AND INCLUDE A PUSH BAR. IS THE "PUSH BAR" A PANIC
 DEVICE OR FIRE EXIT HARDWARE IN COMPLIANCE WITH
 FBC1008.1.10?
  
 IT APPEARS THAT THE FOOD AND DRINK VENDING AREAS WITH
 THEIR SHARED SEATING AREA (REAR PATIO) WILL HAVE AN
 OCCUPANT LOAD WHICH EXCEEDS 50, SO PANIC BARS WOULD BE
 REQUIRED, FBC 1008.1.10. IT APPEARS THAT THIS IS
 DESIGNER?S INTENT. REVISE PLAN TO SPECIFY PANIC BARS
 FOR HARDWARE SET 1 OR CONTACT ME TO DISCUSS.
  
 NOTE THAT 30 SF PER PERSON FOR MERCANTILE IS FOR USES
 OF MERCANTILE TYPE SPACES; STORES WITH DISPLAYS AND ONE
 OR TWO CHECK OUT AREAS. THE SPACE PROPOSED INCLUDES
 ONLY THE CONCENTRATED CHECK OUT AREA TYPE OF SPACE, SO
 30 SF PER PERSON DOES NOT APPEAR TO BE A NUMBER
 CONSISTENT WITH THE USE.
  
 NOTE ALSO THAT, WITH PANIC DEVICES, SPACE COMPLIES WITH
 A2 OCCUPANCY FOR FBC BUILDING.
  
 15. FBC 107, MINIMUM 1/8 INCH SCALE REQUIRED, ALS1.1,
 A1.1.1.
  
 16. SHOW THE EXIT DISCHARGE FROM THE REAR STAIRS TO THE
 PUBLIC WAY, FBC 1027.
  
 17. E6 DOES NOT SHOW AN EXIT SIGN AT THE REAR EXIT, FBC
 1011.1.
  
 18. ALS1.1, BUILDING DIAGONAL TO SHOW THAT TWO REQUIRED
 EXITS ARE REMOTELY LOCATED SHOULD MEASURE SPACE WHICH
 IS SERVED BY THE TWO EXITS. THE DIAGONAL INCLUDES A
 LARGE SPACE WHICH HAS A SEPARATE EXIT. THE DIMENSION
 BETWEEN THE TWO EXITS SHOULD MEASURE THE TWO EXITS
 WHICH SERVE THE SPACE REQUIRING TWO EXITS, FBC
 1015.2.1. THE DIMENSION SHOWN MEASURES TWO EXITS
 SERVING TWO DIFFERENT PORTIONS OF THE BUILDING.
  
 19. REVISE PLAN TO SHOW COMPLIANCE WITH FBC 1006, MEANS
 OF EGRESS ILLUMINATION, REAR EXIT AND, IF APPLICABLE,
 THE SECOND EXIT FOR ROOM 134. E6.0, PHM1, DO NOT SHOW
 ANY LIGHTING FOR THE REAR EXIT AND EXIT DISCHARGE TO
 THE PUBLIC WAY.
  
 20. REQUIRED FIRE RATED WALLS ARE NOT SHOWN. AT LEAST
 TWO SIDES OF THE BUILDING LIKELY HAVE FIRE RATING
 REQUIREMENTS AS THEY SIT IN CLOSE PROXIMITY TO THE
 PROPERTY LINE. REVISE PLAN TO SHOW ALL FIRE RATED
 WALLS, FBC TABLE 705.8, FBC EXISTING BUILDING 1012.6.
  
 21. FBC ACCESSIBILITY 207.1, REVISE PLAN TO INDICATE
 WHICH METHOD OF COMPLIANCE IS ELECTED.
  
 22. THE APPLICATION SUBMITTED IS FOR 1401 CLARE AVENUE,
 BUT THE PARCEL ID AND SITE ARE CONSISTENT WITH 1301
 CLARE AVENUE PER PROPERTY APPRAISER. REVISE PLAN AND
 APPLICATION OR CLARIFY. IF APPLICANT WOULD LIKE THE
 ADDRESS CHANGED TO 1401 CLARE AVENUE, PLEASE ADVISE. AT
 THIS TIME IT APPEARS THAT THE LEGAL ADDRESS FOR THIS
 PARCEL IS 1301 CLARE AVENUE.
  
 23. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL, FBC 107. THE PRODUCT
 APPROVALS SUBMITTED WERE REVIEWED BY SOMEONE OTHER THAN
 ARCHITECT OF RECORD. PER BUILDING OFFICIAL, A DESIGN
 PROFESSIONAL OTHER THAN THE ARCHITECT OF RECORD BUT
 FROM THE SAME OFFICE MAY REVIEW ON BEHALF OF THE
 ARCHITECT OF RECORD. THAT LICENSED INDIVIDUAL IS TO
 INCLUDE THEIR FULL NAME AND LICENSE NUMBER ON THE
 REVIEW STAMP.
  
 THE 3100 RESISTOR STOREFRONT IS REFERENCED ON SHEET
 A1.1.1, BUT I WAS UNABLE TO LOCATE A REFERENCE TO THE
 DOOR. EITHER HAVE ARCHITECT SIGN THE SHOP DRAWING
 REVIEW STAMP FOR THE DOOR, OR INCORPORATE A REFERENCE
 IN THE PLAN. FYI, IF ARCHITECT?S REVIEW IS DONE VIA A
 REFERENCE IN THE PLAN, A CHANGE OF PRODUCT WOULD
 REQUIRE A REVISION TO THE PLAN AS WELL AS A NEW PRODUCT
 APPROVAL TO BE SUBMITTED.
  
 24. PROVIDE A DETAIL FOR THE RAMP WHICH SHOWS
 COMPLIANCE WITH FBC ACCESSIBILITY 405.7, LANDINGS AT
 THE TOP AND BOTTOM OF THE RAMP.
  
 25. PROVIDE A DETAIL FOR THE RAMP WHICH SHOWS
 COMPLIANCE WITH FBC ACCESSIBILITY 405.6, RAMP RISE NOT
 TO EXCEED 30 INCHES. A SECTION IS SUGGESTED.
  
 26. A2.01, DETAIL A, SHOWS A RAIN LEADER AND HOSE BIBB
 AT THE BOTTOM OF THE RAMP. EITHER REVISE TO A DIFFERENT
 LOCATION OR PROVIDE A DETAIL TO SHOW HOW THIS WILL NOT
 AFFECT THE WALKING SURFACE STABILITY FBC ACCESSIBILITY
 302.1 AND HOW THIS WILL NOT PROTRUDE INTO THE MEANS OF
 EGRESS.
  
 27. A2.02, COUNTERTOP HEIGHT NOT CLEAR. DETAIL A SHOWS
 A DIMENSION OF 2 FT FOR COUNTER BAR TOP, BUT THE NOTE
 SPECS 42 INCHES.
  
 REVISE PLAN TO SHOW SEATING AREAS AND SHOW COMPLIANCE
 WITH FBC ACCESSIBILITY 902.
  
 28. FBC ACCESSIBILITY, REVISE PLAN TO SHOW LOCATION OF
 CHECK OUT AISLES, SALES AND SERVICE COUNTERS, FBC
 ACCESSIBILITY 904.
 . A2.02 DETAIL 5 DEPICTS A WALL WITH WINDOWS AND DOORS,
 CLARIFY LOCATION.
  
 29. PROVIDE A DETAIL FOR THE MEANS OF EGRESS STAIR FROM
 THE FRONT PATIO TO REAR OF BUILDING, FBC 107. S2.0
 APPEARS TO SHOW THIS AS EXISTING, A1.1.1 SPECS STEEL
 STAIRS.
  
 30. WHEN A CONTRACTOR IS ASSIGNED, PROVIDE A COPY OF
 THE CONTRACT FOR THIS JOB, FBC 109. THE VALUE ON THE
 PERMIT APPLICATION IS TO INCLUDE LABOR, MATERIALS,
 OVERHEAD, PROFIT, EVEN IF PROVIDED BY OTHERS.
  
 THIS ITEM SHOULD NOT DELAY RESUBMITTAL (MAY BE DEALT
 WITH AT A LATER DATE, PRIOR TO ISSUANCE).
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-01-14 Cont ID  
Sent By vperez Date 2017-01-14 Time 13:37 Rev Time 0.00
Received By vperez Date 2017-01-14 Time 13:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-12-13 Cont ID  
Sent By vperez Date 2016-12-13 Time 08:59 Rev Time 0.00
Received By vperez Date 2016-12-13 Time 08:59 Sent To  
Notes
2016-12-13 09:00:15ELECTRICAL COMMETS ADDRESSED, PLEASE ADDRESS FIRE
 COMMENTS FOR AN ELECTRICAL APPROVAL.
  
 VAL PEREZ
 *6717

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-10-17 Cont ID  
Sent By vperez Date 2016-10-17 Time 08:49 Rev Time 0.00
Received By vperez Date 2016-10-17 Time 08:49 Sent To  
Notes
2016-10-17 09:03:40INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL LOW
 VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA, WIRELESS
 SYSTEMS, KITCHEN HOODS, ETC. A NOTE WILL SUFFICE.
 2. SHEET E1.0- PLEASE ADD A GENERAL NOTE TO SHEET TO
 INDICATE THE REQUIREMENTS OF NEC 300.5D3 AND TABLE
 300.5 FOR MINIMUM COVER REQUIREMENTS FOR CONDUITS AND
 THE PLACEMENT OF A WARNING RIBBON FOR THE SERVICE
 LATERAL CONDUCTORS SHOWN FOR THIS PROJECT. A NOTE WILL
 SUFFICE
 3. SHEET E1.0- ADD A NOTE TO MAINTAIN ALL ELECTRICAL
 EQUIPMENT ABOVE THE BASELINE FLOOD ELEVATION PER STATE
 AND CITY REGULATORY AGENCIES.
 4. SHEET E2.0-E3.0 LABEL GFCI PROTECTED ALL 120V 20A
 RECEPTACLES WITHIN THE FOOD PREP AREAS AND WITHIN 6 FT
 OF SINKS. SEE AREAS SHOWN AS FOOD PREP, PIZZA, TACO,
 BUTCHER, BAKERY ETC. NEC 210.8B
 5. PROVIDE OR CLARIFY RECEPTACLE OUTLET REQUIRED FOR
 ALL AHU UNITS FOR SERVICEABILITY. NEC 210.63
 6. SHUNT TRIP BREAKERS NOT SHOWN ON PANEL SCHEDULE
 DESIGNATIONS FOR ALL ELECTRICAL UNDER HOOD AREAS,
 PLEASE CLARIFY. FBC 107.3.5
 7. ADDRESS ANY MECHANICAL AND FIRE REVIEW COMMENTS
 RELATED TO ELECTRICAL.
 8. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.24- AVAILABLE FAULT CURRENT- FIELD
 MARKINGS; SEE VERBIAGE IN CODE.
 9. PER FBC-EC 405.7- A MINIMUM OF 50% OF ALL
 RECEPTACLES SHALL BE AUTOMATICALLY CONTROLLED FOR
 OFFICE AREAS. SHOW COMPLIANCE.
 10. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2016-12-14 Cont ID  
Sent By mkhan Date 2016-12-14 Time 12:50 Rev Time 0.00
Received By mkhan Date 2016-12-14 Time 12:50 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-01-11 Cont ID  
Sent By wjolin Date 2017-01-06 Time 15:24 Rev Time 0.00
Received By wjolin Date 2017-01-06 Time 13:40 Sent To  
Notes
2017-01-06 14:20:501401 CLARE AVENUE
 PERMIT #16090638
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SPOKE WITH JOHN AT GS&P (01/11/17 @12:50PM) AND AGREED
 TO PASS THE PLAN SUBJECT TO THE FOLLOWING ISSUES BEING
 CORRECTED IN A FUTURE REVISION BEFORE A CO IS ISSUED:
  
 SHEET C2.1: RECOMMEND OPTION 5 BELOW FOR THE FIRE
 BACKFLOW PREVENTER:
 PER NFPA 24 SECTION 6.2.1, ALL CONNECTIONS TO PRIVATE
 FIRE SERVICE MAINS FOR FIRE PROTECTION SYSTEMS SHALL BE
 ARRANGED IN ACCORDANCE WITH ONE OF THE FOLLOWING SO
 THAT THEY CAN BE ISOLATED:
 (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH SECTION 6.4
 (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A
 BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE
 SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
 (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
 SHEET M18.0: COMMERCIAL COOKING EXHAUST : PLAN
 INDICATES GREASE DUCT EXHAUSTS MOUNTED TO WEST FACE OF
 BUILDING WALL AND DISCHARGING 10 FEET FROM THE PROPERTY
 LINE; HOWEVER, CIVIL PLAN C2.1 INDICATES THAT THE WEST
 WALL OF THE BUILDING IS VIRTUALLY LOCATED ON THE
 PROPERTY LINE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2016-12-01 Cont ID  
Sent By pleduc Date 2016-12-01 Time   Rev Time 0.00
Received By pleduc Date 2016-12-01 Time 11:40 Sent To  
Notes
2016-12-01 11:49:18THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) REPEAT OF COMMENT 6:
  
 THE PROPOSED REMODEL APPEARS TO ALTER 50 OR MORE
 AUTOMATIC FIRE SPRINKLERS.
  
 PER FL BLDG CODE 105.3..1.2(2)
  
 2. FIRE SPRINKLER DOCUMENTS FOR ANY NEW BUILDING OR
 ADDITION WHICH INCLUDES A FIRE SPRINKLER SYSTEM WHICH
 CONTAINS 50 OR MORE SPRINKLER HEADS. PERSONNEL AS
 AUTHORIZED BY CHAPTER 633 FLORIDA STATUTES, MAY DESIGN
 A FIRE SPRINKLER SYSTEM OF 49 OR FEWER HEADS AND MAY
 DESIGN THE ALTERATION OF AN EXISTING FIRE SPRINKLER
 SYSTEM IF THE ALTERATION CONSISTS OF THE RELOCATION,
 ADDITION OR DELETION OF NOT MORE THAN 49 HEADS,
 NOTWITHSTANDING THE SIZE OF THE EXISTING FIRE SPRINKLER
 SYSTEM.
  
  
 NO FIRE PROTECTION DOCUMENTS HAVE BEEN SUBMITTED. THE
 FUTURE SUBMITTAL OF SHOP DRAWINGS WILL NOT MEET THE
 REQUIREMENTS OF THE BLDG CODE OR FAC.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 THE MASTER PLAN SUBMITTAL (THIS SUBMITTAL) SHALL
 INCLUDE ALL OF THE REQUIRED ELEMENTS OF THE ABOVE NOTED
 FAC EITHER IN WRITTEN NARRATIVE OR DRAWING FORMAT,
 SIGNED AND SEALED BY THE EOC. SHOP DRAWINGS SHALL THEN
 BE PREPARED AND SUBMITTED BASED ON THE EOR CRITERIA AT
 THE APPLICBALE TIME UNDER SEPARATE PERMIT SUBMITTAL.
  
 PLEASE PROVIDE THE REQUIRED DOCUMENTATION WITH THIS
 PERMIT.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-09-21 Cont ID  
Sent By wjolin Date 2016-09-21 Time 15:12 Rev Time 0.00
Received By wjolin Date 2016-09-21 Time 13:30 Sent To  
Notes
2016-09-21 14:23:171401 CLARE AVENUE
 PERMIT #16090638
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET ALS1.1: AN EQUIPMENT LAYOUT IS NEEDED FOR THE
 EXERCISE ROOMS IN ORDER TO UTILIZE AN OCCUPANT LOAD
 FACTOR OF 50 SQ.FT. PER PERSON.
  
 SHEET ALS1.1: WITH ALL THESE FOOD PLACES LOCATED WITHIN
 A SINGLE BUILDING, WILL SEATING BE PROVIDED? HAS AN
 ASSEMBLY OCCUPANCY BEEN CONSIDERED GIVING THE BUILDING
 USE MORE FLEXIBILITY.
  
 SHEET ALS1.1: DESCRIBE THE USE OF FLIGHT #101 AND BIRD
 #121.
  
 SHEET A1.1.1: WHAT IS THE USE/FUNCTION OF PATIO #106.
  
 COMMERCIAL COOKING EXHAUST (CAPTIVEAIRE) SHEET 11 OF
 11: PLAN INDICATES GREASE DUCT EXHAUSTS MOUNTED TO WEST
 FACE OF BUILDING WALL AND DISCHARGING 10 FEET FROM THE
 PROPERTY LINE; HOWEVER, CIVIL PLAN C2.1 INDICATES THAT
 THE WEST WALL OF THE BUILDING IS VIRTUALLY LOCATED ON
 THE PROPERTY LINE.
  
 FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION
 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES
 SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE
 DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE
 SPRINKLERS. PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS
 SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER
 SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE
 TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR
 EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN
 DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT
 FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION
 SUCH AS PRE-ENGINEERED SYSTEMS. AFTER THE BUILDING
 PERMIT HAS BEEN ISSUED, THE SPRINKLER SUBCONTRACTOR CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2016-12-07 Cont ID  
Sent By gjohnson Date 2016-12-07 Time 09:36 Rev Time 0.00
Received By gjohnson Date 2016-12-06 Time 17:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-02-27 Cont ID  
Sent By shill Date 2017-02-27 Time 12:30 Rev Time 0.00
Received By shill Date 2017-02-22 Time 16:32 Sent To  
Notes
2017-02-22 16:32:18TO SHILL DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-01-19 Cont ID  
Sent By shill Date 2017-01-19 Time 11:19 Rev Time 0.00
Received By shill Date 2016-12-22 Time 14:28 Sent To  
Notes
2016-12-22 14:28:54C39

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-13 Cont ID  
Sent By vperez Date 2016-12-13 Time 09:05 Rev Time 0.00
Received By vperez Date 2016-12-13 Time 09:05 Sent To  
Notes
2016-11-16 15:45:46C39

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-27 Cont ID  
Sent By shill Date 2016-10-27 Time 09:10 Rev Time 0.00
Received By shill Date 2016-09-16 Time 10:10 Sent To  
Notes
2016-09-19 10:10:52C38

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2017-03-01 Cont ID  
Sent By shill Date 2017-03-01 Time 06:43 Rev Time 0.00
Received By shill Date 2017-03-01 Time 06:43 Sent To  
Notes
2017-03-01 06:43:42MU 2017-4432
  
 RECEIPT WAS RECEIVED VIA EMAIL AND FORWARDED TO RECORDS
 VIA EMAIL
 TWO COMPLETE SETS OF PLANS (SAME AS PLANS REVIEWED)
 WERE RETURNED TO THIS OFFICE FROM IMPACT FEES. THE
 COVER SHEETS WITH THE COUNTY IMPACT FEE STAMP WERE
 REMOVED FROM EACH SET AND PUT WITH THE PERMIT SETS.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2017-02-27 Cont ID  
Sent By shill Date 2017-02-27 Time 12:28 Rev Time 0.00
Received By shill Date 2017-02-27 Time 12:28 Sent To  
Notes
2017-02-27 12:29:21****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PRIOR TO ISSUANCE OF A BUILDING PERMIT, AN IMPACT FEE
 ASSESSMENT IS REQUIRED. THE PLANS ARE TO BE STAMPED AND
 THE RECEIPT SHOWING THAT ANY FEES DUE, WERE PAID.
  
 THE PLANS HAVE BEEN STAMPED. PROVIDE THE RECEIPT
 SHOWING THAT THE IMPACT FEES OF $89,435.37 HAVE BEEN
 PAID. THIS MAY BE DONE VIA EMAIL.
  
 MU 2017-4432
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-01-19 Cont ID  
Sent By shill Date 2017-01-19 Time 06:54 Rev Time 0.00
Received By shill Date 2017-01-19 Time 06:53 Sent To  
Notes
2017-01-19 06:54:20****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PRIOR TO ISSUANCE OF A BUILDING PERMIT, AN IMPACT FEE
 ASSESSMENT IS REQUIRED. THE PLANS ARE TO BE STAMPED AND
 THE RECEIPT SHOWING THAT ANY FEES DUE, WERE PAID.
  
 561-233-5025 FOR MORE INFORMATION
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-10-18 Cont ID  
Sent By shill Date 2016-10-18 Time 15:38 Rev Time 0.00
Received By shill Date 2016-10-18 Time 15:38 Sent To  
Notes
2016-10-18 15:39:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PRIOR TO ISSUANCE OF A BUILDING PERMIT, AN IMPACT FEE
 ASSESSMENT IS REQUIRED. THE PLANS ARE TO BE STAMPED AND
 THE RECEIPT SHOWING THAT ANY FEES DUE, WERE PAID.
  
 561-233-5025 FOR MORE INFORMATION
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-01-10 Cont ID  
Sent By ccole Date 2017-01-10 Time 09:56 Rev Time 0.00
Received By ccole Date 2017-01-09 Time 16:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-11-28 Cont ID  
Sent By ccole Date 2016-11-28 Time 12:04 Rev Time 0.00
Received By ccole Date 2016-11-28 Time 10:24 Sent To  
Notes
2016-11-28 12:14:112ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16090638
 11/28/16
  
 1) SYSTEM COMMISSIONING IS REQUIRED IN ACCORDANCE WITH
 SECTION C408 FBC-14 ENERGY CONSERVATION. SEE SECTION
 C408.2.1 AND PROVIDE A COMMISSIONING PLAN.
  
 2) M1.0: CU-1 & 2 ARE LOCATED WITHIN 10' OF THE ROOF
 EDGE. PLEASE VERIFY THAT THERE IS AN EXISTING 42" HIGH
 PARAPET WALL THERE OR PROVIDE A GUARD- SECTION 304.11.
  
 3) CLARIFY HOW ACCESS TO THE ROOFTOP MECHANICAL
 EQUIPMENT IS BEING PROVIDED. IS THERE AN EXISTING ROOF
 LADDER AND HATCH?- SECTION 306.5.
  
 4) OUTDOOR AIR INTAKES SHALL BE LOCATED A MINIMUM OF
 10' FROM STREETS, ALLEYS, PARKING LOTS OR OTHER DRIVE
 AREAS PER SECTION 401.4. PLEASE INDICATE COMPLIANCE ON
 THE PLAN.
  
 5) PLEASE NOTE THAT AN INCREASE IN OCCUPANT LOADS BASED
 ON BUILDING REVIEW COMMENTS MAY RESULT IN INCREASED
 OUTDOOR AIR SUPPLY WHICH WILL REQUIRE REVISED O/A
 CALCULATIONS AND POSSIBLY INCREASED COOLING AND HEATING
 CAPACITIES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-09-28 Cont ID  
Sent By ccole Date 2016-09-28 Time 08:38 Rev Time 0.00
Received By ccole Date 2016-09-27 Time 17:17 Sent To  
Notes
2016-09-28 09:02:161ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16090638
 9/28/16
  
 1) SEPARATE PERMITS AND PLANS ARE REQUIRED FOR KITCHEN
 EXHAUST HOODS, FIRE SUPRESSION SYSTEMS, AND WALK-IN
 COOLERS AND FREEZERS. PLEASE PLACE A NOTE ON THE PLAN
 IN BOLD LETTERS.
  
 2) PROVIDE MINIMUM VENTILATION CALCULATIONS ON THE PLAN
 PER TABLE 403.3. PROVIDE A SCHEDULE OR TABLE THAT SHOWS
 THE REQUIRED AND PROVIDED CFMS OF O/A.
  
 3) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 GAS-FIRED COOKING APPLIANCE- SECTION 304 FBC-14 FUEL
 GAS.
  
 4) PROVIDE INSTALLATION DETAILS FOR THE AHU'S.
  
 5) PROVIDE PRIMARY AND SECONDARY CONDENSATE DISPOSAL
 DETAILS FOR THE AHU'S- SECTION 307. SHOW THE PRIMARY
 PIPING RUNS AND DISCHARGE LOCATIONS.
  
 6) THE PLAN DESIGNATES ONE TENANT ROOM AS A BAKERY,
 HOWEVER NO BAKING OVENS ARE SHOWN IN THE SCHEDULES-
 PLEASE REVIEW AND VERIFY NO BAKING TO BE DONE IN THE
 ROOM.
  
 7) SHEET M2.0: TRANSFERRED AIR FROM THE FOOD PREP 104
 TO THE HALL 100 IS PROHIBITED PER SECTION 601.2. THE
 LOCATION OF THE GRILL IN THE ROOM IS ALSO NOT IN
 COMPLIANCE WITH SECTION 918.6.
  
 8) M3.0: TRANSFERRED AIR FROM THE STORAGE 119 TO THE
 CORRIDOR 120 IS PROHIBITED- SECTION 601.2.
  
 9) SOME OF THE RETURN GRILLS FOR THE AHU'S APPEAR
 UNDERSIZED FOR THE AMOUNT OF CFMS BEING RETURNED.
 PLEASE INDICATE WHAT CALULATION METHODOLOGY IS BEING
 USED FOR SIZING THE GRILLS.
  
 10) PROVIDE A MECHANICAL ROOF PLAN SHOWING ALL REQUIRED
 CLEARANCE DISTANCE MEASUREMENTS FROM AIR INTAKES TO
 EXHAUST OUTLETS, AND FROM EQUIPMENT TO ROOF EDGES.
  
 11) SUBMIT THE NOA'S LISTED ON THE PLANS FOR THE ROOF
 STANDS AND LOUVERS WITH SHOP DRAWING APPROVAL
 SIGNATURES. PLEASE HIGHLIGHT, CIRCLE, OR OTHERWISE MARK
 ALL APPLICABLE INSTALLATION DETAILS, NOTES, DESIGN
 PRESSURES, ETC. ON THE ROOF STAND NOA.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2016-12-09 Cont ID  
Sent By shill Date 2016-12-09 Time 10:54 Rev Time 0.00
Received By shill Date 2016-12-09 Time 10:54 Sent To  
Notes
2016-12-09 10:55:29****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 ABBREVIATIONS USED (SEE ALSO FBC 1612):
  
 BFE, BASE FLOOD ELEVATION
 DFE, DESIGN FLOOD ELEVATION (BFE PLUS FREEBOARD AND
 OTHER REQUIREMENTS)
 FFE, FINISHED FLOOR ELEVATION
 FIRM, FLOOD INSURANCE RATE MAP
 SFHA, SPECIAL FLOOD HAZARD AREA
  
 THIS STRUCTURE IS LOCATED IN SFHA ZONE A8, BFE 13 FEET
 NGVD29 PER FIRM. BASED ON PROJECT VALUE AND PROPERTY
 APPRAISER VALUE OF THE STRUCTURE, THIS IS CONSIDERED A
 SUBSTANTIAL IMPROVEMENT.
  
 PROPERTY APPRAISER PROPOSED 2016 VALUE FOR STRUCTURE,
 $480,558
 VALUE OF IMPROVEMENT, $1,000,000
  
 BASED ON THE SURVEY PROVIDED (MILLER SURVEYING DEC 23,
 2015) THE FINISHED FLOOR FOR THIS BUILDING IS 18.20,
 WHICH COMPLIES WITH THE MINIMUM DFE WHICH APPEARS TO BE
 14 FT NGVD29.
  
 PRIOR TO CONCRETE POUR, A FORM BOARD SURVEY WITH
 ELEVATIONS WILL BE REQUIRED. ALL IMPROVEMENTS ARE TO BE
 AT OR ABOVE DFE OR BE DESIGNED TO RESIST FLOOD LOADS,
 FBC 1612.
  
 7. PROVISO, PRIOR TO FINAL INSPECTION, THE FOLLOWING IS
 TO BE SUBMITTED:
  
 A. COMPLETED ELEVATION CERTIFICATE. ALL EQUIPMENT AND
 IMPROVEMENTS TO BE ABOVE DFE (14 FEET NGVD29).
 B. PHOTOGRAPHS OF ALL SIDES OF THE STRUCTURE
 C. PHOTOGRAPHS OF ALL MECHANICAL AND UTILITY EQUIPMENT
 LOCATED OUTSIDE THE BUILDING SHOWING ITS RELATION TO
 THE BUILDING AND GROUND AND ITS REQUIRED ANCHORING.
  
 NOTE THAT ROOFTOP EQUIPMENT IS NOT EXEMPTED FROM
 PHOTOGRAPH REQUIREMENTS.
  
 THESE REQUIREMENTS ARE FROM CRS ACTIVITY RA3 TO
 DOCUMENT COMPLIANCE WITH FBC 1612.
  
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2016-10-26 Cont ID  
Sent By shill Date 2016-10-26 Time 07:41 Rev Time 0.00
Received By shill Date 2016-10-26 Time 07:41 Sent To  
Notes
2016-10-26 08:49:00****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 ABBREVIATIONS USED (SEE ALSO FBC 1612):
  
 BFE, BASE FLOOD ELEVATION
 DFE, DESIGN FLOOD ELEVATION (BFE PLUS FREEBOARD AND
 OTHER REQUIREMENTS)
 FFE, FINISHED FLOOR ELEVATION
 FIRM, FLOOD INSURANCE RATE MAP
 SFHA, SPECIAL FLOOD HAZARD AREA
  
 THIS STRUCTURE IS LOCATED IN SFHA ZONE A8, BFE 13 FEET
 NGVD29 PER FIRM. BASED ON PROJECT VALUE AND PROPERTY
 APPRAISER VALUE OF THE STRUCTURE, THIS IS CONSIDERED A
 SUBSTANTIAL IMPROVEMENT.
  
 PROPERTY APPRAISER PROPOSED 2016 VALUE FOR STRUCTURE,
 $480,558
 VALUE OF IMPROVEMENT, $1,000,000
  
 BASED ON THE SURVEY PROVIDED (MILLER SURVEYING DEC 23,
 2015) THE FINISHED FLOOR FOR THIS BUILDING IS 18.20,
 WHICH COMPLIES WITH THE MINIMUM DFE WHICH APPEARS TO BE
 14 FT NGVD29.
  
 AS A SUBSTANTIAL IMPROVEMENT, THE FOLLOWING IS
 REQUIRED:
  
 1. REVISE PLAN TO SHOW ALL EQUIPMENT SERVICING THE
 BUILDING, EXISTING AND PROPOSED. MECHANICAL EQUIPMENT
 IS SHOWN ON OTHER PAGES (SUCH AS E4.0). INCORPORATE
 INTO PLAN WITH PROPOSED ELEVATION.
  
 2. REVISE PLAN TO INCORPORATE THE FFE.
  
 3. REVISE PLAN TO SHOW PROPOSED ELEVATION OF THE BOTTOM
 OF THE RAMP AND STAIRS.
  
 4. THE SURVEY AND CIVIL PAGES ARE REQUIRED TO BE
 SIGNED, SEALED DATED ORIGINALS FS471. THESE SHEETS ARE
 REQUIRED TO SHOW COMPLIANCE WITH FBC 1612 (AND OTHER
 CODE REQUIREMENTS).
  
 5. PROVISO, PRIOR TO CONCRETE POUR, A FORM BOARD SURVEY
 WITH ELEVATIONS WILL BE REQUIRED. ALL IMPROVEMENTS ARE
 TO BE AT OR ABOVE DFE OR BE DESIGNED TO RESIST FLOOD
 LOADS, FBC 1612.
  
 6. PROVISO, PRIOR TO FINAL INSPECTION, THE FOLLOWING IS
 TO BE SUBMITTED:
  
 A. COMPLETED ELEVATION CERTIFICATE. ALL EQUIPMENT AND
 IMPROVEMENTS TO BE ABOVE DFE (14 FEET NGVD29).
 B. PHOTOGRAPHS OF ALL SIDES OF THE STRUCTURE
 C. PHOTOGRAPHS OF ALL MECHANICAL AND UTILITY EQUIPMENT
 LOCATED OUTSIDE THE BUILDING SHOWING ITS RELATION TO
 THE BUILDING AND GROUND AND ITS REQUIRED ANCHORING.
  
 NOTE THAT ROOFTOP EQUIPMENT IS NOT EXEMPTED FROM
 PHOTOGRAPH REQUIREMENTS.
  
 THESE REQUIREMENTS ARE FROM CRS ACTIVITY RA3 TO
 DOCUMENT COMPLIANCE WITH FBC 1612.
  
 PLEASE FEEL FREE TO CONTACT ME TO DISCUSS.
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-01-19 Cont ID  
Sent By gjohnson Date 2017-01-19 Time 11:14 Rev Time 0.00
Received By gjohnson Date 2017-01-19 Time 11:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-12-07 Cont ID  
Sent By gjohnson Date 2016-12-07 Time 09:05 Rev Time 0.00
Received By gjohnson Date 2016-12-06 Time 11:48 Sent To  
Notes
2016-12-07 09:07:052ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: PREVIOUS COMMENT
  
  
 NOT COMPLIED 12. IT APPEARS THAT THE MAIN BATHROOM IS
 COMBINED BATHROOM GROUP FOR BOTH SEX. BATHROOMS SHALL
 COMPLY WITH . FBC PL 403.2 SEPARATE FACILITIES.
 WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE
 FACILITIES SHALL BE PROVIDED FOR EACH SEX.
 IF YOU INTEND TO USE EACH SEPARATE TOILET ROOM TO
 PROVIDE SEPARATE FACILITIES YOU SHALL PROVIDE A
 LAVATORY IN EACH TOILET ROOM. PER FPC PL 405.3.2
  
 1. THE 2 TOILET ROOMS THAT DO NOT HAVE LAVATORY'S IN
 THEM DO NOT COMPLY WITH FPC PL 405.3.2 THESE TOILET
 ROOMS ARE NOT REQUIRED TO MEET THE FIXTURE COUNT. IF
 YOUR REQUESTING RELIEF FROM THIS CODE SEC PLEASE
 PROVIDE SIGNED AND SEALED LETTER ADDRESSED TO ROBERT
 BROWN REFERENCING THAT THESE ARE NOT REQUIRED FIXTURES
 AND COULD BE DELETED IF THE OCCUPANCY STAYS AS A
 MERCANTILE.
  
 2. PLEASE COMPLY WITH BUILDINGS COMMENTS ON THE
 OCCUPANCY TYPE. WPB AMEND TO FBC 107.2.1
  
  
 PLEASE FEEL FREE TO CONTACT ME TO SET UP A MEETING TO
 GET THIS ISSUE RESOLVED.
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-10-19 Cont ID  
Sent By gjohnson Date 2016-10-19 Time 15:09 Rev Time 0.00
Received By gjohnson Date 2016-10-14 Time 10:20 Sent To  
Notes
2016-10-19 16:10:111ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW DEPTH OF SHOWER SHALL COMPLY WITH FBC
 ACC 608.2.2
  
 2. SHOW CLEAR FLOW SPACE FOR SHOWER SHALL COMPLY WITH
 FBC ACC 608.2.2.1
  
 3. PLEASE SHOW THE END OF THE GRAB BARS IN SHOWER 6IN.
 FROM ADJACENT WALLS PER FBC ACC 608.3.2
  
 4. PLEASE INDICATE WITCH WALL SHOWER CONTROLS WILL BE
 LOCATED AND SHOW COMPLIANCE WITH FBC ACC 608.5.2
  
 5. DOR SWING IN BATHROOMS SHALL COMPLY WITHE FBC ACC
 603.2.3 DOOR SWING.
 DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR
 CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE
 PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE.
  
 6. A SEPARATE PERMIT IS REQUIRED FOR BACK FLOW.PER WPB
 UTILITIES DEPT.
  
 7. THE DFU STATED ON BUILDING SEWER APPEARS LOW PLEASE
 PROVIDE CALCULATIONS PER FBC PL SEC 709 AND INDICATE ON
 THE PLAN THE SLOPE OF THE PIPE. SHALL COMPLY WITH FBC
 PL TABLE 710.1(1)
  
 8. THE FLOOR SINKS THAT ARE SERVING DELI OR DISPLAY
 CASES SUCH AS IN RM 107, 108 SHALL HAVE TRAP PRIMERS
 PER FBC PL 1002.4
  
 9. PLEASE PROVIDE A OCCUPANT LOAD BREAKDOWN BY AREA AND
 ROOM. PER WPB AMEND TO FBC 107.2.1
  
 10. IF YOU ARE SERVING FOOD AND DRINKS TO THE PUBLIC
 FOR CONSUMPTION ON THE PROPERTY IT SHALL BE CLASSIFIED
 AS AN A2 NOT AN M OCCUPANCY. PER FBC 303.3 ASSEMBLY
 GROUP A-2.
 ASSEMBLY USES INTENDED FOR FOOD AND/OR DRINK
 CONSUMPTION INCLUDING, BUT NOT LIMITED TO:
  
 BANQUET HALLS
  
 CASINOS (GAMING AREAS)
  
 NIGHTCLUBS
  
 RESTAURANTS, CAFETERIAS AND SIMILAR DINING FACILITIES
 (INCLUDING ASSOCIATED COMMERCIAL KITCHENS)
  
 TAVERNS AND BARS
  
 11. IS THER GOING TO BE SEATING ANYWHERE SUCH AS THE
 PATIOS OR HALL AREAS PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 12. IT APPEARS THAT THE MAIN BATHROOM IS COMBINED
 BATHROOM GROUP FOR BOTH SEX. BATHROOMS SHALL COMPLY
 WITH . FBC PL 403.2 SEPARATE FACILITIES.
 WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE
 FACILITIES SHALL BE PROVIDED FOR EACH SEX.
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2021-01-27 Cont ID  
Sent By shill Date 2021-01-27 Time 18:00 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
2021-01-27 18:01:01EVANS HUGHES INSPECTIONS
  

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2017-01-09 Time   Rev Time 0.00
Received By pgreilic Date 2017-01-09 Time 11:43 Sent To  
Notes
2017-01-09 11:46:09APPROVED WITH THE FOLLOWING SPECIFIC CONDITIONS:
  
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY
 FOR THE BUILDING AT 1401 CLARE AVE, THE FOLLOWING
 CONDITIONS SHALL BE ADDRESSED:
  
 1.) A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE
 PLAN, SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR
 REVIEW.
  
 2.) THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED
 LANDSCAPE PERMIT SHALL BE INSTALLED AND PASSA FINAL
 LANDSCAPE INSPECTION.
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2016-11-22 Time   Rev Time 0.00
Received By pgreilic Date 2016-11-22 Time 14:40 Sent To  
Notes
2016-11-22 14:41:29 
 1.) LABEL SQUARE FOOTAGE OF ALL PROPOSED USES INCLUDING
 FOOD AREAS, EXERCISE SPACE, FUTURE USES ETC.
  
 2.) LANDSCAPING ON SITE WILL NEED TO MEET REGULATIONS
 OUTLINED IN ARTICLE XIV OF THE CITY?S ZONING AND LAND
 DEVELOPMENT REGULATIONS
  
 3.) WHAT IS BEING PROPOSED FOR THE NORTHERNMOST PORTION
 OF THE SITE? PROVIDE A SITE PLAN THAT INCLUDES THE
 ENTIRE SITE. STAFF RECOMMENDS APPLICANT SUBMITS A SITE
 PLAN AND LANDSCAPE PLAN CONCURRENTLY.
  
 4.) INDICATE LOCATION AND DIMENSIONS OF LOADING ZONE
  
 5.) DIMENSION PARKING STALLS AND DRIVE AISLES
  
 6.) PROVIDE BICYCLE RACKS PER SEC. 94-485. INDICATE
 SPACING AND ORIENTATION OF INDIVIDUAL BIKE RACKS
  
 7.) PROVIDE DETAILS FOR PARKING SPACES, BIKE RACKS,
 DUMPSTER
  
  
 PAUL GREILICH
 SENIOR PLANNER
 [email protected]
 (561)-822-1443
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-09-27 Cont ID  
Sent By pg Date 2016-09-27 Time   Rev Time 0.00
Received By pgreilic Date 2016-09-23 Time 16:06 Sent To  
Notes
2016-09-27 11:07:161.) SHOW SQUARE FOOTAGE OF ALL PROPOSED USES INCLUDING
 RESTAURANTS, EXERCISE SPACE, AND FUTURE USES
  
 2.) LANDSCAPING ON SITE WILL NEED TO MEET REGULATIONS
 OUTLINED IN ARTICLE XIV OF THE CITY?S ZONING AND LAND
 DEVELOPMENT REGULATIONS
  
 3.) TERMINAL ISLANDS ARE REQUIRED AFTER 10 CONSECUTIVE
 PARKING SPACES PER SECTION 94-443
  
 4.) MITIGATION OF REMOVED TREES (4 PALMS, 1 FLOWERING
 TREE) REQUIRED
  
 5.) WHAT IS BEING PROPOSED FOR THE NORTHERNMOST PORTION
 OF THE SITE? INDICATE IF IT WILL BE PAVED, LANDSCAPED,
 ETC.
  
 6.) INDICATE LOCATION AND DIMENSIONS OF LOADING ZONE
  
 7.) DIMENSION PARKING STALLS AND DRIVE AISLES
  
 8.) PROVIDE BICYCLE RACKS PER SEC. 94-485
  
 9.) PROVIDE PEDESTRIAN ACCESS TO BUILDING AND
 SURROUNDING SIDEWALKS PER SEC. 94-172
  
 PAUL GREILICH
 SENIOR PLANNER
 [email protected]
 (561)-822-1443
  