| 2016-12-30 06:45:38 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16090626 |
| | ADD: 1721 PALM BEACH LAKES BLVD. SUITE # E419 |
| | CONT: AIR SOUTH MECHANICAL INC. |
| | TEL: 305-828-9400 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW. |
| | DATE: FRI. DEC. 30/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE NOTE THE 1ST REVIEW WAS PASSED BELIEVING THIS |
| | TO BE A INDOOR COOLER/ FREEZER, THIS IS NOT THE CASE. |
| | IT APPEARS THAT INTERNATIONAL CODE STORAGE HAS HAD |
| | TESTING COMPLETED AND REVIEWED BY THE STATE OF FLORIDA |
| | FOR A STATEWIDE PRODUCT APPROVAL. PLEASE NOTE TO DATE |
| | NO FLORIDA COVERSHEET HAS BEEN PROVIDED WITH A CURRENT |
| | FLORIDA APPROVAL NUMBER. IF GOING THROUGH THE PROCESS |
| | AND NOT AFFIRMED BY THE STATE THEN LET US KNOW WE CAN |
| | E-MAIL THE FORMS FOR A LOCAL PRODUCT APPROVAL. THE CITY |
| | OF WEST PALM BEACH USES THE SAME 10 CRITERIA AS THE |
| | STATE BUT MUST BE SUBMITTED ON THE CITY FORMS FOR |
| | REVIEW BY THE BUILDING OFFICIAL. |
| | 2014 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | ADMINISTRATIVE CODE 61G20-3.004 OPTIONAL STATEWIDE |
| | APPROVAL. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)((G) EXTERIOR COOLER& FREEZERS. |
| | |
| | 2) SHEET K-3 DOES NOT PROVIDE WHO IS THE DESIGNER OF |
| | RECORD FOR THIS SHEET. IN THE TITLE BLOCK THERE IS NO |
| | DESIGNERS NAME TAKING RESPONSIBILITY FOR THE DESIGN. IT |
| | WOULD APPEAR THAT INTERNATIONAL COLD STORAGE IS THE |
| | DESIGNER. 2014 FLORIDA BUILDING CODE W 2014 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE. |
| | |
| | 3) SHEET K-3 IN THE CENTER OF THE SHEET THERE IS THE |
| | WIND DESIGN CRITERIA. UNDER THE HEADINGCOMPONENTS AND |
| | CLADDING ULTIMATE WIND. |
| | PRESSURES WALL ARE IN VULT. PLEASE CONVERT TO VASD |
| | SINCE ALL PRODUCT APPROVALS ARE IN VASD. |
| | ROOF PRESSURES DO NOT PROVIDE THE SQAURE FOOT AREA |
| | THESE PRESSURES WERE TAKEN FOR? FOR THE COMPONENTS AND |
| | CLADDING THE SQUARE FOOT AREA IS UASULLY TAKEN FOR THE |
| | FASTENERS OR 10 SQ. FT. IT ALSO APPEARS THEY ARE IN |
| | VULT, PLEASE ALSO PROVIDE IN VASD SINCE ALL PRODUCT |
| | APPROVALS ARE IN VASD. 1609.3.1 WIND SPEED CONVERSION. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |