Plan Review Details - Permit 16090500
Plan Review Stops For Permit 16090500
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-12-28 Cont ID  
Sent By cthroop Date 2016-12-28 Time 15:15 Rev Time 0.00
Received By cthroop Date 2016-12-28 Time 14:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-10-04 Cont ID  
Sent By cthroop Date 2016-10-04 Time 13:37 Rev Time 0.00
Received By cthroop Date 2016-10-04 Time 12:49 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2017-04-17 Cont ID  
Sent By vperez Date 2017-04-17 Time 08:47 Rev Time 0.00
Received By vperez Date 2017-04-17 Time 08:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2017-03-10 Cont ID  
Sent By vperez Date 2017-03-10 Time 09:32 Rev Time 0.00
Received By vperez Date 2017-03-10 Time 09:32 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-02-14 Cont ID  
Sent By vperez Date 2017-02-14 Time 13:36 Rev Time 0.00
Received By vperez Date 2017-02-14 Time 13:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-01-09 Cont ID  
Sent By vperez Date 2017-01-09 Time 03:54 Rev Time 0.00
Received By vperez Date 2017-01-09 Time 03:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-09-21 Cont ID  
Sent By vperez Date 2016-09-21 Time 08:44 Rev Time 0.00
Received By vperez Date 2016-09-20 Time 17:33 Sent To B
Notes
2016-09-21 08:48:58PLEASE CLARIFY EXISTING SUBPANEL LOAD AT GARAGE NOT
 SHOWN ON CALCULATION AT THE 200A PANEL. SHOULD BE A
 60/2POLE BREAKER SHOWN AND LOADS REFLECTED. FBC 107.3.5
  
 VAL PEREZ
 *6717

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2017-04-18 Cont ID  
Sent By hmoser Date 2017-04-18 Time 09:13 Rev Time 0.00
Received By hmoser Date 2017-04-13 Time 11:08 Sent To  
Notes
2017-04-14 11:08:34RESUB ROUTED TO VPEREZ

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-03-23 Cont ID  
Sent By hmoser Date 2017-03-23 Time 11:37 Rev Time 0.00
Received By hmoser Date 2017-03-09 Time 16:07 Sent To  
Notes
2017-03-09 16:07:36RESUB ROUTED TO VPEREZ

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-02-24 Cont ID  
Sent By cthroop Date 2017-02-24 Time 09:05 Rev Time 0.00
Received By cthroop Date 2017-02-24 Time 09:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-02-14 Cont ID  
Sent By vperez Date 2017-02-14 Time 13:37 Rev Time 0.00
Received By vperez Date 2017-02-14 Time 13:37 Sent To  
Notes
2017-02-13 12:44:32VPEREZ'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-26 Cont ID  
Sent By cpuell Date 2017-01-26 Time 12:46 Rev Time 0.00
Received By cpuell Date 2016-12-14 Time 11:28 Sent To  
Notes
2016-12-15 11:29:21R07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-05 Cont ID  
Sent By cpuell Date 2016-10-05 Time 08:38 Rev Time 0.00
Received By cpuell Date 2016-09-14 Time 10:49 Sent To  
Notes
2016-09-15 10:49:31R01

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-02-24 Cont ID  
Sent By cthroop Date 2017-02-24 Time 09:05 Rev Time 0.00
Received By cthroop Date 2017-02-24 Time 09:05 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-10-04 Cont ID  
Sent By cthroop Date 2016-10-04 Time 12:48 Rev Time 0.00
Received By cthroop Date 2016-10-04 Time 12:48 Sent To  
Notes
2016-10-04 12:48:52BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2017-04-18 Cont ID  
Sent By hmoser Date 2017-04-18 Time 09:13 Rev Time 0.00
Received By hmoser Date 2017-04-18 Time 08:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2017-03-23 Cont ID  
Sent By hmoser Date 2017-03-23 Time 11:36 Rev Time 0.00
Received By hmoser Date 2017-03-23 Time 11:30 Sent To  
Notes
2017-03-23 11:36:53PLAN DENIED
 HVAC LOAD CALCULATION AND PLAN DO NOT MATCH.
 LOAD CALCULATION CALLS FOR 2TON 15 SEER.
 PLAN CALLS FOR 1 1/2 TON 16 SEER .
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-02-21 Cont ID  
Sent By jvalido Date 2017-02-21 Time 17:50 Rev Time 0.00
Received By jvalido Date 2017-02-21 Time 17:21 Sent To  
Notes
2017-02-21 17:45:18CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) EQUIPMENT SCHEDULE STATES CONDENSER WITH (2) AIR
 HANDLER UNITS. PLANS SHOW ONLY (1) AIR HANDLER.
  
 FLORIDA ENERGY CODE FBC 2014
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-01-25 Cont ID  
Sent By jvalido Date 2017-01-25 Time 16:27 Rev Time 0.00
Received By jvalido Date 2017-02-14 Time 17:20 Sent To  
Notes
2017-01-25 16:14:52CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE EQUIPMENT SCHEDULE ON THE PLANS.
 (2) PROVIDE BATHROOM EXHAUST AS PER TABLE M1507.4
 MINIMUM REQUIRED LOCAL EXHAUST RATES FOR ONE- AND
 TWO-FAMILY DWELLINGS.
  
 FLORIDA ENERGY CODE FBC 2014
  
 (3) PROVIDE SIGNATURE OF "OWNER/AGENT" ON FORM
 R405-2014 ENERGY CALCULATIONS (AREA HIGHLIGHTED)
 (4) PROVIDE INFORMATION ON HEAT LOAD CALCULATIONS OF
 WHO PREPARED THE REPORT.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-10-04 Cont ID  
Sent By jvalido Date 2016-10-04 Time 17:45 Rev Time 0.00
Received By jvalido Date 2016-10-04 Time 17:36 Sent To  
Notes
2016-10-04 17:40:34CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE MECHANICAL PLANS.
  
 FLORIDA ENERGY CODE FBC 2014
  
 (2) PROVIDE FORM ENERGY AND HEAT LOAD CALCULATIONS
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-01-20 Cont ID  
Sent By gjohnson Date 2017-01-20 Time 14:26 Rev Time 0.00
Received By gjohnson Date 2017-01-20 Time 14:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-09-16 Cont ID  
Sent By tklarge Date 2016-09-16 Time 06:33 Rev Time 0.00
Received By tklarge Date 2016-09-16 Time 06:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-12-22 Cont ID  
Sent By   Date 2016-12-22 Time   Rev Time 0.00
Received By   Date 2016-12-22 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2016-09-19 Time 14:27 Rev Time 0.00
Received By pgreilic Date 2016-09-19 Time 14:27 Sent To  
Notes
***NONE***