| 2016-09-09 08:12:55 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16090263 |
| | ADD: 1731 UPLAND RD. |
| | CONT: ROOFPRO |
| | TEL: 561-249-0247 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SEPT. 09/2016 |
| | ACTION: DENIED |
| | |
| | 1) THE PRODUCT APPROVAL SUBMITTED FL654-R19 A TRINTY |
| | /ERD EVALUATION REPORT WAS SUBMITTED, SHEET 26 OF 45 |
| | WAS SELECTED AND SYSTEM SC-26 WAS HIGHLIGHTED WITH |
| | HIGHLIGHTED RECTANGLE WITH A -52.5 POUNDS PER SQUARE |
| | FOOT. PAGE 4 OF 5 LIMITATIONS SECTION 5.7 DOES ALLOW |
| | FOR ENHANCED FASTENING BY A QUALIFIED DESIGN |
| | PROFESSIONAL, COMMON METHODS USED ARE RAS 117 AND |
| | FMLPDS 1-29. |
| | 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE |
| | CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND |
| | DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, |
| | FASTENING |
| | REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE |
| | RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT |
| | EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE |
| | WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE |
| | OR A STATEMENT BY AN ARCHITECT OR ENGINEER FOR THE |
| | SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |