Plan Review Details - Permit 16090150
Plan Review Stops For Permit 16090150
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-10-05 Cont ID  
Sent By shill Date 2016-10-05 Time 13:36 Rev Time 0.00
Received By shill Date 2016-10-05 Time 13:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-09-12 Cont ID  
Sent By shill Date 2016-09-12 Time 12:31 Rev Time 0.00
Received By shill Date 2016-09-12 Time 12:31 Sent To  
Notes
2016-09-12 12:32:15****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A MEANS OF EGRESS DOOR FOR WORKROOM 109, FBC
 1014.2(1).
  
 2. SHEET A2.3 DETAIL B2, CONSTRUCTION AND COMPLIANCE
 FOR THE UL DETAIL IS NOT CLEAR. THE WALL IS OFFSET;
 STRUCTURAL SUPPORT OF THE WALL AS DRAWN IS NOT CLEAR.
 CONFIRM WITH U.L. THAT THIS WALL DETAIL CAN BE USED IN
 A HORIZONTAL (CEILING) APPLICATION. CONFIRM WITH U.L.
 THAT THE WALL CAN BE CONSTRUCTED IN AN OFFSET MANNER
 AND MAINTAIN THE REQUIRED RATING.
  
 COMPLETE THE DETAIL BY EITHER PROVIDING THE OPTION
 SELECTED OR ALL OF THE OPTIONS, FBC 107.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-10-11 Cont ID  
Sent By vperez Date 2016-10-11 Time 11:13 Rev Time 0.00
Received By vperez Date 2016-10-11 Time 11:13 Sent To  
Notes
2016-10-11 11:15:14PROVISO- SUBMIT A NEW SHEET E2, INK IS FADING AWAY
  
 VAL PEREZ
 *6717

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-09-15 Cont ID  
Sent By vperez Date 2016-09-15 Time 09:31 Rev Time 0.00
Received By vperez Date 2016-09-15 Time 09:31 Sent To  
Notes
2016-09-15 09:37:55PLEASE NOTE THAT THE QUALITY OF PLANS SHEETS ARE FADING
 DUE TO INK DEFICIENCY, MAKING IT NON-LIGIBLE. REPRINT
 AND SUBMIT NEW. SEE PLANS.
  
 PROVIDE PER NEC 702.7-SIGNS- A GENERAL NOTE ON RISER
 DIAGRAM TO INDICATE SINAGE REQUIREMENTS FOR THE
 OPTIONAL STANDY SYSTEM.
  
 ADDRESS MECHANICAL COMMENT REGARDING EX FAN STORAGE
 ROOM
  
 UPGRADED 200A NOW SHOWN FOR UNTT 120, SHOWS A THE
 NEUTRAL CONDUCTOR REDUCTION IN SIZE. EITHER PROVIDE
 NEUTRAL CALCULATION OR SHOW AT THE SAME SIZE OF
 UNGROUNDED CONDUCTORS. NEC 220.61
 ALSO THE UPGRADE TO UNIT IMPACTS THE EXISTING SERVICE
 SIZE SHOWN AT 800AMPS. BY INCREASING LOADS PLEASE
 PROVIDE A REVISED CALCULATION OF SERVICE TO VERIFY THAT
 THE EXISTING SERVICE WILL HANDLE THE INCREASE TO 200AMP
 SERVICE. FBC 107.3.5
  
  
 VAL PEREZ
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-10-17 Cont ID  
Sent By pleduc Date 2016-10-17 Time   Rev Time 0.00
Received By pleduc Date 2016-10-17 Time 14:42 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-09-16 Cont ID  
Sent By pleduc Date 2016-09-16 Time   Rev Time 0.00
Received By pleduc Date 2016-09-16 Time 09:34 Sent To  
Notes
2016-09-16 09:56:11THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE APPEARS TO BE A/C DUCT WORK PASSING TROUGH
 FIRE RATED WALLS.
  
 PER THE FLORIDA FIRE PREVENTION CODE NFPA 1 AND 101,
 5TH EDITION:
  
 CHAPTER 8 FEATURES OF FIRE PROTECTION
  
 8.3.5.7 OPENINGS FOR AIR-HANDLING DUCTWORK. OPENINGS IN
 FIRE BARRIERS FOR AIR-HANDLING DUCTWORK OR AIR MOVEMENT
 SHALL BE PROTECTED IN ACCORDANCE WITH 9.2.1.
  
 8.5.5.5 ACCESS AND IDENTIFICATION. ACCESS TO THE
 DAMPERS SHALL BE PROVIDED FOR INSPECTION, TESTING, AND
 MAINTENANCE. THE ACCESS OPENINGS SHALL NOT REDUCE THE
 FIRE RESISTANCE RATING OF THE FIRE BARRIER ASSEMBLY.
  
 9.2 HEATING, VENTILATING, AND AIR-CONDITIONING.
  
 9.2.1 AIR-CONDITIONING, HEATING, VENTILATING DUCTWORK,
 AND RELATED EQUIPMENT. AIR-CONDITIONING, HEATING,
 VENTILATING DUCTWORK, AND RELATED EQUIPMENT SHALL BE IN
 ACCORDANCE WITH NFPA 90A, STANDARD FOR THE INSTALLATION
 OF AIR-CONDITIONING AND
 VENTILATING SYSTEMS, OR NFPA 90B, STANDARD FOR THE
 INSTALLATION OF WARM AIR HEATING AND AIR-CONDITIONING
 SYSTEMS, AS APPLICABLE, UNLESS SUCH INSTALLATIONS ARE
 APPROVED EXISTING INSTALLATIONS, WHICH SHALL BE
 PERMITTED TO BE CONTINUED IN SERVICE.
  
  
  
 2) ENSURE THE FIRE RATED WALL IS IDENTIFIED AS
 REQUIRED.
  
 8.3.2.4 EACH NEW FIRE WALL, FIRE BARRIER, FIRE
 PARTITION, SMOKE BARRIER, SMOKE PARTITION, OR ANY OTHER
 NEW WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES WITH THE
 WORDING, ?FIRE AND SMOKE BARRIER ? PROTECT ALL
 OPENINGS,? OR SIMILAR LANGUAGE. SUCH SIGNS OR
 STENCILING SHALL BE IN 4 INCH HIGH LETTERS, ? INCH
 STROKE, AND NOT MORE THAN 15 FEET ON-CENTER.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-17 Cont ID  
Sent By pleduc Date 2016-10-17 Time   Rev Time 0.00
Received By pleduc Date 2016-09-30 Time 11:37 Sent To  
Notes
2016-10-03 11:37:42B07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-30 Cont ID  
Sent By tklarge Date 2016-09-30 Time 12:36 Rev Time 0.00
Received By tklarge Date 2016-09-07 Time 13:22 Sent To  
Notes
2016-09-07 13:22:21B07

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-10-11 Cont ID  
Sent By ccole Date 2016-10-11 Time 09:10 Rev Time 0.00
Received By ccole Date 2016-10-11 Time 07:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-09-12 Cont ID  
Sent By ccole Date 2016-09-12 Time 12:12 Rev Time 0.00
Received By ccole Date 2016-09-12 Time 12:12 Sent To  
Notes
2016-09-12 14:13:061ST REVIEW FBC-2014 MECHANICAL
 PERMIT REVISION #16090150
 9/12/16
  
 1) FIRE DAMPERS MISSING FOR THE RETURN AIR DUCTS
 PENETRATING THE FIRE-RATED CONTROL ROOM WALLS.
  
 2) THE REVISED DRAWING SHOWS THE EF-1 REMOVED FROM THE
 CHEMICAL STORAGE CLOSET. THIS IS A REQUIRED EXHAUST FAN
 PER THE APPROVED PLANS.
  
 2) CLARIFY THE PURPOSE OF THE NEW CLOSET 110. IS THIS
 ALSO A CHEMICAL STORAGE CLOSET? PLEASE NOTE THAT RETURN
 AIR FROM A CLOSET IS PROHIBITED- SEE SECTION 918.6.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-10-03 Cont ID  
Sent By gjohnson Date 2016-10-03 Time 13:15 Rev Time 0.00
Received By gjohnson Date 2016-10-03 Time 13:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-09-30 Cont ID  
Sent By gjohnson Date 2016-09-30 Time 12:35 Rev Time 0.00
Received By tklarge Date 2016-09-30 Time 12:34 Sent To  
Notes
2016-09-30 12:35:46PLUMBING FAILED AT CUSTOMER'S REQUEST IN ORDER TO
 RESUBMIT CORRECTIONS. WILL REVIEW PLUMBING ON
 RESUBMITTAL.