Plan Review Details - Permit 16090195
Plan Review Stops For Permit 16090195
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-11-29 Cont ID  
Sent By jwitmer Date 2016-11-29 Time 12:40 Rev Time 0.00
Received By jwitmer Date 2016-11-29 Time 11:33 Sent To  
Notes
2016-11-29 12:40:28EXCEPT FOR IMPACT FEES THE PERMIT SUBMITTED IS READY
 FOR ISSUANCE,
 FEE BALANCE LISTED BELOW CAN BE PAID AT TIME OF PERMIT
 ISSUANCE:
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-10-31 Cont ID  
Sent By jwitmer Date 2016-10-31 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2016-10-29 Time 14:16 Sent To  
Notes
2016-10-31 07:32:47BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16090195
 ADD: 5300 EAST AVE.
 CONT: TRILLIUM CONSTRUCTION
 TEL: 561-296-0700
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. OCT. 31/2016
 ACTION: DENIED
  
 1-4) COMPLIED.
  
 5) 2ND REQUEST. SEMI-COMPLIED. SHEET A-8 DOES PROVIDE
 THE VASD PRESSURES FOR THE NEW DOOR OPENINGS.
 WHAT IS STILL MISSING IS THE ACTUAL WIND DESIGN
 CRITERIA. IT LOOKS LIKE THE PRESSURES ARE FOR AN B
 EXPOSURE FOR 50 SQUARE FEET OPENING OF BY +6.3.PSF AND
 -3.24 PSF.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 5.2. RISK CATEGORY.
  
 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 1ST ROUND OF COMMENTS. SHEET A1 ROOMS 111-115 SHOW THE
 INSTALLATION OF NEW EXTERIOR DOORS, SHEET SHOWS DETAILS
 FOR THE NEW STOREFRONT SYSTEM BUT I COULD NOT FIND
 WHERE THE 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 6) SEMI-COMPLIED. THIS REVIEW (1) PRODUCT APPROVAL FOR
 EXTERIOR DOORS WAS SUBMITTED TRULITE (NOA 14-0225.02)
 AND (1) TRULITE STOREFRONT WINDOW WALL SYSTEM
 NOA(14-0203.01.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.1 REQUIRES A MINIMUM OF 2 PRODUCT
 APPROVALS TO BE SUBMITTED.
  
 1ST ROUND OF COMMENTS. PLEASE NOTE A SERIES 35H YKK AP
 AMERICA OUTSWING ENTRANCE DOORS TECHNICAL SHEETS WERE
 SUBMITTED, THEY DO NOT HAVE ANY INDICATION IF THEY ARE
 A FLORIDA APPROVAL OR A MIAMI-DADE NOA. 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7A) NEW COMMENT. TRULITE NOA 14-0225.02 SEE PAGE 4 OF
 11 OVER HANG REQUIREMENTS FOR WATER INFILTRATION ARE
 NOT MET SEE 1710.5.1 EXCEP. # 2 .
  
 7B) NEW COMMENT. TRULITE NOA 14-0225.02 SEE PAGE 4 OF
 11, FOR AN ACCESSIBLE THRESHOLD(ADA-ACCESSIBLE) THE
 THRESHOLD TO BE INSTALLED AND COMPLIANCE WITH WATER
 INFILTRATION THE 1/2 INCH THRESHOLD IS LIMITED TO LESS
 OR EQUAL TO +33.3 PSF PRESSURE.
  
 8)COMPLIED. MICROWAVE.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-09-20 Cont ID  
Sent By jwitmer Date 2016-09-20 Time 09:46 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2016-09-20 09:45:43BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16090195
 ADD: 5300 EAST AVE.
 CONT: TRILLIUM CONSTRUCTION
 TEL: 561-296-0700
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. SEPT. 20/2016
 ACTION: DENIED
  
 1) SHEET LS1 VERSES SHEET A1. LS 1 IN THE 200 & 300 1-2
 SLEEPING ROOM CARE SUITES THE PLANS SHOW A SMOKE RATED
 WALL BETWEEN THE CORRIDOR AND SLEEPING ROOMS. SHEET A1
 DOES NOT DEPICT THIS ON THE FLOOR PLAN DISCREPANCY IN
 PLANS, 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
 CORRIDOR WALLS ARE TO BE CONSTRUCTED AS SMOKE
 PARTITIONS IN ACCORDANCE WITH 2014 FBC-B 710.4
 CONTINUITY.
  
