Plan Review Details - Permit 16090638
| Plan Review Stops For Permit 16090638 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2017-01-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-01-19 |
Time |
08:15 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-01-19 |
Time |
08:15 |
Sent To |
|
|
| Notes |
| 2017-01-19 08:20:38 | ****PROVISOS**** | | | ****ISSUED AT APPLICANT'S RISK**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC 5TH EDITION, BUILDING | | | | | | 1. FBC 503.1, FBC EXISTING BUILDING 1012.5; COMPLIANCE | | | NOT CLEAR; REVISE PAGE. | | | REFER TO EMAILS; MOST STRINGENT OCCUPANCY WAS NOT | | | UTILIZED, INCREASE FOR 1 STORY RATHER THAN 2 STORY | | | USED. OPTIONS ARE: SEPARATED USE, NON SEPARATED MIXED | | | USE SHOWING COMPLIANCE FOR A3, USE FRONTAGE INCREASE, | | | DIFFERENT BUILDING TYPE - IT APPEARS THAT BUILDING | | | COMPLIES; A REVISION IS REQUIRED, ISSUED AT APPLICANT'S | | | RISK | | | | | | 2. FBC 1006, MEANS OF EGRESS ILLUMINATION, REAR EXIT, | | | REQUIRES ILLUMINATION IN THE EXIT DISCHARGE TO THE | | | PUBLIC WAY. | | | ILLUMINATION NOT SHOWN BUT IS REQUIRED. SITE LIGHTING | | | IS UNDER A SEPARATE PERMIT AND SHOULD INCLUDE | | | PHOTOMETRICS TO SHOW COMPLIANCE. THIS MAY BE EITHER | | | DEMONSTRATED VIA A REVISION, SITE LIGHTING PERMIT, OR | | | FIELD VERIFIED BY THE INSPECTOR. | | | | | | 4. FBC ACCESSIBILITY 405.6, RAMP RISE NOT TO EXCEED 30 | | | INCHES. | | | THE DETAIL ON A 2.0.1 SHOWS A RISE OF 33". THIS ITEM | | | HAS BEEN REDLINED. THE RISE LIMITATION OF 30" WILL BE | | | FIELD VERIFIED BY THE INSPECTOR. IF A SIGNIFICANT | | | DESIGN CHANGE IS REQUIRED, A REVISION IS REQUIRED. | | | | | | 5. CHECK OUT AISLES, SALES AND SERVICE COUNTERS, TO | | | COMPLY WITH FBC ACCESSIBILITY 904. | | | | | | 6. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC | | | 109. | | | | | | FLOOD / NFIP PROVISO: | | | | | | ABBREVIATIONS USED (SEE ALSO FBC 1612): | | | | | | BFE, BASE FLOOD ELEVATION | | | DFE, DESIGN FLOOD ELEVATION (BFE PLUS FREEBOARD AND | | | OTHER REQUIREMENTS) | | | FFE, FINISHED FLOOR ELEVATION | | | FIRM, FLOOD INSURANCE RATE MAP | | | SFHA, SPECIAL FLOOD HAZARD AREA | | | | | | THIS STRUCTURE IS LOCATED IN SFHA ZONE A8, BFE 13 FEET | | | NGVD29 PER FIRM. BASED ON PROJECT VALUE AND PROPERTY | | | APPRAISER VALUE OF THE STRUCTURE, THIS IS CONSIDERED A | | | SUBSTANTIAL IMPROVEMENT. | | | | | | PRIOR TO CONCRETE POUR, A FORM BOARD SURVEY WITH | | | ELEVATIONS WILL BE REQUIRED. ALL IMPROVEMENTS ARE TO BE | | | AT OR ABOVE DFE OR BE DESIGNED TO RESIST FLOOD LOADS, | | | FBC 1612. | | | | | | 7. PROVISO, PRIOR TO FINAL INSPECTION, THE FOLLOWING IS | | | TO BE SUBMITTED: | | | | | | A. COMPLETED ELEVATION CERTIFICATE. ALL EQUIPMENT AND | | | IMPROVEMENTS TO BE ABOVE DFE (14 FEET NGVD29). | | | B. PHOTOGRAPHS OF ALL SIDES OF THE STRUCTURE | | | C. PHOTOGRAPHS OF ALL MECHANICAL AND UTILITY EQUIPMENT | | | LOCATED OUTSIDE THE BUILDING SHOWING ITS RELATION TO | | | THE BUILDING AND GROUND AND ITS REQUIRED ANCHORING. | | | | | | NOTE THAT ROOFTOP EQUIPMENT IS NOT EXEMPTED FROM | | | PHOTOGRAPH REQUIREMENTS. | | | | | | THESE REQUIREMENTS ARE FROM CRS ACTIVITY RA3 TO | | | DOCUMENT COMPLIANCE WITH FBC 1612. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2016-12-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-12-09 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-12-09 |
Time |
09:34 |
Sent To |
|
|
| Notes |
| 2016-12-09 11:46:12 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC 5TH EDITION, BUILDING | | | | | | PLEASE SEE PREVIOUS PLAN REVIEW. THE RESPONSE LETTER | | | ADDRESSES ONLY THE FIRST TWO, THEN THE NFIP REVIEW. | | | THEREFORE, AS IT IS NOT CLEAR HOW THESE ITEMS WERE | | | ADDRESSED, OR IF THEY WERE ADDRESSED, SOME OF THE SAME | | | COMMENTS REMAIN: | | | | | | 1-4. OK | | | | | | 5. SEE IMPACT FEE REVIEW. IMPACT FEE ASSESSMENT BY PALM | | | BEACH COUNTY IS REQUIRED PRIOR TO PERMIT ISSUANCE. | | | PLEASE CONTACT THEM DIRECTLY TO COORDINATE. | | | | | | 6. OK | | | | | | 7. ALS1.1, PLAN STATES THAT THIS IS BUILDING TYPE VB | | | AND IIB. BUILDING AREA HAS NOT BEEN REVIEWED AS IT IS | | | NOT CLEAR WHICH ONE APPLIES TO THIS PROJECT, FBC 503.1, | | | FBC EXISTING BUILDING 1012.5. | | | | | | 8. ALS1.1, LIFE SAFETY PLAN, COMPLIANCE WITH THE | | | REQUIREMENTS OF FBC CHAPTER 10 NOT CLEAR. | | | | | | FOR INSTANCE, LIFE SAFETY REQUIREMENTS PROVIDES AN | | | OVERALL SQUARE FOOT AREA WITH ONE OCCUPANT LOAD FOR THE | | | MERCANTILE AREA, BUT ALL OF THE MERCANTILE OCCUPANTS | | | ARE DISTRIBUTED THROUGHOUT DIFFERENT AREAS AND DO NOT | | | USE THE SAME EXITS AS THEY ARE IN DIFFERENT PORTIONS OF | | | THE BUILDING. | | | | | | FOR INSTANCE, THREE DIFFERENT AREAS UTILIZE ONE MEANS | | | OF EGRESS COMPONENT (RAMP) BUT IT IS NOT CLEAR HOW MANY | | | OCCUPANTS WILL USE THIS COMPONENT. | | | | | | REVISE PLAN TO INCLUDE THE FOLLOWING: | | | | | | SQUARE FOOT AREA OF EACH SPACE | | | MEANS OF EGRESS WIDTH FOR EACH COMPONENT | | | | | | 9. PROVIDE AN OCCUPANCY CLASSIFICATION, OCCUPANT LOAD, | | | SQUARE FOOT AREA FOR THE FRONT PATIO, ENTRY DECK, REAR | | | PATIO, FBC 1004. | | | | | | 10. FBC 303.4, A3 OCCUPANCY INCLUDES GYMNASIUMS, PLAN | | | PROPOSES BUSINESS FOR THE SPIN AREAS. EXPLAIN RATIONALE | | | OR REVISE PLAN. IF PLAN IS NOT REVISED TO A3, PLEASE | | | EMAIL RATIONALE PRIOR TO RESUBMITTING. | | | | | | 11. PROVIDE INFORMATION REGARDING THE USE OF THE FRONT | | | PATIO AREA FOR SEATING, VENDING, AND EXIT DISCHARGE. IT | | | IS NOT CLEAR HOW MANY OCCUPANTS WILL BE SEATED IN THIS | | | AREA, HOW MANY OCCUPANTS WILL BE FORCED TO TRAVEL | | | THROUGH THIS AREA AS A REQUIRED EXIT DISCHARGE. HOW | | | WILL THE REQUIRED EXIT PATH BE KEPT CLEAR? NO SEATING | | | PLAN WAS SHOWN, BUT MY UNDERSTANDING IS THAT THIS AREA | | | WILL BE USED FOR DINING AND EVENTS. FBC 107. | | | | | | 12. AN OCCUPANT LOAD OF 30 SF PER PERSON FOR MERCANTILE | | | DOES NOT APPEAR TO BE A REASONABLE OCCUPANT LOAD | | | | | | 13. FBC 303.1.2, IT APPEARS THAT THE FOOD AND DRINK | | | VENDORS SHOULD BE CLASSIFIED AS BUSINESS OCCUPANCY OR | | | A2 RATHER THAN MERCANTILE. REVISE OR PROVIDE | | | CLARIFICATION. | | | | | | 14. CLARIFY DESIGN INTENT REGARDING HARDWARE FOR EXIT | | | DOORS A1.1.1. HARDWARE SET 1 IS SPECIFIED FOR THE EXIT | | | DOORS AND INCLUDE A PUSH BAR. IS THE "PUSH BAR" A PANIC | | | DEVICE OR FIRE EXIT HARDWARE IN COMPLIANCE WITH | | | FBC1008.1.10? | | | | | | IT APPEARS THAT THE FOOD AND DRINK VENDING AREAS WITH | | | THEIR SHARED SEATING AREA (REAR PATIO) WILL HAVE AN | | | OCCUPANT LOAD WHICH EXCEEDS 50, SO PANIC BARS WOULD BE | | | REQUIRED, FBC 1008.1.10 (IF ASSEMBLY OCCUPANCY). IT | | | APPEARS THAT THIS IS DESIGNER?S INTENT. REVISE PLAN TO | | | SPECIFY PANIC BARS FOR HARDWARE SET 1 OR CONTACT ME TO | | | DISCUSS. | | | | | | NOTE THAT 30 SF PER PERSON FOR MERCANTILE IS FOR USES | | | OF MERCANTILE TYPE SPACES; STORES WITH DISPLAYS AND ONE | | | OR TWO CHECK OUT AREAS. THE SPACE PROPOSED INCLUDES | | | ONLY THE CONCENTRATED CHECK OUT AREA TYPE OF SPACE, SO | | | 30 SF PER PERSON DOES NOT APPEAR TO BE A NUMBER | | | CONSISTENT WITH THE USE. | | | | | | NOTE ALSO THAT, WITH PANIC DEVICES, SPACE COMPLIES WITH | | | A2 OCCUPANCY FOR FBC BUILDING. | | | | | | 15. FBC 107, MINIMUM 1/8 INCH SCALE REQUIRED, ALS1.1, | | | A1.1.1. | | | | | | 16. SHOW THE EXIT DISCHARGE FROM THE REAR STAIRS TO THE | | | PUBLIC WAY, FBC 1027. | | | | | | 17. E6 DOES NOT SHOW AN EXIT SIGN AT THE REAR EXIT, FBC | | | 1011.1. | | | | | | 18. ALS1.1, BUILDING DIAGONAL TO SHOW THAT TWO REQUIRED | | | EXITS ARE REMOTELY LOCATED SHOULD MEASURE SPACE WHICH | | | IS SERVED BY THE TWO EXITS. THE DIAGONAL INCLUDES A | | | LARGE SPACE WHICH HAS A SEPARATE EXIT. THE DIMENSION | | | BETWEEN THE TWO EXITS SHOULD MEASURE THE TWO EXITS | | | WHICH SERVE THE SPACE REQUIRING TWO EXITS, FBC | | | 1015.2.1. THE DIMENSION SHOWN MEASURES TWO EXITS | | | SERVING TWO DIFFERENT PORTIONS OF THE BUILDING. | | | | | | 19. REVISE PLAN TO SHOW COMPLIANCE WITH FBC 1006, MEANS | | | OF EGRESS ILLUMINATION, REAR EXIT AND, IF APPLICABLE, | | | THE SECOND EXIT FOR ROOM 134. E6.0, PHM1, DO NOT SHOW | | | ANY LIGHTING FOR THE REAR EXIT AND EXIT DISCHARGE TO | | | THE PUBLIC WAY. | | | | | | 20. REQUIRED FIRE RATED WALLS ARE NOT SHOWN. AT LEAST | | | TWO SIDES OF THE BUILDING LIKELY HAVE FIRE RATING | | | REQUIREMENTS AS THEY SIT IN CLOSE PROXIMITY TO THE | | | PROPERTY LINE. REVISE PLAN TO SHOW ALL FIRE RATED | | | WALLS, FBC TABLE 705.8, FBC EXISTING BUILDING 1012.6. | | | | | | 21. FBC ACCESSIBILITY 207.1, REVISE PLAN TO INDICATE | | | WHICH METHOD OF COMPLIANCE IS ELECTED. | | | | | | 22. THE APPLICATION SUBMITTED IS FOR 1401 CLARE AVENUE, | | | BUT THE PARCEL ID AND SITE ARE CONSISTENT WITH 1301 | | | CLARE AVENUE PER PROPERTY APPRAISER. REVISE PLAN AND | | | APPLICATION OR CLARIFY. IF APPLICANT WOULD LIKE THE | | | ADDRESS CHANGED TO 1401 CLARE AVENUE, PLEASE ADVISE. AT | | | THIS TIME IT APPEARS THAT THE LEGAL ADDRESS FOR THIS | | | PARCEL IS 1301 CLARE AVENUE. | | | | | | 23. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL, FBC 107. THE PRODUCT | | | APPROVALS SUBMITTED WERE REVIEWED BY SOMEONE OTHER THAN | | | ARCHITECT OF RECORD. PER BUILDING OFFICIAL, A DESIGN | | | PROFESSIONAL OTHER THAN THE ARCHITECT OF RECORD BUT | | | FROM THE SAME OFFICE MAY REVIEW ON BEHALF OF THE | | | ARCHITECT OF RECORD. THAT LICENSED INDIVIDUAL IS TO | | | INCLUDE THEIR FULL NAME AND LICENSE NUMBER ON THE | | | REVIEW STAMP. | | | | | | THE 3100 RESISTOR STOREFRONT IS REFERENCED ON SHEET | | | A1.1.1, BUT I WAS UNABLE TO LOCATE A REFERENCE TO THE | | | DOOR. EITHER HAVE ARCHITECT SIGN THE SHOP DRAWING | | | REVIEW STAMP FOR THE DOOR, OR INCORPORATE A REFERENCE | | | IN THE PLAN. FYI, IF ARCHITECT?S REVIEW IS DONE VIA A | | | REFERENCE IN THE PLAN, A CHANGE OF PRODUCT WOULD | | | REQUIRE A REVISION TO THE PLAN AS WELL AS A NEW PRODUCT | | | APPROVAL TO BE SUBMITTED. | | | | | | 24. PROVIDE A DETAIL FOR THE RAMP WHICH SHOWS | | | COMPLIANCE WITH FBC ACCESSIBILITY 405.7, LANDINGS AT | | | THE TOP AND BOTTOM OF THE RAMP. | | | | | | 25. PROVIDE A DETAIL FOR THE RAMP WHICH SHOWS | | | COMPLIANCE WITH FBC ACCESSIBILITY 405.6, RAMP RISE NOT | | | TO EXCEED 30 INCHES. A SECTION IS SUGGESTED. | | | | | | 26. A2.01, DETAIL A, SHOWS A RAIN LEADER AND HOSE BIBB | | | AT THE BOTTOM OF THE RAMP. EITHER REVISE TO A DIFFERENT | | | LOCATION OR PROVIDE A DETAIL TO SHOW HOW THIS WILL NOT | | | AFFECT THE WALKING SURFACE STABILITY FBC ACCESSIBILITY | | | 302.1 AND HOW THIS WILL NOT PROTRUDE INTO THE MEANS OF | | | EGRESS. | | | | | | 27. A2.02, COUNTERTOP HEIGHT NOT CLEAR. DETAIL A SHOWS | | | A DIMENSION OF 2 FT FOR COUNTER BAR TOP, BUT THE NOTE | | | SPECS 42 INCHES. | | | | | | REVISE PLAN TO SHOW SEATING AREAS AND SHOW COMPLIANCE | | | WITH FBC ACCESSIBILITY 902. | | | | | | 28. FBC ACCESSIBILITY, REVISE PLAN TO SHOW LOCATION OF | | | CHECK OUT AISLES, SALES AND SERVICE COUNTERS, FBC | | | ACCESSIBILITY 904. | | | . A2.02 DETAIL 5 DEPICTS A WALL WITH WINDOWS AND DOORS, | | | CLARIFY LOCATION. | | | | | | 29. PROVIDE A DETAIL FOR THE MEANS OF EGRESS STAIR FROM | | | THE FRONT PATIO TO REAR OF BUILDING, FBC 107. S2.0 | | | APPEARS TO SHOW THIS AS EXISTING, A1.1.1 SPECS STEEL | | | STAIRS. | | | | | | 30. WHEN A CONTRACTOR IS ASSIGNED, PROVIDE A COPY OF | | | THE CONTRACT FOR THIS JOB, FBC 109. THE VALUE ON THE | | | PERMIT APPLICATION IS TO INCLUDE LABOR, MATERIALS, | | | OVERHEAD, PROFIT, EVEN IF PROVIDED BY OTHERS. | | | | | | THIS ITEM SHOULD NOT DELAY RESUBMITTAL (MAY BE DEALT | | | WITH AT A LATER DATE, PRIOR TO ISSUANCE). | | | | | | NEW COMMENT: | | | | | | ANY COMMENTS MADE BY OTHER TRADES WHICH ARE ALSO | | | REQUIRED BY THE FBC B ARE APPLICABLE FOR BUILDING | | | REVIEW (ROOF EQUIPMENT GUARDRAIL AND ACCESS, FIRE | | | SPRINKLERS, PLUMBING COMMENTS REGARDING ACCESSIBLITY, | | | ZONING COMMENT RE LOADING ZONE). | | | | | | REGARDING THE LOADING ZONE, WHEN ADDRESSING ZONING'S | | | COMMENT, PLEASE CLARIFY WHETHER THIS IS A PASSENGER | | | LOADING ZONE (AND SUBJECT TO ACCESSIBILITY). |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-10-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-10-26 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-10-26 |
Time |
08:49 |
Sent To |
|
|
| Notes |
| 2016-10-26 08:59:42 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC 5TH EDITION, BUILDING | | | | | | 1. THIS APPEARS TO BE A CHANGE OF OCCUPANCY IN ADDITION | | | TO A LEVEL II ALTERATION. SHEET ALS1.1, REVISE | | | CLASSIFICATION OF WORK AND REVISE PLAN TO SHOW | | | COMPLIANCE WITH FBC 5TH EDITION EXISTING BUILDING | | | CHAPTER 10 (ALL SECTIONS). | | | | | | 2. FBC EXISTING BUILDING 505, THIS APPEARS TO BE A | | | LEVEL THREE ALTERATION AS THE ENTIRE SPACE IS BEING | | | RECONFIGURED, REVISE PLAN. | | | | | | 3. SEE FBC CHAPTER 2, DEFINITION OF COVERED MALL. IT | | | APPEARS THAT THIS BUILDING MAY FALL UNDER THIS | | | CLASSIFICATION. SEE ALSO FBC 402.1 EXCEPTION 2. REVISE | | | PLAN ACCORDINGLY, OR CONTACT ME TO DISCUSS. | | | | | | 4. SEE NFIP REVIEW. THIS PERMIT WILL BE ISSUED WITH | | | PROVISOS FOR THE DOCUMENTS REQUIRED PRIOR TO CONCRETE | | | POUR AND PRIOR TO FINAL INSPECTION. | | | | | | 5. SEE IMPACT FEE REVIEW. IMPACT FEE ASSESSMENT BY PALM | | | BEACH COUNTY IS REQUIRED PRIOR TO PERMIT ISSUANCE. | | | PLEASE CONTACT THEM DIRECTLY TO COORDINATE. | | | | | | 6. SHEET M5.0, A1.1.1 SHOW THE SECOND FLOOR AS STORAGE. | | | ALS1.1 PROPOSES MERCANTILE FOR THE SECOND FLOOR. FBC | | | 107, CHAPTER 3, PROVIDE PROPOSED OCCUPANCY | | | CLASSIFICATION, TO BE THE SAME ON ALL SHEETS. | | | | | | IF THIS IS DESIGNATED AS STORAGE, PROVIDE INFORMATION | | | REGARDING THE USE OF THE STORAGE AREA. THE PERMIT WILL | | | BE ISSUED WITH PROVISO THAT THIS AREA CANNOT BE USED | | | FOR BUSINESS OR MERCANTILE WITHOUT A PERMIT TO APPLY | | | FOR A CHANGE OF OCCUPANCY. | | | | | | IF THIS IS MERCANTILE, COMPLIANCE WITH ACCESSIBLE ROUTE | | | SHOULD BE SHOWN ON THE PLAN. | | | | | | 7. ALS1.1, PLAN STATES THAT THIS IS BUILDING TYPE VB | | | AND IIB. BUILDING AREA HAS NOT BEEN REVIEWED AS IT IS | | | NOT CLEAR WHICH ONE APPLIES TO THIS PROJECT, FBC 503.1, | | | FBC EXISTING BUILDING 1012.5. | | | | | | 8. ALS1.1, LIFE SAFETY PLAN, COMPLIANCE WITH THE | | | REQUIREMENTS OF FBC CHAPTER 10 NOT CLEAR. | | | | | | FOR INSTANCE, LIFE SAFETY REQUIREMENTS PROVIDES AN | | | OVERALL SQUARE FOOT AREA WITH ONE OCCUPANT LOAD FOR THE | | | MERCANTILE AREA, BUT ALL OF THE MERCANTILE OCCUPANTS | | | ARE DISTRIBUTED THROUGHOUT DIFFERENT AREAS AND DO NOT | | | USE THE SAME EXITS AS THEY ARE IN DIFFERENT PORTIONS OF | | | THE BUILDING. | | | | | | FOR INSTANCE, THREE DIFFERENT AREAS UTILIZE ONE MEANS | | | OF EGRESS COMPONENT (RAMP) BUT IT IS NOT CLEAR HOW MANY | | | OCCUPANTS WILL USE THIS COMPONENT. | | | | | | REVISE PLAN TO INCLUDE THE FOLLOWING: | | | | | | SQUARE FOOT AREA OF EACH SPACE | | | MEANS OF EGRESS WIDTH FOR EACH COMPONENT | | | | | | 9. PROVIDE AN OCCUPANCY CLASSIFICATION, OCCUPANT LOAD, | | | SQUARE FOOT AREA FOR THE FRONT PATIO, ENTRY DECK, REAR | | | PATIO, FBC 1004. | | | | | | 10. FBC 303.4, A3 OCCUPANCY INCLUDES GYMNASIUMS, PLAN | | | PROPOSES BUSINESS FOR THE SPIN AREAS. EXPLAIN RATIONALE | | | OR REVISE PLAN. IF PLAN IS NOT REVISED TO A3, PLEASE | | | EMAIL RATIONALE PRIOR TO RESUBMITTING. | | | | | | 11. PROVIDE INFORMATION REGARDING THE USE OF THE FRONT | | | PATIO AREA FOR SEATING, VENDING, AND EXIT DISCHARGE. IT | | | IS NOT CLEAR HOW MANY OCCUPANTS WILL BE SEATED IN THIS | | | AREA, HOW MANY OCCUPANTS WILL BE FORCED TO TRAVEL | | | THROUGH THIS AREA AS A REQUIRED EXIT DISCHARGE. HOW | | | WILL THE REQUIRED EXIT PATH BE KEPT CLEAR? NO SEATING | | | PLAN WAS SHOWN, BUT MY UNDERSTANDING IS THAT THIS AREA | | | WILL BE USED FOR DINING AND EVENTS. FBC 107. | | | | | | 12. AN OCCUPANT LOAD OF 30 SF PER PERSON FOR MERCANTILE | | | DOES NOT APPEAR TO BE A REASONABLE OCCUPANT LOAD | | | | | | 13. FBC 303.1.2, IT APPEARS THAT THE FOOD AND DRINK | | | VENDORS SHOULD BE CLASSIFIED AS BUSINESS OCCUPANCY OR | | | A2 RATHER THAN MERCANTILE. REVISE OR PROVIDE | | | CLARIFICATION. | | | | | | 14. CLARIFY DESIGN INTENT REGARDING HARDWARE FOR EXIT | | | DOORS A1.1.1. HARDWARE SET 1 IS SPECIFIED FOR THE EXIT | | | DOORS AND INCLUDE A PUSH BAR. IS THE "PUSH BAR" A PANIC | | | DEVICE OR FIRE EXIT HARDWARE IN COMPLIANCE WITH | | | FBC1008.1.10? | | | | | | IT APPEARS THAT THE FOOD AND DRINK VENDING AREAS WITH | | | THEIR SHARED SEATING AREA (REAR PATIO) WILL HAVE AN | | | OCCUPANT LOAD WHICH EXCEEDS 50, SO PANIC BARS WOULD BE | | | REQUIRED, FBC 1008.1.10. IT APPEARS THAT THIS IS | | | DESIGNER?S INTENT. REVISE PLAN TO SPECIFY PANIC BARS | | | FOR HARDWARE SET 1 OR CONTACT ME TO DISCUSS. | | | | | | NOTE THAT 30 SF PER PERSON FOR MERCANTILE IS FOR USES | | | OF MERCANTILE TYPE SPACES; STORES WITH DISPLAYS AND ONE | | | OR TWO CHECK OUT AREAS. THE SPACE PROPOSED INCLUDES | | | ONLY THE CONCENTRATED CHECK OUT AREA TYPE OF SPACE, SO | | | 30 SF PER PERSON DOES NOT APPEAR TO BE A NUMBER | | | CONSISTENT WITH THE USE. | | | | | | NOTE ALSO THAT, WITH PANIC DEVICES, SPACE COMPLIES WITH | | | A2 OCCUPANCY FOR FBC BUILDING. | | | | | | 15. FBC 107, MINIMUM 1/8 INCH SCALE REQUIRED, ALS1.1, | | | A1.1.1. | | | | | | 16. SHOW THE EXIT DISCHARGE FROM THE REAR STAIRS TO THE | | | PUBLIC WAY, FBC 1027. | | | | | | 17. E6 DOES NOT SHOW AN EXIT SIGN AT THE REAR EXIT, FBC | | | 1011.1. | | | | | | 18. ALS1.1, BUILDING DIAGONAL TO SHOW THAT TWO REQUIRED | | | EXITS ARE REMOTELY LOCATED SHOULD MEASURE SPACE WHICH | | | IS SERVED BY THE TWO EXITS. THE DIAGONAL INCLUDES A | | | LARGE SPACE WHICH HAS A SEPARATE EXIT. THE DIMENSION | | | BETWEEN THE TWO EXITS SHOULD MEASURE THE TWO EXITS | | | WHICH SERVE THE SPACE REQUIRING TWO EXITS, FBC | | | 1015.2.1. THE DIMENSION SHOWN MEASURES TWO EXITS | | | SERVING TWO DIFFERENT PORTIONS OF THE BUILDING. | | | | | | 19. REVISE PLAN TO SHOW COMPLIANCE WITH FBC 1006, MEANS | | | OF EGRESS ILLUMINATION, REAR EXIT AND, IF APPLICABLE, | | | THE SECOND EXIT FOR ROOM 134. E6.0, PHM1, DO NOT SHOW | | | ANY LIGHTING FOR THE REAR EXIT AND EXIT DISCHARGE TO | | | THE PUBLIC WAY. | | | | | | 20. REQUIRED FIRE RATED WALLS ARE NOT SHOWN. AT LEAST | | | TWO SIDES OF THE BUILDING LIKELY HAVE FIRE RATING | | | REQUIREMENTS AS THEY SIT IN CLOSE PROXIMITY TO THE | | | PROPERTY LINE. REVISE PLAN TO SHOW ALL FIRE RATED | | | WALLS, FBC TABLE 705.8, FBC EXISTING BUILDING 1012.6. | | | | | | 21. FBC ACCESSIBILITY 207.1, REVISE PLAN TO INDICATE | | | WHICH METHOD OF COMPLIANCE IS ELECTED. | | | | | | 22. THE APPLICATION SUBMITTED IS FOR 1401 CLARE AVENUE, | | | BUT THE PARCEL ID AND SITE ARE CONSISTENT WITH 1301 | | | CLARE AVENUE PER PROPERTY APPRAISER. REVISE PLAN AND | | | APPLICATION OR CLARIFY. IF APPLICANT WOULD LIKE THE | | | ADDRESS CHANGED TO 1401 CLARE AVENUE, PLEASE ADVISE. AT | | | THIS TIME IT APPEARS THAT THE LEGAL ADDRESS FOR THIS | | | PARCEL IS 1301 CLARE AVENUE. | | | | | | 23. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL, FBC 107. THE PRODUCT | | | APPROVALS SUBMITTED WERE REVIEWED BY SOMEONE OTHER THAN | | | ARCHITECT OF RECORD. PER BUILDING OFFICIAL, A DESIGN | | | PROFESSIONAL OTHER THAN THE ARCHITECT OF RECORD BUT | | | FROM THE SAME OFFICE MAY REVIEW ON BEHALF OF THE | | | ARCHITECT OF RECORD. THAT LICENSED INDIVIDUAL IS TO | | | INCLUDE THEIR FULL NAME AND LICENSE NUMBER ON THE | | | REVIEW STAMP. | | | | | | THE 3100 RESISTOR STOREFRONT IS REFERENCED ON SHEET | | | A1.1.1, BUT I WAS UNABLE TO LOCATE A REFERENCE TO THE | | | DOOR. EITHER HAVE ARCHITECT SIGN THE SHOP DRAWING | | | REVIEW STAMP FOR THE DOOR, OR INCORPORATE A REFERENCE | | | IN THE PLAN. FYI, IF ARCHITECT?S REVIEW IS DONE VIA A | | | REFERENCE IN THE PLAN, A CHANGE OF PRODUCT WOULD | | | REQUIRE A REVISION TO THE PLAN AS WELL AS A NEW PRODUCT | | | APPROVAL TO BE SUBMITTED. | | | | | | 24. PROVIDE A DETAIL FOR THE RAMP WHICH SHOWS | | | COMPLIANCE WITH FBC ACCESSIBILITY 405.7, LANDINGS AT | | | THE TOP AND BOTTOM OF THE RAMP. | | | | | | 25. PROVIDE A DETAIL FOR THE RAMP WHICH SHOWS | | | COMPLIANCE WITH FBC ACCESSIBILITY 405.6, RAMP RISE NOT | | | TO EXCEED 30 INCHES. A SECTION IS SUGGESTED. | | | | | | 26. A2.01, DETAIL A, SHOWS A RAIN LEADER AND HOSE BIBB | | | AT THE BOTTOM OF THE RAMP. EITHER REVISE TO A DIFFERENT | | | LOCATION OR PROVIDE A DETAIL TO SHOW HOW THIS WILL NOT | | | AFFECT THE WALKING SURFACE STABILITY FBC ACCESSIBILITY | | | 302.1 AND HOW THIS WILL NOT PROTRUDE INTO THE MEANS OF | | | EGRESS. | | | | | | 27. A2.02, COUNTERTOP HEIGHT NOT CLEAR. DETAIL A SHOWS | | | A DIMENSION OF 2 FT FOR COUNTER BAR TOP, BUT THE NOTE | | | SPECS 42 INCHES. | | | | | | REVISE PLAN TO SHOW SEATING AREAS AND SHOW COMPLIANCE | | | WITH FBC ACCESSIBILITY 902. | | | | | | 28. FBC ACCESSIBILITY, REVISE PLAN TO SHOW LOCATION OF | | | CHECK OUT AISLES, SALES AND SERVICE COUNTERS, FBC | | | ACCESSIBILITY 904. | | | . A2.02 DETAIL 5 DEPICTS A WALL WITH WINDOWS AND DOORS, | | | CLARIFY LOCATION. | | | | | | 29. PROVIDE A DETAIL FOR THE MEANS OF EGRESS STAIR FROM | | | THE FRONT PATIO TO REAR OF BUILDING, FBC 107. S2.0 | | | APPEARS TO SHOW THIS AS EXISTING, A1.1.1 SPECS STEEL | | | STAIRS. | | | | | | 30. WHEN A CONTRACTOR IS ASSIGNED, PROVIDE A COPY OF | | | THE CONTRACT FOR THIS JOB, FBC 109. THE VALUE ON THE | | | PERMIT APPLICATION IS TO INCLUDE LABOR, MATERIALS, | | | OVERHEAD, PROFIT, EVEN IF PROVIDED BY OTHERS. | | | | | | THIS ITEM SHOULD NOT DELAY RESUBMITTAL (MAY BE DEALT | | | WITH AT A LATER DATE, PRIOR TO ISSUANCE). | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2017-01-14 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2017-01-14 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2017-01-14 |
Time |
13:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2016-12-13 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-12-13 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-12-13 |
Time |
08:59 |
Sent To |
|
|
| Notes |
| 2016-12-13 09:00:15 | ELECTRICAL COMMETS ADDRESSED, PLEASE ADDRESS FIRE | | | COMMENTS FOR AN ELECTRICAL APPROVAL. | | | | | | VAL PEREZ | | | *6717 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-10-17 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-10-17 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-10-17 |
Time |
08:49 |
Sent To |
|
|
| Notes |
| 2016-10-17 09:03:40 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE | | | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE | | | PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL LOW | | | VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE | | | ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA, WIRELESS | | | SYSTEMS, KITCHEN HOODS, ETC. A NOTE WILL SUFFICE. | | | 2. SHEET E1.0- PLEASE ADD A GENERAL NOTE TO SHEET TO | | | INDICATE THE REQUIREMENTS OF NEC 300.5D3 AND TABLE | | | 300.5 FOR MINIMUM COVER REQUIREMENTS FOR CONDUITS AND | | | THE PLACEMENT OF A WARNING RIBBON FOR THE SERVICE | | | LATERAL CONDUCTORS SHOWN FOR THIS PROJECT. A NOTE WILL | | | SUFFICE | | | 3. SHEET E1.0- ADD A NOTE TO MAINTAIN ALL ELECTRICAL | | | EQUIPMENT ABOVE THE BASELINE FLOOD ELEVATION PER STATE | | | AND CITY REGULATORY AGENCIES. | | | 4. SHEET E2.0-E3.0 LABEL GFCI PROTECTED ALL 120V 20A | | | RECEPTACLES WITHIN THE FOOD PREP AREAS AND WITHIN 6 FT | | | OF SINKS. SEE AREAS SHOWN AS FOOD PREP, PIZZA, TACO, | | | BUTCHER, BAKERY ETC. NEC 210.8B | | | 5. PROVIDE OR CLARIFY RECEPTACLE OUTLET REQUIRED FOR | | | ALL AHU UNITS FOR SERVICEABILITY. NEC 210.63 | | | 6. SHUNT TRIP BREAKERS NOT SHOWN ON PANEL SCHEDULE | | | DESIGNATIONS FOR ALL ELECTRICAL UNDER HOOD AREAS, | | | PLEASE CLARIFY. FBC 107.3.5 | | | 7. ADDRESS ANY MECHANICAL AND FIRE REVIEW COMMENTS | | | RELATED TO ELECTRICAL. | | | 8. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO | | | INDICATE NEC 110.24- AVAILABLE FAULT CURRENT- FIELD | | | MARKINGS; SEE VERBIAGE IN CODE. | | | 9. PER FBC-EC 405.7- A MINIMUM OF 50% OF ALL | | | RECEPTACLES SHALL BE AUTOMATICALLY CONTROLLED FOR | | | OFFICE AREAS. SHOW COMPLIANCE. | | | 10. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL | | | FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS | | | REGARDING THIS PROJECT. | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2016-12-14 |
|
|
Cont ID |
|
| Sent By |
mkhan |
Date |
2016-12-14 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
mkhan |
Date |
2016-12-14 |
Time |
