| Plan Review Stops For Permit 16090458 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-10-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-10-12 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-10-12 |
Time |
08:19 |
Sent To |
|
|
| Notes |
| 2016-10-12 12:34:30 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 5TH EDITION | | | | | | 1. THIS STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD | | | AREA. THE SHELL WAS PERMITTED WITHOUT A CONCRETE FLOOR. | | | PROVIDE THE PERMIT NUMBER FOR THE FLOOR FOR THIS UNIT, | | | OR INCLUDE IN THIS SUBMITTAL. IF INCLUDED IN THIS | | | PERMIT, A FORM BOARD SURVEY WITH ELEVATIONS OR | | | ELEVATION CERTIFICATE WILL BE REQUIRED PRIOR TO | | | CONCRETE POUR. AN ELEVATION CERTIFICATE WILL BE | | | REQUIRED PRIOR TO FINAL INSPECTION. | | | | | | 2. FBC 2014 ACCESSIBILITY 208.2.2, REHABILITATION | | | FACILITIES AND OUTPATIENT PHYSICAL THERAPY FACILITIES | | | HAVE ADDITIONAL ACCESSIBLE PARKING REQUIREMENTS. REVISE | | | PLAN TO SHOW COMPLIANCE. | | | | | | 3. APPLICATION STATES SQUARE FOOT AREA IS 2500, PLAN | | | SHOWS 1599, EXPLAIN AREA DISCREPANCY AND REVISE, FBC | | | 107. | | | | | | 4. PLANS STATE THAT THIS IS AN EXISTING BUILDING, BUT | | | THIS WAS PERMITTED AS A SHELL BUILDING, C.O. TO BE | | | ISSUED UPON TENANT BUILDOUT. THIS PROJECT IS GOVERNED | | | BY FBC BUILDING, NOT EXISTING BUILDING, REVISE. | | | | | | 5. STRUCTURAL NOTES, A0.03, SEE FBC 1603.1.4 AND REVISE | | | WIND SPEED INFORMATION. | | | | | | 6. M2, RTU DETAIL REFERS TO STRUCTURAL FOR CURB DETAIL, | | | PROVIDE, FBC1609. | | | | | | 7. VALUE ADJUSTMENT PER ICC TABLE WAS DONE, FBC 109. | | | THE VALUE OF THE SHELL WAS DEDUCTED FROM THE VALUE IN | | | THE ICC TABLE. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-09-19 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-09-19 |
Time |
16:00 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-09-19 |
Time |
13:10 |
Sent To |
|
|
| Notes |
| 2016-09-19 16:03:11 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] FBC-E C405.5. INTERIOR LIGHTING POWER REQUIREMENTS. | | | A BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL | | | CONNECTED LIGHTING POWER CALCULATED UNDER SECTION | | | C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER | | | CALCULATED UNDER SECTION C405.5.2. PROVIDE A LIGHTING | | | POWER DENSITY CHART TO SHOW COMPLIANCE. | | | | | | 2] FBC-E C405.7.3 VOLTAGE DROP. FEEDERS & CUSTOMER | | | OWNED SERVICE CONDUCTORS SHALL BE SIZED FOR A MAXIMUM | | | OF 2% VOLTAGE DROP. BRANCH CIRCUITS SHALL BE SIZED FOR | | | A MAXIMUM OF 3% VOLTAGE DROP. | | | | | | 3] PROVIDE MANUFACTURE SPECS OF THE X-RAY MACHINE. FBC | | | 107 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2016-09-21 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2016-09-21 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2016-09-21 |
Time |
12:53 |
Sent To |
|
|
| Notes |
| 2016-09-21 13:01:55 | 8170 OKEECHOBEE BOULEVARD #7 | | | PERMIT #16090458 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | SHEET A2.01: DEAD-END CORRIDORS ARE LIMITED TO 20 FEET | | | IN BUSINESS OCCUPANCIES NOT PROTECTED BY AUTOMATIC | | | SPRINKLERS PER 38.2.5.2.2 OF NFPA 101. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-10-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-10-12 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-09-14 |
Time |
13:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-09-20 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-09-20 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-09-20 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2016-09-20 13:52:33 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING, | | | ENERGY CONSERVATION CODES | | | PERMIT #16090458 | | | 9/20/16 | | | | | | 1) SUBMIT AC COOLING AND HEATING CALCULATION IN | | | ACCORDANCE WITH SECTION C403.2.1 FBC-14 ENERGY | | | CONSERVATION. | | | | | | 2) THE SUBMITTED ENERGY FORM C402 MUST BE SIGNED BY THE | | | OWNER/AGENT- SECTION C103.1.1.2. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2016-10-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-10-12 |
Time |
08:38 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-10-12 |
Time |
08:38 |
Sent To |
|
|
| Notes |
| 2016-10-12 08:38:45 | SEE BUILDING REVIEW | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2016-10-03 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-10-03 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-10-03 |
Time |
11:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2016-10-04 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2016-10-04 |
Time |
12:05 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2016-10-04 |
Time |
12:05 |
Sent To |
|
|
| Notes |
| 2016-10-04 12:05:20 | FAILED | | | | | | CHIROPRACTOR'S OFFICES ARE CLASSIFIED AS MEDICAL | | | OFFICES BY THE CITY OF WEST PALM BEACH. RESOLUTION | | | 288-11, WHICH ESTABLISHES THE PERMITTED USES WITHIN THE | | | SEDONA COMMONS CPD, DOES NOT PERMIT MEDICAL OFFICE USES | | | IN THE BUILDING AT 8170 OKEECHOBEE BOULEVARD (BUILDING | | | NO. 7). DUE TO THE MEDICAL USE NOT BEING PERMITTED IN | | | THIS BUILDING, ZONING WILL NOT APPROVE THE BUILDING | | | PERMIT TO BUILD THE SPACE OUT AS A CHIROPRACTOR'S | | | OFFICE. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | |
|
|