Plan Review Details - Permit 16090458
Plan Review Stops For Permit 16090458
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-10-12 Cont ID  
Sent By shill Date 2016-10-12 Time 12:19 Rev Time 0.00
Received By shill Date 2016-10-12 Time 08:19 Sent To  
Notes
2016-10-12 12:34:30****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 5TH EDITION
  
 1. THIS STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA. THE SHELL WAS PERMITTED WITHOUT A CONCRETE FLOOR.
 PROVIDE THE PERMIT NUMBER FOR THE FLOOR FOR THIS UNIT,
 OR INCLUDE IN THIS SUBMITTAL. IF INCLUDED IN THIS
 PERMIT, A FORM BOARD SURVEY WITH ELEVATIONS OR
 ELEVATION CERTIFICATE WILL BE REQUIRED PRIOR TO
 CONCRETE POUR. AN ELEVATION CERTIFICATE WILL BE
 REQUIRED PRIOR TO FINAL INSPECTION.
  
 2. FBC 2014 ACCESSIBILITY 208.2.2, REHABILITATION
 FACILITIES AND OUTPATIENT PHYSICAL THERAPY FACILITIES
 HAVE ADDITIONAL ACCESSIBLE PARKING REQUIREMENTS. REVISE
 PLAN TO SHOW COMPLIANCE.
  
 3. APPLICATION STATES SQUARE FOOT AREA IS 2500, PLAN
 SHOWS 1599, EXPLAIN AREA DISCREPANCY AND REVISE, FBC
 107.
  
 4. PLANS STATE THAT THIS IS AN EXISTING BUILDING, BUT
 THIS WAS PERMITTED AS A SHELL BUILDING, C.O. TO BE
 ISSUED UPON TENANT BUILDOUT. THIS PROJECT IS GOVERNED
 BY FBC BUILDING, NOT EXISTING BUILDING, REVISE.
  
 5. STRUCTURAL NOTES, A0.03, SEE FBC 1603.1.4 AND REVISE
 WIND SPEED INFORMATION.
  
 6. M2, RTU DETAIL REFERS TO STRUCTURAL FOR CURB DETAIL,
 PROVIDE, FBC1609.
  
 7. VALUE ADJUSTMENT PER ICC TABLE WAS DONE, FBC 109.
 THE VALUE OF THE SHELL WAS DEDUCTED FROM THE VALUE IN
 THE ICC TABLE.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-09-19 Cont ID  
Sent By mvaldes Date 2016-09-19 Time 16:00 Rev Time 0.00
Received By mvaldes Date 2016-09-19 Time 13:10 Sent To  
Notes
2016-09-19 16:03:11REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] FBC-E C405.5. INTERIOR LIGHTING POWER REQUIREMENTS.
 A BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL
 CONNECTED LIGHTING POWER CALCULATED UNDER SECTION
 C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER
 CALCULATED UNDER SECTION C405.5.2. PROVIDE A LIGHTING
 POWER DENSITY CHART TO SHOW COMPLIANCE.
  
 2] FBC-E C405.7.3 VOLTAGE DROP. FEEDERS & CUSTOMER
 OWNED SERVICE CONDUCTORS SHALL BE SIZED FOR A MAXIMUM
 OF 2% VOLTAGE DROP. BRANCH CIRCUITS SHALL BE SIZED FOR
 A MAXIMUM OF 3% VOLTAGE DROP.
  
 3] PROVIDE MANUFACTURE SPECS OF THE X-RAY MACHINE. FBC
 107

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-09-21 Cont ID  
Sent By wjolin Date 2016-09-21 Time 13:01 Rev Time 0.00
Received By wjolin Date 2016-09-21 Time 12:53 Sent To  
Notes
2016-09-21 13:01:558170 OKEECHOBEE BOULEVARD #7
 PERMIT #16090458
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A2.01: DEAD-END CORRIDORS ARE LIMITED TO 20 FEET
 IN BUSINESS OCCUPANCIES NOT PROTECTED BY AUTOMATIC
 SPRINKLERS PER 38.2.5.2.2 OF NFPA 101.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-12 Cont ID  
Sent By shill Date 2016-10-12 Time 12:34 Rev Time 0.00
Received By shill Date 2016-09-14 Time 13:27 Sent To  
Notes
2016-09-15 13:27:11B08

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-09-20 Cont ID  
Sent By ccole Date 2016-09-20 Time 13:47 Rev Time 0.00
Received By ccole Date 2016-09-20 Time 13:47 Sent To  
Notes
2016-09-20 13:52:331ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #16090458
 9/20/16
  
 1) SUBMIT AC COOLING AND HEATING CALCULATION IN
 ACCORDANCE WITH SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
  
 2) THE SUBMITTED ENERGY FORM C402 MUST BE SIGNED BY THE
 OWNER/AGENT- SECTION C103.1.1.2.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2016-10-12 Cont ID  
Sent By shill Date 2016-10-12 Time 08:38 Rev Time 0.00
Received By shill Date 2016-10-12 Time 08:38 Sent To  
Notes
2016-10-12 08:38:45SEE BUILDING REVIEW
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-10-03 Cont ID  
Sent By gjohnson Date 2016-10-03 Time 11:47 Rev Time 0.00
Received By gjohnson Date 2016-10-03 Time 11:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-10-04 Cont ID  
Sent By eschneid Date 2016-10-04 Time 12:05 Rev Time 0.50
Received By eschneid Date 2016-10-04 Time 12:05 Sent To  
Notes
2016-10-04 12:05:20FAILED
  
 CHIROPRACTOR'S OFFICES ARE CLASSIFIED AS MEDICAL
 OFFICES BY THE CITY OF WEST PALM BEACH. RESOLUTION
 288-11, WHICH ESTABLISHES THE PERMITTED USES WITHIN THE
 SEDONA COMMONS CPD, DOES NOT PERMIT MEDICAL OFFICE USES
 IN THE BUILDING AT 8170 OKEECHOBEE BOULEVARD (BUILDING
 NO. 7). DUE TO THE MEDICAL USE NOT BEING PERMITTED IN
 THIS BUILDING, ZONING WILL NOT APPROVE THE BUILDING
 PERMIT TO BUILD THE SPACE OUT AS A CHIROPRACTOR'S
 OFFICE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  