12:50 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2017-01-11 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2017-01-06 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2017-01-06 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2017-01-06 14:20:50 | 1401 CLARE AVENUE | | | PERMIT #16090638 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | SPOKE WITH JOHN AT GS&P (01/11/17 @12:50PM) AND AGREED | | | TO PASS THE PLAN SUBJECT TO THE FOLLOWING ISSUES BEING | | | CORRECTED IN A FUTURE REVISION BEFORE A CO IS ISSUED: | | | | | | SHEET C2.1: RECOMMEND OPTION 5 BELOW FOR THE FIRE | | | BACKFLOW PREVENTER: | | | PER NFPA 24 SECTION 6.2.1, ALL CONNECTIONS TO PRIVATE | | | FIRE SERVICE MAINS FOR FIRE PROTECTION SYSTEMS SHALL BE | | | ARRANGED IN ACCORDANCE WITH ONE OF THE FOLLOWING SO | | | THAT THEY CAN BE ISOLATED: | | | (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40 | | | FEET FROM THE BUILDING. | | | (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST | | | INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED | | | CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE | | | BUILDING AS THE HEIGHT OF THE WALL FACING THE POST | | | INDICATOR VALVE. | | | (2) A WALL POST INDICATOR VALVE | | | (3) AN INDICATING VALVE IN A PIT, INSTALLED IN | | | ACCORDANCE WITH SECTION 6.4 | | | (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING | | | VALVE NOT LESS THAN 40 FEET FROM THE BUILDING. | | | (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A | | | BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE | | | SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET | | | BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF | | | THE WALL FACING THE BACKFLOW PREVENTER. | | | (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM | | | ACCESSIBLE FROM THE EXTERIOR | | | (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE | | | ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE | | | AUTHORITY HAVING JURISDICTION | | | | | | SHEET M18.0: COMMERCIAL COOKING EXHAUST : PLAN | | | INDICATES GREASE DUCT EXHAUSTS MOUNTED TO WEST FACE OF | | | BUILDING WALL AND DISCHARGING 10 FEET FROM THE PROPERTY | | | LINE; HOWEVER, CIVIL PLAN C2.1 INDICATES THAT THE WEST | | | WALL OF THE BUILDING IS VIRTUALLY LOCATED ON THE | | | PROPERTY LINE. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2016-12-01 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-12-01 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-12-01 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2016-12-01 11:49:18 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) REPEAT OF COMMENT 6: | | | | | | THE PROPOSED REMODEL APPEARS TO ALTER 50 OR MORE | | | AUTOMATIC FIRE SPRINKLERS. | | | | | | PER FL BLDG CODE 105.3..1.2(2) | | | | | | 2. FIRE SPRINKLER DOCUMENTS FOR ANY NEW BUILDING OR | | | ADDITION WHICH INCLUDES A FIRE SPRINKLER SYSTEM WHICH | | | CONTAINS 50 OR MORE SPRINKLER HEADS. PERSONNEL AS | | | AUTHORIZED BY CHAPTER 633 FLORIDA STATUTES, MAY DESIGN | | | A FIRE SPRINKLER SYSTEM OF 49 OR FEWER HEADS AND MAY | | | DESIGN THE ALTERATION OF AN EXISTING FIRE SPRINKLER | | | SYSTEM IF THE ALTERATION CONSISTS OF THE RELOCATION, | | | ADDITION OR DELETION OF NOT MORE THAN 49 HEADS, | | | NOTWITHSTANDING THE SIZE OF THE EXISTING FIRE SPRINKLER | | | SYSTEM. | | | | | | | | | NO FIRE PROTECTION DOCUMENTS HAVE BEEN SUBMITTED. THE | | | FUTURE SUBMITTAL OF SHOP DRAWINGS WILL NOT MEET THE | | | REQUIREMENTS OF THE BLDG CODE OR FAC. | | | | | | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, | | | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE | | | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF | | | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, | | | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER | | | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) | | | AND ANY PERFORMANCE BASED INFORMATION SUCH AS | | | PRE-ENGINEERED SYSTEMS. | | | | | | THE MASTER PLAN SUBMITTAL (THIS SUBMITTAL) SHALL | | | INCLUDE ALL OF THE REQUIRED ELEMENTS OF THE ABOVE NOTED | | | FAC EITHER IN WRITTEN NARRATIVE OR DRAWING FORMAT, | | | SIGNED AND SEALED BY THE EOC. SHOP DRAWINGS SHALL THEN | | | BE PREPARED AND SUBMITTED BASED ON THE EOR CRITERIA AT | | | THE APPLICBALE TIME UNDER SEPARATE PERMIT SUBMITTAL. | | | | | | PLEASE PROVIDE THE REQUIRED DOCUMENTATION WITH THIS | | | PERMIT. | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2016-09-21 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2016-09-21 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2016-09-21 |
Time |
13:30 |
Sent To |
|
|
| Notes |
| 2016-09-21 14:23:17 | 1401 CLARE AVENUE | | | PERMIT #16090638 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | SHEET ALS1.1: AN EQUIPMENT LAYOUT IS NEEDED FOR THE | | | EXERCISE ROOMS IN ORDER TO UTILIZE AN OCCUPANT LOAD | | | FACTOR OF 50 SQ.FT. PER PERSON. | | | | | | SHEET ALS1.1: WITH ALL THESE FOOD PLACES LOCATED WITHIN | | | A SINGLE BUILDING, WILL SEATING BE PROVIDED? HAS AN | | | ASSEMBLY OCCUPANCY BEEN CONSIDERED GIVING THE BUILDING | | | USE MORE FLEXIBILITY. | | | | | | SHEET ALS1.1: DESCRIBE THE USE OF FLIGHT #101 AND BIRD | | | #121. | | | | | | SHEET A1.1.1: WHAT IS THE USE/FUNCTION OF PATIO #106. | | | | | | COMMERCIAL COOKING EXHAUST (CAPTIVEAIRE) SHEET 11 OF | | | 11: PLAN INDICATES GREASE DUCT EXHAUSTS MOUNTED TO WEST | | | FACE OF BUILDING WALL AND DISCHARGING 10 FEET FROM THE | | | PROPERTY LINE; HOWEVER, CIVIL PLAN C2.1 INDICATES THAT | | | THE WEST WALL OF THE BUILDING IS VIRTUALLY LOCATED ON | | | THE PROPERTY LINE. | | | | | | FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION | | | 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES | | | SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE | | | DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE | | | SPRINKLERS. PER FLORIDA ADMINISTRATIVE CODE SECTION | | | 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS | | | SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER | | | SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE | | | TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR | | | EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN | | | DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT | | | FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION | | | SUCH AS PRE-ENGINEERED SYSTEMS. AFTER THE BUILDING | | | PERMIT HAS BEEN ISSUED, THE SPRINKLER SUBCONTRACTOR CAN | | | THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED | | | CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. | | | | | | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY | | | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING | | | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM | | | WWW.KNOXBOX.COM. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2016-12-07 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-12-07 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-12-06 |
Time |
17:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2017-02-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-02-27 |
Time |
12:30 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-02-22 |
Time |
16:32 |
Sent To |
|
|
| Notes |
| 2017-02-22 16:32:18 | TO SHILL DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-01-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-01-19 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-12-22 |
Time |
14:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-12-13 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-12-13 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-12-13 |
Time |
09:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-10-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-10-27 |
Time |
09:10 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-09-16 |
Time |
10:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
4 |
Status |
P |
Date |
2017-03-01 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-03-01 |
Time |
06:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-03-01 |
Time |
06:43 |
Sent To |
|
|
| Notes |
| 2017-03-01 06:43:42 | MU 2017-4432 | | | | | | RECEIPT WAS RECEIVED VIA EMAIL AND FORWARDED TO RECORDS | | | VIA EMAIL | | | TWO COMPLETE SETS OF PLANS (SAME AS PLANS REVIEWED) | | | WERE RETURNED TO THIS OFFICE FROM IMPACT FEES. THE | | | COVER SHEETS WITH THE COUNTY IMPACT FEE STAMP WERE | | | REMOVED FROM EACH SET AND PUT WITH THE PERMIT SETS. | | | | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
F |
Date |
2017-02-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-02-27 |
Time |
12:28 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-02-27 |
Time |
12:28 |
Sent To |
|
|
| Notes |
| 2017-02-27 12:29:21 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | PRIOR TO ISSUANCE OF A BUILDING PERMIT, AN IMPACT FEE | | | ASSESSMENT IS REQUIRED. THE PLANS ARE TO BE STAMPED AND | | | THE RECEIPT SHOWING THAT ANY FEES DUE, WERE PAID. | | | | | | THE PLANS HAVE BEEN STAMPED. PROVIDE THE RECEIPT | | | SHOWING THAT THE IMPACT FEES OF $89,435.37 HAVE BEEN | | | PAID. THIS MAY BE DONE VIA EMAIL. | | | | | | MU 2017-4432 | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2017-01-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-01-19 |
Time |
06:54 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-01-19 |
Time |
06:53 |
Sent To |
|
|
| Notes |
| 2017-01-19 06:54:20 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | PRIOR TO ISSUANCE OF A BUILDING PERMIT, AN IMPACT FEE | | | ASSESSMENT IS REQUIRED. THE PLANS ARE TO BE STAMPED AND | | | THE RECEIPT SHOWING THAT ANY FEES DUE, WERE PAID. | | | | | | 561-233-5025 FOR MORE INFORMATION | | | | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2016-10-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-10-18 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-10-18 |
Time |
15:38 |
Sent To |
|
|
| Notes |
| 2016-10-18 15:39:23 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | PRIOR TO ISSUANCE OF A BUILDING PERMIT, AN IMPACT FEE | | | ASSESSMENT IS REQUIRED. THE PLANS ARE TO BE STAMPED AND | | | THE RECEIPT SHOWING THAT ANY FEES DUE, WERE PAID. | | | | | | 561-233-5025 FOR MORE INFORMATION | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2017-01-10 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-01-10 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-01-09 |
Time |
16:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2016-11-28 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-11-28 |
Time |
12:04 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-11-28 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2016-11-28 12:14:11 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16090638 | | | 11/28/16 | | | | | | 1) SYSTEM COMMISSIONING IS REQUIRED IN ACCORDANCE WITH | | | SECTION C408 FBC-14 ENERGY CONSERVATION. SEE SECTION | | | C408.2.1 AND PROVIDE A COMMISSIONING PLAN. | | | | | | 2) M1.0: CU-1 & 2 ARE LOCATED WITHIN 10' OF THE ROOF | | | EDGE. PLEASE VERIFY THAT THERE IS AN EXISTING 42" HIGH | | | PARAPET WALL THERE OR PROVIDE A GUARD- SECTION 304.11. | | | | | | 3) CLARIFY HOW ACCESS TO THE ROOFTOP MECHANICAL | | | EQUIPMENT IS BEING PROVIDED. IS THERE AN EXISTING ROOF | | | LADDER AND HATCH?- SECTION 306.5. | | | | | | 4) OUTDOOR AIR INTAKES SHALL BE LOCATED A MINIMUM OF | | | 10' FROM STREETS, ALLEYS, PARKING LOTS OR OTHER DRIVE | | | AREAS PER SECTION 401.4. PLEASE INDICATE COMPLIANCE ON | | | THE PLAN. | | | | | | 5) PLEASE NOTE THAT AN INCREASE IN OCCUPANT LOADS BASED | | | ON BUILDING REVIEW COMMENTS MAY RESULT IN INCREASED | | | OUTDOOR AIR SUPPLY WHICH WILL REQUIRE REVISED O/A | | | CALCULATIONS AND POSSIBLY INCREASED COOLING AND HEATING | | | CAPACITIES. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-09-28 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-09-28 |
Time |
08:38 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-09-27 |
Time |
17:17 |
Sent To |
|
|
| Notes |
| 2016-09-28 09:02:16 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16090638 | | | 9/28/16 | | | | | | 1) SEPARATE PERMITS AND PLANS ARE REQUIRED FOR KITCHEN | | | EXHAUST HOODS, FIRE SUPRESSION SYSTEMS, AND WALK-IN | | | COOLERS AND FREEZERS. PLEASE PLACE A NOTE ON THE PLAN | | | IN BOLD LETTERS. | | | | | | 2) PROVIDE MINIMUM VENTILATION CALCULATIONS ON THE PLAN | | | PER TABLE 403.3. PROVIDE A SCHEDULE OR TABLE THAT SHOWS | | | THE REQUIRED AND PROVIDED CFMS OF O/A. | | | | | | 3) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE | | | GAS-FIRED COOKING APPLIANCE- SECTION 304 FBC-14 FUEL | | | GAS. | | | | | | 4) PROVIDE INSTALLATION DETAILS FOR THE AHU'S. | | | | | | 5) PROVIDE PRIMARY AND SECONDARY CONDENSATE DISPOSAL | | | DETAILS FOR THE AHU'S- SECTION 307. SHOW THE PRIMARY | | | PIPING RUNS AND DISCHARGE LOCATIONS. | | | | | | 6) THE PLAN DESIGNATES ONE TENANT ROOM AS A BAKERY, | | | HOWEVER NO BAKING OVENS ARE SHOWN IN THE SCHEDULES- | | | PLEASE REVIEW AND VERIFY NO BAKING TO BE DONE IN THE | | | ROOM. | | | | | | 7) SHEET M2.0: TRANSFERRED AIR FROM THE FOOD PREP 104 | | | TO THE HALL 100 IS PROHIBITED PER SECTION 601.2. THE | | | LOCATION OF THE GRILL IN THE ROOM IS ALSO NOT IN | | | COMPLIANCE WITH SECTION 918.6. | | | | | | 8) M3.0: TRANSFERRED AIR FROM THE STORAGE 119 TO THE | | | CORRIDOR 120 IS PROHIBITED- SECTION 601.2. | | | | | | 9) SOME OF THE RETURN GRILLS FOR THE AHU'S APPEAR | | | UNDERSIZED FOR THE AMOUNT OF CFMS BEING RETURNED. | | | PLEASE INDICATE WHAT CALULATION METHODOLOGY IS BEING | | | USED FOR SIZING THE GRILLS. | | | | | | 10) PROVIDE A MECHANICAL ROOF PLAN SHOWING ALL REQUIRED | | | CLEARANCE DISTANCE MEASUREMENTS FROM AIR INTAKES TO | | | EXHAUST OUTLETS, AND FROM EQUIPMENT TO ROOF EDGES. | | | | | | 11) SUBMIT THE NOA'S LISTED ON THE PLANS FOR THE ROOF | | | STANDS AND LOUVERS WITH SHOP DRAWING APPROVAL | | | SIGNATURES. PLEASE HIGHLIGHT, CIRCLE, OR OTHERWISE MARK | | | ALL APPLICABLE INSTALLATION DETAILS, NOTES, DESIGN | | | PRESSURES, ETC. ON THE ROOF STAND NOA. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
P |
Date |
2016-12-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-12-09 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-12-09 |
Time |
10:54 |
Sent To |
|
|
| Notes |
| 2016-12-09 10:55:29 | ****PROVISO**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | ABBREVIATIONS USED (SEE ALSO FBC 1612): | | | | | | BFE, BASE FLOOD ELEVATION | | | DFE, DESIGN FLOOD ELEVATION (BFE PLUS FREEBOARD AND | | | OTHER REQUIREMENTS) | | | FFE, FINISHED FLOOR ELEVATION | | | FIRM, FLOOD INSURANCE RATE MAP | | | SFHA, SPECIAL FLOOD HAZARD AREA | | | | | | THIS STRUCTURE IS LOCATED IN SFHA ZONE A8, BFE 13 FEET | | | NGVD29 PER FIRM. BASED ON PROJECT VALUE AND PROPERTY | | | APPRAISER VALUE OF THE STRUCTURE, THIS IS CONSIDERED A | | | SUBSTANTIAL IMPROVEMENT. | | | | | | PROPERTY APPRAISER PROPOSED 2016 VALUE FOR STRUCTURE, | | | $480,558 | | | VALUE OF IMPROVEMENT, $1,000,000 | | | | | | BASED ON THE SURVEY PROVIDED (MILLER SURVEYING DEC 23, | | | 2015) THE FINISHED FLOOR FOR THIS BUILDING IS 18.20, | | | WHICH COMPLIES WITH THE MINIMUM DFE WHICH APPEARS TO BE | | | 14 FT NGVD29. | | | | | | PRIOR TO CONCRETE POUR, A FORM BOARD SURVEY WITH | | | ELEVATIONS WILL BE REQUIRED. ALL IMPROVEMENTS ARE TO BE | | | AT OR ABOVE DFE OR BE DESIGNED TO RESIST FLOOD LOADS, | | | FBC 1612. | | | | | | 7. PROVISO, PRIOR TO FINAL INSPECTION, THE FOLLOWING IS | | | TO BE SUBMITTED: | | | | | | A. COMPLETED ELEVATION CERTIFICATE. ALL EQUIPMENT AND | | | IMPROVEMENTS TO BE ABOVE DFE (14 FEET NGVD29). | | | B. PHOTOGRAPHS OF ALL SIDES OF THE STRUCTURE | | | C. PHOTOGRAPHS OF ALL MECHANICAL AND UTILITY EQUIPMENT | | | LOCATED OUTSIDE THE BUILDING SHOWING ITS RELATION TO | | | THE BUILDING AND GROUND AND ITS REQUIRED ANCHORING. | | | | | | NOTE THAT ROOFTOP EQUIPMENT IS NOT EXEMPTED FROM | | | PHOTOGRAPH REQUIREMENTS. | | | | | | THESE REQUIREMENTS ARE FROM CRS ACTIVITY RA3 TO | | | DOCUMENT COMPLIANCE WITH FBC 1612. | | | | | | | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2016-10-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-10-26 |
Time |
07:41 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-10-26 |
Time |
07:41 |
Sent To |
|
|
| Notes |
| 2016-10-26 08:49:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | ABBREVIATIONS USED (SEE ALSO FBC 1612): | | | | | | BFE, BASE FLOOD ELEVATION | | | DFE, DESIGN FLOOD ELEVATION (BFE PLUS FREEBOARD AND | | | OTHER REQUIREMENTS) | | | FFE, FINISHED FLOOR ELEVATION | | | FIRM, FLOOD INSURANCE RATE MAP | | | SFHA, SPECIAL FLOOD HAZARD AREA | | | | | | THIS STRUCTURE IS LOCATED IN SFHA ZONE A8, BFE 13 FEET | | | NGVD29 PER FIRM. BASED ON PROJECT VALUE AND PROPERTY | | | APPRAISER VALUE OF THE STRUCTURE, THIS IS CONSIDERED A | | | SUBSTANTIAL IMPROVEMENT. | | | | | | PROPERTY APPRAISER PROPOSED 2016 VALUE FOR STRUCTURE, | | | $480,558 | | | VALUE OF IMPROVEMENT, $1,000,000 | | | | | | BASED ON THE SURVEY PROVIDED (MILLER SURVEYING DEC 23, | | | 2015) THE FINISHED FLOOR FOR THIS BUILDING IS 18.20, | | | WHICH COMPLIES WITH THE MINIMUM DFE WHICH APPEARS TO BE | | | 14 FT NGVD29. | | | | | | AS A SUBSTANTIAL IMPROVEMENT, THE FOLLOWING IS | | | REQUIRED: | | | | | | 1. REVISE PLAN TO SHOW ALL EQUIPMENT SERVICING THE | | | BUILDING, EXISTING AND PROPOSED. MECHANICAL EQUIPMENT | | | IS SHOWN ON OTHER PAGES (SUCH AS E4.0). INCORPORATE | | | INTO PLAN WITH PROPOSED ELEVATION. | | | | | | 2. REVISE PLAN TO INCORPORATE THE FFE. | | | | | | 3. REVISE PLAN TO SHOW PROPOSED ELEVATION OF THE BOTTOM | | | OF THE RAMP AND STAIRS. | | | | | | 4. THE SURVEY AND CIVIL PAGES ARE REQUIRED TO BE | | | SIGNED, SEALED DATED ORIGINALS FS471. THESE SHEETS ARE | | | REQUIRED TO SHOW COMPLIANCE WITH FBC 1612 (AND OTHER | | | CODE REQUIREMENTS). | | | | | | 5. PROVISO, PRIOR TO CONCRETE POUR, A FORM BOARD SURVEY | | | WITH ELEVATIONS WILL BE REQUIRED. ALL IMPROVEMENTS ARE | | | TO BE AT OR ABOVE DFE OR BE DESIGNED TO RESIST FLOOD | | | LOADS, FBC 1612. | | | | | | 6. PROVISO, PRIOR TO FINAL INSPECTION, THE FOLLOWING IS | | | TO BE SUBMITTED: | | | | | | A. COMPLETED ELEVATION CERTIFICATE. ALL EQUIPMENT AND | | | IMPROVEMENTS TO BE ABOVE DFE (14 FEET NGVD29). | | | B. PHOTOGRAPHS OF ALL SIDES OF THE STRUCTURE | | | C. PHOTOGRAPHS OF ALL MECHANICAL AND UTILITY EQUIPMENT | | | LOCATED OUTSIDE THE BUILDING SHOWING ITS RELATION TO | | | THE BUILDING AND GROUND AND ITS REQUIRED ANCHORING. | | | | | | NOTE THAT ROOFTOP EQUIPMENT IS NOT EXEMPTED FROM | | | PHOTOGRAPH REQUIREMENTS. | | | | | | THESE REQUIREMENTS ARE FROM CRS ACTIVITY RA3 TO | | | DOCUMENT COMPLIANCE WITH FBC 1612. | | | | | | PLEASE FEEL FREE TO CONTACT ME TO DISCUSS. | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2017-01-19 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-01-19 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-01-19 |
Time |
11:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2016-12-07 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-12-07 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-12-06 |
Time |
11:48 |
Sent To |
|
|
| Notes |
| 2016-12-07 09:07:05 | 2ND REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: PREVIOUS COMMENT | | | | | | | | | NOT COMPLIED 12. IT APPEARS THAT THE MAIN BATHROOM IS | | | COMBINED BATHROOM GROUP FOR BOTH SEX. BATHROOMS SHALL | | | COMPLY WITH . FBC PL 403.2 SEPARATE FACILITIES. | | | WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE | | | FACILITIES SHALL BE PROVIDED FOR EACH SEX. | | | IF YOU INTEND TO USE EACH SEPARATE TOILET ROOM TO | | | PROVIDE SEPARATE FACILITIES YOU SHALL PROVIDE A | | | LAVATORY IN EACH TOILET ROOM. PER FPC PL 405.3.2 | | | | | | 1. THE 2 TOILET ROOMS THAT DO NOT HAVE LAVATORY'S IN | | | THEM DO NOT COMPLY WITH FPC PL 405.3.2 THESE TOILET | | | ROOMS ARE NOT REQUIRED TO MEET THE FIXTURE COUNT. IF | | | YOUR REQUESTING RELIEF FROM THIS CODE SEC PLEASE | | | PROVIDE SIGNED AND SEALED LETTER ADDRESSED TO ROBERT | | | BROWN REFERENCING THAT THESE ARE NOT REQUIRED FIXTURES | | | AND COULD BE DELETED IF THE OCCUPANCY STAYS AS A | | | MERCANTILE. | | | | | | 2. PLEASE COMPLY WITH BUILDINGS COMMENTS ON THE | | | OCCUPANCY TYPE. WPB AMEND TO FBC 107.2.1 | | | | | | | | | PLEASE FEEL FREE TO CONTACT ME TO SET UP A MEETING TO | | | GET THIS ISSUE RESOLVED. | | | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2016-10-19 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-10-19 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-10-14 |
Time |
10:20 |
Sent To |
|
|
| Notes |
| 2016-10-19 16:10:11 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. PLEASE SHOW DEPTH OF SHOWER SHALL COMPLY WITH FBC | | | ACC 608.2.2 | | | | | | 2. SHOW CLEAR FLOW SPACE FOR SHOWER SHALL COMPLY WITH | | | FBC ACC 608.2.2.1 | | | | | | 3. PLEASE SHOW THE END OF THE GRAB BARS IN SHOWER 6IN. | | | FROM ADJACENT WALLS PER FBC ACC 608.3.2 | | | | | | 4. PLEASE INDICATE WITCH WALL SHOWER CONTROLS WILL BE | | | LOCATED AND SHOW COMPLIANCE WITH FBC ACC 608.5.2 | | | | | | 5. DOR SWING IN BATHROOMS SHALL COMPLY WITHE FBC ACC | | | 603.2.3 DOOR SWING. | | | DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR | | | CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE | | | PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE. | | | | | | 6. A SEPARATE PERMIT IS REQUIRED FOR BACK FLOW.PER WPB | | | UTILITIES DEPT. | | | | | | 7. THE DFU STATED ON BUILDING SEWER APPEARS LOW PLEASE | | | PROVIDE CALCULATIONS PER FBC PL SEC 709 AND INDICATE ON | | | THE PLAN THE SLOPE OF THE PIPE. SHALL COMPLY WITH FBC | | | PL TABLE 710.1(1) | | | | | | 8. THE FLOOR SINKS THAT ARE SERVING DELI OR DISPLAY | | | CASES SUCH AS IN RM 107, 108 SHALL HAVE TRAP PRIMERS | | | PER FBC PL 1002.4 | | | | | | 9. PLEASE PROVIDE A OCCUPANT LOAD BREAKDOWN BY AREA AND | | | ROOM. PER WPB AMEND TO FBC 107.2.1 | | | | | | 10. IF YOU ARE SERVING FOOD AND DRINKS TO THE PUBLIC | | | FOR CONSUMPTION ON THE PROPERTY IT SHALL BE CLASSIFIED | | | AS AN A2 NOT AN M OCCUPANCY. PER FBC 303.3 ASSEMBLY | | | GROUP A-2. | | | ASSEMBLY USES INTENDED FOR FOOD AND/OR DRINK | | | CONSUMPTION INCLUDING, BUT NOT LIMITED TO: | | | | | | BANQUET HALLS | | | | | | CASINOS (GAMING AREAS) | | | | | | NIGHTCLUBS | | | | | | RESTAURANTS, CAFETERIAS AND SIMILAR DINING FACILITIES | | | (INCLUDING ASSOCIATED COMMERCIAL KITCHENS) | | | | | | TAVERNS AND BARS | | | | | | 11. IS THER GOING TO BE SEATING ANYWHERE SUCH AS THE | | | PATIOS OR HALL AREAS PLEASE CLARIFY. PER WPB AMEND TO | | | FBC 107.2.1 | | | | | | 12. IT APPEARS THAT THE MAIN BATHROOM IS COMBINED | | | BATHROOM GROUP FOR BOTH SEX. BATHROOMS SHALL COMPLY | | | WITH . FBC PL 403.2 SEPARATE FACILITIES. | | | WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE | | | FACILITIES SHALL BE PROVIDED FOR EACH SEX. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
P |
Date |
2021-01-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-01-27 |
Time |
18:00 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2021-01-27 18:01:01 | EVANS HUGHES INSPECTIONS | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-01-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2017-01-09 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2017-01-09 11:46:09 | APPROVED WITH THE FOLLOWING SPECIFIC CONDITIONS: | | | | | | PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY | | | FOR THE BUILDING AT 1401 CLARE AVE, THE FOLLOWING | | | CONDITIONS SHALL BE ADDRESSED: | | | | | | 1.) A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE | | | PLAN, SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR | | | REVIEW. | | | | | | 2.) THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED | | | LANDSCAPE PERMIT SHALL BE INSTALLED AND PASSA FINAL | | | LANDSCAPE INSPECTION. | | | | | | PAUL GREILICH, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2016-11-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2016-11-22 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2016-11-22 14:41:29 | | | | 1.) LABEL SQUARE FOOTAGE OF ALL PROPOSED USES INCLUDING | | | FOOD AREAS, EXERCISE SPACE, FUTURE USES ETC. | | | | | | 2.) LANDSCAPING ON SITE WILL NEED TO MEET REGULATIONS | | | OUTLINED IN ARTICLE XIV OF THE CITY?S ZONING AND LAND | | | DEVELOPMENT REGULATIONS | | | | | | 3.) WHAT IS BEING PROPOSED FOR THE NORTHERNMOST PORTION | | | OF THE SITE? PROVIDE A SITE PLAN THAT INCLUDES THE | | | ENTIRE SITE. STAFF RECOMMENDS APPLICANT SUBMITS A SITE | | | PLAN AND LANDSCAPE PLAN CONCURRENTLY. | | | | | | 4.) INDICATE LOCATION AND DIMENSIONS OF LOADING ZONE | | | | | | 5.) DIMENSION PARKING STALLS AND DRIVE AISLES | | | | | | 6.) PROVIDE BICYCLE RACKS PER SEC. 94-485. INDICATE | | | SPACING AND ORIENTATION OF INDIVIDUAL BIKE RACKS | | | | | | 7.) PROVIDE DETAILS FOR PARKING SPACES, BIKE RACKS, | | | DUMPSTER | | | | | | | | | PAUL GREILICH | | | SENIOR PLANNER | | | [email protected] | | | (561)-822-1443 | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2016-09-27 |
|
|
Cont ID |
|
| Sent By |
pg |
Date |
2016-09-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2016-09-23 |
Time |
16:06 |
Sent To |
|
|
| Notes |
| 2016-09-27 11:07:16 | 1.) SHOW SQUARE FOOTAGE OF ALL PROPOSED USES INCLUDING | | | RESTAURANTS, EXERCISE SPACE, AND FUTURE USES | | | | | | 2.) LANDSCAPING ON SITE WILL NEED TO MEET REGULATIONS | | | OUTLINED IN ARTICLE XIV OF THE CITY?S ZONING AND LAND | | | DEVELOPMENT REGULATIONS | | | | | | 3.) TERMINAL ISLANDS ARE REQUIRED AFTER 10 CONSECUTIVE | | | PARKING SPACES PER SECTION 94-443 | | | | | | 4.) MITIGATION OF REMOVED TREES (4 PALMS, 1 FLOWERING | | | TREE) REQUIRED | | | | | | 5.) WHAT IS BEING PROPOSED FOR THE NORTHERNMOST PORTION | | | OF THE SITE? INDICATE IF IT WILL BE PAVED, LANDSCAPED, | | | ETC. | | | | | | 6.) INDICATE LOCATION AND DIMENSIONS OF LOADING ZONE | | | | | | 7.) DIMENSION PARKING STALLS AND DRIVE AISLES | | | | | | 8.) PROVIDE BICYCLE RACKS PER SEC. 94-485 | | | | | | 9.) PROVIDE PEDESTRIAN ACCESS TO BUILDING AND | | | SURROUNDING SIDEWALKS PER SEC. 94-172 | | | | | | PAUL GREILICH | | | SENIOR PLANNER | | | [email protected] | | | (561)-822-1443 | | | |
|
|
|