Plan Review Details - Permit 16090274
Plan Review Stops For Permit 16090274
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-10-21 Cont ID  
Sent By rmcdouga Date 2016-10-21 Time 18:25 Rev Time 0.00
Received By rmcdouga Date 2016-10-21 Time 16:26 Sent To  
Notes
2016-10-21 18:10:01PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ON SHEET A-1.0 THE COMPONENT AND CLADDING PRESSURES
 FOR ROOF ZONES 1, 2 & 3 ARE INCORRECT FOR A ONE STORY
 STRUCTURE WITH A 3/12 ROOF SLOPE IN EXPOSURE CATEGORY C
 WITH A 170 MPH VULT WINDSPEED. THE WINDSPEEDS THAT WERE
 CALCULATED BASED ON FBCR TABLE R301.2(2) AND R301.2(3)
 ARE +21.9, -35.4 PSF FOR ZONE 1, +21.9, -60.4 PSF FOR
 ZONE 2 AND +21.9, -89.4 PSF FOR ZONE 3. PLEASE RECHECK
 THE PRESSURES THAT WERE SPECIFIED ON THE PLANS AND MAKE
 CORRECTIONS AS NECESSARY.
  
 2) FBC R403.1.4 REQUIRES THE BOTTOM OF EXTERIOR
 FOOTINGS TO BE AT LEAST 12 INCHES BELOW GRADE. PLEASE
 REVISE THE WALL SECTION ON SHEET A1.1 ACCORDINGLY.
  
 3) SPECIFY THE SIZES OF THE DOORS ON THE PLANS. FBC
 107.2.1
  
 4) SHOW COMPLIANCE WITH FBC R 807.1 FOR ATTIC ACCESS TO
 THE ADDITION.
  
 5) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 ENERGY FORM R405. FBC ENERGY SECTION R103.1.1.2
  
 6) THE TRUSS ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 IS REQUIRED ON THE ROOF TRUSS DRAWINGS AND THE ROOF
 TRUSS LAYOUTS. SIGNATURE STAMPS, COPIES OR OTHER
 FACSIMILES ARE NOT ACCEPTABLE PER FAC 61G15-23.002.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-09-14 Cont ID  
Sent By albarran Date 2016-09-14 Time 12:55 Rev Time 0.00
Received By albarran Date 2016-09-14 Time 10:07 Sent To  
Notes
2016-09-14 12:56:031ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC)
  
 PROJECT NAME: WILLIAMS ADDITION
 JOB ADDRESS: 1353 13TH ST.
 DESCRIPTION: ADDITION TO HOUSE
 MASTER PERMIT: 16090274
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. YOU SHALL MARK ON THE SITE PLAN THE LOCATION OF THE
 ELECTRIC UTILITY POLE SERVING THE RESIDENCE ALONG WITH
 THE LOCATION OF THE ELECTRIC METER AND MAIN DISCONNECT.
 YOU SHALL INDICATE IF THE SERVICE FEEDER IS AERIAL OR
 UNDERGROUND.
 2. THE WORD ?ROMEX? AS USED IN THIS NOTE IS TO IDENTIFY
 A TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT A TYPE
 OF CABLE, REFER TO CABLE TYPES ?NM?, ?NMC? OR ?NMS?.
 3. THE WORD ?OUTLET? AS EXPRESSED IN NEC 210.12(B) DOES
 NOT IMPLY RECEPTACLES ONLY; IT REFERS TO EVERY OUTLET
 (MEANING EVERY CIRCUIT IN THE NAMED AREAS). CORRECT
 NOTE 5 ACCORDINGLY.
 4. FBC-RE4003.5 RECESSED INCANDESCENT LUMINAIRES:
 RECESSED INCANDESCENT LUMINAIRES SHALL HAVE THERMAL
 PROTECTION AND SHALL BE LISTED AS THERMALLY PROTECTED.
 5. FBC-RE3905.8 NEC 314.27(D) PADDLE FANS. BOXES USED
 FOR THE SOLE SUPPORT OF CEILING FANS SHALL BE MARKED BY
 THE MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND
 INDICATE THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED
 TO SUPPORT PADDLE FANS HEAVIER THAN 70 LBS.
 6. FBC-RE3602.2/NEC 220.82 SERVICE LOAD: THE MINIMUM
 LOAD FOR UNGROUNDED SERVICE CONDUCTORS AND SERVICE
 DEVICES THAT SERVE 100 PERCENT OF THE DWELLING UNIT
 LOAD SHALL BE COMPUTED IN ACCORDANCE WITH TABLE
 E3602.2. UNGROUNDED SERVICE CONDUCTORS AND SERVICE
 DEVICES THAT SERVE LESS THAN 100 PERCENT OF THE
 DWELLING UNIT LOAD SHALL BE COMPUTED AS REQUIRED FOR
 FEEDERS IN ACCORDANCE WITH CHAPTER 37. PROVIDE A SITE
 SPECIFIC AND LEGIBLE LOAD CALC. SUBMIT A SITE SPECIFIC
 RISER DIAGRAM, INCLUDE CONDUCTOR TYPES AND SIZING.
 7. FBC-R3706.2 NEC 408.4(A) REQUIRES THAT YOU PROVIDE A
 PANEL SCHEDULE OR CIRCUIT DIRECTORY LEGIBLY INDICATING
 THE SPECIFIC PURPOSE OF EVERY CIRCUIT. PROVIDE A SITE
 SPECIFIC CIRCUIT DIRECTORY FOR EVERY PANEL
 8. SHOW ON THE ELECTRICAL PLAN THE LOCATION OF ALL HVAC
 EQUIPMENT AND THE REQUIRED SERVICE OUTLET.
 9. FBC-ER404.1: A MINIMUM OF 75% OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75% OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICIENCY LAMPS.
  
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-21 Cont ID  
Sent By gjohnson Date 2016-10-21 Time 18:25 Rev Time 0.00
Received By rmcdouga Date 2016-09-09 Time 10:39 Sent To  
Notes
2016-09-12 10:40:05R02

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-10-21 Cont ID  
Sent By rmcdouga Date 2016-10-21 Time 11:48 Rev Time 0.00
Received By rmcdouga Date 2016-10-21 Time 11:48 Sent To  
Notes
2016-10-21 11:48:46BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-10-20 Cont ID  
Sent By hmoser Date 2016-10-20 Time 10:53 Rev Time 0.00
Received By hmoser Date 2016-10-20 Time 09:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-10-12 Cont ID  
Sent By gjohnson Date 2016-10-12 Time 08:27 Rev Time 0.00
Received By gjohnson Date 2016-10-11 Time 11:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-09-26 Cont ID  
Sent By njwira Date 2016-09-26 Time 16:25 Rev Time 0.00
Received By njwira Date 2016-09-23 Time 16:03 Sent To  
Notes
2016-09-26 16:28:019/23/16- FAILED
  
 SF-7 SINGLE FAMILY LOW DENSITY RESIDENTIAL
  
 FAILED
 1. PLEASE PROVIDE TWO(2)COPIES OF A SURVEY SHOWING
 WHERE THE BUILDING WITH ADDITIONS WILL BE LOCATED IN
 RELATION TO THE REQUIRED SETBACKS.
 2. PLEASE INDICATE WHERE THE ADDITIONS WILL BE LOCATED
 IN RELATION TO WHAT IS CURRENTLY THERE.
  
 PASSED
 1. BUILDING MEETS HEIGHT LIMIT OF 30FT.
 2. ONE KITCHEN MAKES THIS ONE UNIT.
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  