 2) THE FLOOR PLAN SHEET LS1 AND SHEET A1. NEITHER SHOW
 SMOKE RATED WALLS FOR ROOMS 008 SOILED LINEN AND 009
 CENTRAL SUPPLY ROOM. THE ROOM FINISH SCHEDULE ON SHEET
 A1 INDICATES UNDER REMARKS: 0.060 INCH THICK WALL
 PROTECTION. FBC-B 509.4.2 PROTECTION. WHERE TABLE 509
 PERMITS AN AUTOMATIC SPRINKLER SYSTEM WITHOUT A FIRE
 BARRIER, THE INCIDENTAL USES SHALL BE SEPARATED FROM
 THE REMAINDER OF THE BUILDING BY CONSTRUCTION CAPABLE
 OF RESISTING THE PASSAGE OF SMOKE. DOORS SHALL BE SELF-
 OR AUTOMATIC-CLOSING UPON DETECTION OF SMOKE IN
 ACCORDANCE WITH SECTION 716.5.9.3.
  
 3) SHEET A1 UNDER THE HEADING OF ROOM FINISH SCHEDULE
 INDICATES ROOMS 218 & 318 AS WHEELCHAIR STORAGE BUT I
 DID NOT FIND THESE ROOMS IN THE 1-2 SUITE OF ROOMS.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) SHEET A1 SHOWS THE ELEVATOR BEING ELIMINATED, PLEASE
 PROVIDE HOW WILL COMPLIANCE WITH 201.1.1 ACCESS. CODE
 VERTICAL ACCESSIBILITY BE ACHIEVED?
  
 5) SHEET A1 ROOMS 111-115 SHOW THE INSTALLATION OF NEW
 EXTERIOR DOORS, SHEET SHOWS DETAILS FOR THE NEW
 STOREFRONT SYSTEM BUT I COULD NOT FIND WHERE THE 2014
 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 6) PLEASE NOTE A SERIES 35H YKK AP AMERICA OUTSWING
 ENTRANCE DOORS TECHNICAL SHEETS WERE SUBMITTED, THEY DO
 NOT HAVE ANY INDICATION IF THEY ARE A FLORIDA APPROVAL
 OR A MIAMI-DADE NOA. 2014 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) THE SERIES 35H YKK AP AMERICA OUTSWING ENTRANCE
 DOORS ARE FOR DOUBLE DOORS ONLY NOT FOR SIDE LIGHTS AS
 DEPICTED ON SHEET A8 DETAIL F2. 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1. FBC 107.3.4.1
 PRODUCT APPROVALS. COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31(C) PANEL WALLS: STOREFRONTS,
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8)SHEET A6 DETAIL B INDICATES A MICROWAVE SITTING ON A
 SHELF AT AN ELEVATION OF 4 FOOT 6 INCHES WHICH IS
 LOCATED ABOVE THE REACH RANGES. SEE 2014 FBC-ACCESS.
 CODE 308.2 FORWARD REACH , 308.3 SIDE REACH AND 309.3
 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE OR
 MORE OF THE REACH RANGES SPECIFIED IN 308.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-10-27 Cont ID  
Sent By albarran Date 2016-10-27 Time 21:49 Rev Time 0.00
Received By albarran Date 2016-10-27 Time 21:28 Sent To  
Notes
2016-10-27 21:50:45APPROVED ELECTRICAL REVIEW BUT MADE MENTION VIA A NOTE
 ON PAGE E2 FOR THE INSPECTOR TO VERIFY COMPLIANCE WITH
 AUTOMATIC RECEPTACLE CONTROL REQUIREMENTS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-09-15 Cont ID  
Sent By albarran Date 2016-09-15 Time 12:07 Rev Time 0.00
Received By albarran Date 2016-09-15 Time 10:27 Sent To  
Notes
2016-09-15 12:07:46ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC)
  
 PROJECT NAME: PATIENT WING IMPROVEMENTS
 JOB ADDRESS: 5300 EAST AVE.
 DESCRIPTION: INTERIOR IMPROVEMENTS TO PATIENT ROOMS &
 UPGRADES TO VARIOUS CORRIDORS & OTHER AREAS
 MASTER PERMIT: 16090195
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 SHEET E2
 1. PANTRY 027- NEC 210.8: GFI PROTECTION REQUIRED FOR
 OUTLETS ON KITCHEN COUNTER.
 2. EXISTING RESIDENT ROOMS, EXISTING PANTRIES 217 &
 317, AND MED 011- NEC 210.8: GFI PROTECTION REQUIRED
 FOR OUTLETS WITHIN 6 FT. OF SINK.
 3. FBC-E 405.7.1: AT THE LEAST 50% OF ALL 125-VOLT, 15-
 AND 20-AMPERE RECEPTACLES SHALL BE AUTOMATICALLY
 CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN
 OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE
 INSTALLED IN MODULAR PARTITIONS. (SEE ASHRAE STANDARD
 90.1)
 SHEET E3
 1. EXIST COUNSEL 309, EXIST CORR. 024-THERE APPEARS TO
 BE A MISPLACED OR INCORRECTLY LABELED EXIT LIGHT
 2. FBC-EC405.2.2.3 DAYLIGHT ZONE CONTROL: DAYLIGHT
 ZONES SHALL BE DESIGNED SUCH THAT LIGHTS IN THE
 DAYLIGHT ZONE ARE CONTROLLED INDEPENDENTLY OF GENERAL
 AREA LIGHTING AND ARE CONTROLLED IN ACCORDANCE WITH
 EITHER SECTION C405.2.2.3.1 OR SECTION C405.2.2.3.2.
 THERE DOES NOT APPEAR TO BE DAYLIGHT ZONIFICATION.
 SHEET E5
 1. PANEL LD CIRCUIT 35 FOR THE EWC SHALL BE GFI
 PROTECTED AT EITHER THE PANEL OR AT THE RECEPTACLE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-10-28 Cont ID  
Sent By pleduc Date 2016-10-28 Time   Rev Time 0.00
Received By pleduc Date 2016-10-28 Time 10:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-09-16 Cont ID  
Sent By wjolin Date 2016-09-16 Time 17:32 Rev Time 0.00
Received By wjolin Date 2016-09-16 Time 13:57 Sent To  
Notes
2016-09-16 17:32:155300 EAST AVENUE
 PERMIT #16090195
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLANS INDICATE SEVERAL FIRE RATED DOORS THROUGHOUT TO
 BE REPLACED BY DIRECT OWNER BUY. NOTE STATES "CONFIRM
 ALL DOORS IN RATED WALLS TO COMPLY WITH NFPA
 REQUIREMENTS." WHO IS RESPONSIBLE FOR CONFIRMING AND
 ENSURING THE PROPER FIRE RATED DOORS AND HARDWARE ARE
 BEING INSTALLED?
  
 HOW WILL THE CONSTRUCTION AREA BE SEPARATED FROM THE
 REST OF THE FACILITY? HOW WILL THE CONSTRUCTION ZONE
 AFFECT EGRESS FO THE EXISTING RESIDENTS AND STAFF?
  
 A COUPLE ROOMS ARE BEING MODIFIED AND MOST CEILINGS
 INDICATE THEY ARE BEING DEMOLISHED AND REPLACED;
 HOWEVER, NO ENGINEERED FIRE ALARM OR FIRE SPRINKLER
 DRAWINGS HAVE BEEN SUBMITTED. SURELY THIS SCOPE OF WORK
 IS AFFECTING SMOKE DETECTORS, HORN-STROBE DEVICES AND
 THE SPRINKLER LOCATIONS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-11-29 Cont ID  
Sent By jwitmer Date 2016-11-29 Time 12:41 Rev Time 0.00
Received By jwitmer Date 2016-11-16 Time 13:34 Sent To  
Notes
2016-11-17 13:34:40RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-04 Cont ID  
Sent By gjohnson Date 2016-11-04 Time 12:46 Rev Time 0.00
Received By gjohnson Date 2016-10-25 Time 10:53 Sent To  
Notes
2016-10-26 10:53:52C10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-20 Cont ID  
Sent By jwitmer Date 2016-09-20 Time 09:46 Rev Time 0.00
Received By jwitmer Date 2016-09-07 Time 11:46 Sent To  
Notes
2016-09-08 11:47:05C09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2016-11-30 Cont ID  
Sent By jwitmer Date 2016-11-30 Time 10:48 Rev Time 0.00
Received By jwitmer Date 2016-11-30 Time 10:47 Sent To  
Notes
2016-11-30 10:49:15PLANS SUBMITTED TO P.B.C. IMPACT FEE OFFICE
 (11/30/2016), STAMPED NO FEES DUE. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-11-29 Cont ID  
Sent By jwitmer Date 2016-11-29 Time 12:29 Rev Time 0.00
Received By jwitmer Date 2016-11-29 Time 12:29 Sent To  
Notes
2016-11-29 12:30:12IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-09-20 Cont ID  
Sent By jwitmer Date 2016-09-20 Time 09:46 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-11-18 Cont ID  
Sent By ccole Date 2016-11-18 Time 10:25 Rev Time 0.00
Received By ccole Date 2016-11-18 Time 10:25 Sent To  
Notes
2016-11-18 10:32:47MECHANICAL PROVISOS
 11/18/16
  
 A REVISION TO THE PLANS IS REQUIRED TO PROVIDE SMOKE
 DAMPERS FOR ALL DUCTS PENETRATING THE NEW CENTRAL
 SUPPLY AND SOILED HOLDING ROOM WALLS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-10-31 Cont ID  
Sent By ccole Date 2016-10-31 Time 14:02 Rev Time 0.00
Received By ccole Date 2016-10-31 Time 14:02 Sent To  
Notes
2016-10-31 14:02:402ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16090886
 10/31/2016
  
 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS: THE NEW
 SOIL HOLDING ROOM 008 MUST BE UNDER NEGATIVE PRESSURE
 WITH ALL AIR EXHAUSTED TO THE OUTDOORS PER TABLE 7-1
 ASHRAE 170-2008. PLEASE REVISE THE PLANS TO SHOW THE
 REQUIORED SYSTEM, AND PROVIDE THE ACH RATES FOR THE
 ROOM AND ALL OTHER NEW ROOMS CONSTRUCTED UNDER THIS
 PERMIT INCLUDING THE CENTRAL SUPPLY-009, THE MEDICAL
 SUPPLY-011, AND THE NURSE'S STATION-012.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-09-12 Cont ID  
Sent By ccole Date 2016-09-12 Time 16:05 Rev Time 0.00
Received By ccole Date 2016-09-12 Time 16:05 Sent To  
Notes
2016-09-12 16:20:231ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #16090195
 9/12/16
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS AND RATES
 FOR ALL ROOMS AND SPACES UNDERGOING RENOVATIONS-
 SEETABLE 403.3 FBC-14 MECHANICAL, TABLE 6-4 ASHRAE
 62.1-2010, AND TABLE 7-1 ASHRAE STANDARD 170- 2008.
 PLEASE NOTE THAT PER THE ASHRAE STANDARSDS, NEGATIVE
 PRESSURE (EXHAUST) IS REQUIRED FOR THE
 SOILED HOLDING ROOMS AND SOILED WORKROOMS.
  
 2) SHOW THE LOCATIONS OF RETURN GRILLS IN THE FAMILY
 SUPPORT ROOMS, AND NURSE STATIONS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2016-09-19 Cont ID  
Sent By jwitmer Date 2016-09-19 Time 16:28 Rev Time 0.00
Received By jwitmer Date 2016-09-19 Time 16:28 Sent To  
Notes
2016-09-19 16:28:32FLOOD ZONE AH / IMPROVEMENT VALUE OF$11,379,041.00 DOES
 NOT MEET
 SUBSTANTIAL IMPROVEMENT ONLY $2,623,548.00 DOLLARS IN
 VALUE WITH THE
 PRESENT PERMIT VALUE OF $1,521,548.00. JW

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-11-04 Cont ID  
Sent By gjohnson Date 2016-11-04 Time 12:46 Rev Time 0.00
Received By gjohnson Date 2016-11-04 Time 10:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-09-19 Cont ID  
Sent By tklarge Date 2016-09-19 Time 05:26 Rev Time 0.00
Received By tklarge Date 2016-09-19 Time 04:07 Sent To  
Notes
2016-09-19 05:14:351) SHT. A-6 - SHOW THE LENGTH AND WIDTH DIMENSIONS OF
 THE NEW TOILET ROOM. A MINIMUM WIDTH OF 85 INCHES IS
 REQUIRED IF BUILT PERFECT. 86 INCHES ALLOWS FOR
 TOLERANCE.
 2) SHT. P-1 SHOWS AIR CHAMBERS ON THE WATER PIPING. AIR
 CHAMBERS ARE NOT PERMITTED.A WATER HAMMER ARRESTOR
 SHALL BE INSTALLED WHERE QUICK-CLOSING VALVES ARE
 UTILIZED. WATER HAMMER ARRESTORS SHALL CONFORM TO ASSE
 1010. FPC SEC.604.9.
 3) SHT. PD-1 - PLANS SHOW THE REMOVAL OF THE DRINKING
 FOUNTAINS IN FAMILY SUPPORT ROOMS # 216 & 316. THIS
 APPEARS TO CREATE A PLUMBING CODE VIOLATION AS DRINKING
 FOUNTAINS ARE REQUIRED. WHERE WILL THESE FOUNTAINS BE
 RELOCATED OR ADDED? CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  