Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-09-26 Cont ID  
Sent By ccole Date 2016-09-26 Time 12:57 Rev Time 0.00
Received By ccole Date 2016-09-26 Time 12:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-09-22 Cont ID  
Sent By ccole Date 2016-09-22 Time 07:29 Rev Time 0.00
Received By ccole Date 2016-09-22 Time 07:29 Sent To  
Notes
2016-09-22 07:36:172ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16090453
 9/22/16
  
 1) PROVIDE RETURN AIR FROM BEDROOM #4- SECTION M1602
 FBC-RESIDENTIAL.
  
 2) THE PLAN INDICATES 1180 CFMS AIR DISTRIBUTION AT THE
 TWO TRUNK LINES, BUT ONLY 956 CFMS ARE SHOWN AT THE
 BRANCH DUCTS AND DIFFUSERS- PLEASE CORRECT.
  
 3) WHEN RESUBNITTING OLEASE NOTE TWO SETS OF PLANS ARE
 REQUIRED PER SECTION 107.1 WPB AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-09-19 Cont ID  
Sent By ccole Date 2016-09-19 Time 16:54 Rev Time 0.00
Received By ccole Date 2016-09-19 Time 16:54 Sent To  
Notes
2016-09-19 17:03:501ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16090453
 9/19/16
  
 1) PROVIDE THE AC EQUIPMENT SCHEDULE ON THE PLAN.
  
 2) IDENTIFY ALL ROOMS ON THE PLAN.
  
 3) THE 6" DUCT IS UNDERSIZED FOR 170 CFMS- PLEASE
 INCREASE THE DUCT SIZE.
  
 4) THE 20"X20" RETURN GRILL AT THE AHU CLOSET IS
 UNDERSIZED FOR RETURNING 1180 CFMS OF AIR: GRILL SIZE
 IS TYPICALLY 2 CFMS PER SQ. IN.
  
 5) THE SUBMITTED PLAN HAS NOT BEEN PREPARED OR SIGNED
 BY THE CONTRACTOR- REFER TO SECTION 107.2 CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE IN
 ACCORDANCE WITH SECTIONS107.2.1 THROUGH 107.2.5.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND
 DRAWN UPON SUITABLE MATERIAL. ELECTRONIC MEDIA
 DOCUMENTS SHALL BE SUBMITTED WHEN APPROVED BY THE
 BUILDING OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF
 THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR
 SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR
 THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN. (SEE ALSO SECTION 107.3.5).
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER