Plan Review Details - Permit 16090358
Plan Review Stops For Permit 16090358
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-09-22 Cont ID  
Sent By mvaldes Date 2016-09-22 Time 15:35 Rev Time 0.00
Received By mvaldes Date 2016-09-22 Time 15:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-09-15 Cont ID  
Sent By mvaldes Date 2016-09-15 Time 13:57 Rev Time 0.00
Received By mvaldes Date 2016-09-15 Time 13:56 Sent To  
Notes
2016-09-15 14:08:10REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] PROVIDE A PANEL SCHEDULE, SHOW CONDUIT AND WIRE
 SIZES ON THE RISER DIAGRAM, AND CLARIFY HOW LOAD
 CALCULATION VALUE FOR THE DRYER IS 1500 VA ? PLEASE
 ADJUST ACCORDINGLY. FBC 107.3.5.3
  
 2] THE INTER-SYSTEM BONDING TERMINAL SHALL BE INSTALLED
 AS PER FBC-R_E3609.3
  
 3] CARBON MONOXIODE ALARMS REQUIRED WITHIN 10' OF EACH
 SLEEPING ROOM. FBC-R 315.1 ( ATTACHED GARAGE )
  
 4] MAIN DOOR BY THE FOYER REQUIRES A SWITCHED LIGHTING
 OUTLET ON THE EXTERIOR SIDE OF THE OUTDOOR EGRESS.
 FBC-R _E3903.3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-15 Cont ID  
Sent By mvaldes Date 2016-09-15 Time 14:09 Rev Time 0.00
Received By mvaldes Date 2016-09-12 Time 14:58 Sent To  
Notes
2016-09-12 14:59:19ROUTED TO ELECTRICAL INBOX