| 2016-09-19 17:03:50 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #16090453 |
| | 9/19/16 |
| | |
| | 1) PROVIDE THE AC EQUIPMENT SCHEDULE ON THE PLAN. |
| | |
| | 2) IDENTIFY ALL ROOMS ON THE PLAN. |
| | |
| | 3) THE 6" DUCT IS UNDERSIZED FOR 170 CFMS- PLEASE |
| | INCREASE THE DUCT SIZE. |
| | |
| | 4) THE 20"X20" RETURN GRILL AT THE AHU CLOSET IS |
| | UNDERSIZED FOR RETURNING 1180 CFMS OF AIR: GRILL SIZE |
| | IS TYPICALLY 2 CFMS PER SQ. IN. |
| | |
| | 5) THE SUBMITTED PLAN HAS NOT BEEN PREPARED OR SIGNED |
| | BY THE CONTRACTOR- REFER TO SECTION 107.2 CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE IN |
| | ACCORDANCE WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| | |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND |
| | DRAWN UPON SUITABLE MATERIAL. ELECTRONIC MEDIA |
| | DOCUMENTS SHALL BE SUBMITTED WHEN APPROVED BY THE |
| | BUILDING OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, |
| | NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN |
| | DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF |
| | THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR |
| | OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE |
| | QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| | AND THE TECHNICAL CODES SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR |
| | SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR |
| | THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| | THE DESIGN. (SEE ALSO SECTION 107.3.5). |
| | |