Plan Review Details - Permit 16090104
Plan Review Stops For Permit 16090104
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-02-08 Cont ID  
Sent By jgomez Date 2017-02-08 Time 15:51 Rev Time 0.00
Received By jgomez Date 2017-02-08 Time 15:02 Sent To  
Notes
2017-02-06 17:28:42BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- THERE IS NO PERMIT FOR THE REAR WOOD DECK. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE REAR WOOD DECK UNDER A SEPARATE
 PERMIT.
 2- PROVIDE PRODUCT APPROVAL FOR METAL ROOF AS SPECIFIED
 ON PLANS.
 3- DESIGNER OF RECORD TO APPROVE IN WRITING ALL PRODUCT
 APPROVALS.
 4- PROVIDE A/C PLAN AND COMPLETE EQUIPMENT SIZING
 CALCULATIONS UNDER A SEPARATE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-10-03 Cont ID  
Sent By jgomez Date 2016-10-03 Time 18:32 Rev Time 0.00
Received By jgomez Date 2016-10-03 Time 18:16 Sent To  
Notes
2016-10-03 18:35:15RESIDENTIAL (R3) CONVERSION OF GARAGE/UTILITY BUILDING
 TO CABANA, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- ACCORDING TO PLANS SUBMITTED THE PROPOSED CABANA IS
 GOING TO BE RAISED TO THE LEVEL OF THE WOOD DECK.
 ACCORDING TO CITY RECORDS IT LOOKS LIKE THERE IS NOT
 PERMIT FOR THE CONSTRUCTION OF THE WOOD DECK. WOOD DECK
 MAY HAVE BEING BUILT WITHOUT A PERMIT. NEED TO OBTAIN A
 PERMIT FOR THE CONSTRUCTION OF THE WOOD DECK AS
 REQUIRED BY SEC. 105.1 CITY AMENDMENTS. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE WOOD DECK TO SHOW COMPLIANCE WITH
 SEC. R301.31 FBC-RESIDENTIAL, 5TH EDITION (2014). NOTE:
 ACCORDING TO PLANS SUBMITTED HANDRAILS ARE REQUIRED
 SEC. R311.7.8 BC-RESIDENTIAL. AND GUARDRAILS MAY BE
 REQUIRED. PLANS FOR THE WOOD DECK CONSTRUCTION TO SHOW
 THE HEIGHT OF THE WOOD DECK ABOVE THE FINISH GRADE.
 SEC. R312.1 FBC-RESIDENTIAL TO VERIFY GUARDRAIL
 REQUIREMENTS..
  
 NOTE: IF SUBMITTING THE WOOD DECK STRUCTURAL FRAMING
 DETAILS AND SPECIFICATIONS UNDER THIS PERMIT, THEN
 UPDATE THE VALUATION DECLARED IN THE PERMIT APPLICATION
 TO INCLUDE THE DECK. OTHERWISE, PROVIDE COMPLETE
 INFORMATION UNDER A SEPARATE PERMIT. PLEASE ADVICE
 WHICH ACTION IS GOING TO TAKE PLACE.
  
 3- THIS STRUCTURE WAS BUILT AROUND 1925. IT LOOKS LIKE
 IT WAS INTENDED FOR GARAGE/STORAGE. PROPOSED USE IS FOR
 HUMAN OCCUPANCY. PROVIDE STRUCTURAL EVALUATION AS
 REQUIRED BY SEC. 1205.2 FBC-EXISTING BUILDING. SHOW HOW
 THE EXISTING STRUCTURE IS REINFORCED TO MEET THE
 CURRENT CODE FOR THE PROPOSED CHANGE OF OCCUPANCY.
  
 4- STEM WALL/FLOOR JOIST SECTION SUBMITTED: THIS
 SECTION IS MISSING ALL THE STRUCTURAL INFORMATION
 SHOWING THE CONTINUOUS LOAD PATH FROM THE ROOF TO THE
 FOUNDATION. PROVIDE COMPLETE INFORMATION SHOWING ALL
 THE STRUCTURAL CONNECTORS. SEC. R301.1 FBC-RESIDENTIAL.
  
 5- PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE WITH
 THE UNDER FLOOR SPACE VENTILATION AND UNDER FLOOR SPACE
 ACCESS AS REQUIRED BY SEC. R408 FBC-RESIDENTIAL.
 SPECIFY ALL OPENINGS SIZES AND LOCATION.
  
 6- RECESSED WALL SECTION DETAIL IS NOT CLEAR. CLEARLY
 SPECIFY ALL FRAMING MEMBERS AND CONNECTORS. SEC. R301.1
 FBC-RESIDENTIAL. PROVIDE CLEAR DRAWINGS SHOWING ALL
 VERTICAL AND HORIZONTAL FRAMING MEMBERS AND STRUCTURAL
 CONNECTORS. NOTE: SIZE OF T & G VERTICAL MEMBERS
 SPECIFIED ON THE RECESSED WALL SECTION DON'T MATCH SIZE
 SPECIFIED ON THE FRONT ELEVATION.
  
 7- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE NEW DOORS AN WINDOWS. SPECIFY ALL FRAMING
 MEMBERS AND CONNECTORS. SEC. R301.1 FBC-RESIDENTIAL.
  
 8- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A)METAL ROOF AS SPECIFIED ON STEM WALL/FLOOR JOIST
 SECTION SUBMITTED.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 DESIGNER OF RECORD TO LIST THE FLORIDA PRODUCT APPROVAL
 NEXT TO EACH SPECIFIED CONNECTOR.
  
 9- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 10- PROVIDE COMPLETE SPECIFICATIONS SHOWING COMPLIANCE
 WITH THE HEATING REQUIREMENTS OF SEC. R303.9
 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-02-02 Cont ID  
Sent By mvaldes Date 2017-02-02 Time 10:33 Rev Time 0.00
Received By mvaldes Date 2017-02-02 Time 09:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-09-07 Cont ID  
Sent By mvaldes Date 2016-09-07 Time 15:26 Rev Time 0.00
Received By mvaldes Date 2016-09-07 Time 14:41 Sent To  
Notes
2016-09-07 15:34:41REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] PROVIDE ELECTRIC SERVICE RISER WITH WIRE SIZES,
 CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE LOAD
 CALCULATIONS, PANEL SCHEDULES AND SHOW MATCHING
 CIRCUITS ON FLOOR PLAN.FBC- 107.3.5.3
  
 2] ALL RECEPTACLE OUTLETS IN THE LAUNDRY ROOM SHALL BE
 GFCI PROTECTED. NEC 210.8(A)
  
 3] ALL NEWLY INSTALLED RECEPTACLES SHALL BE
 TAMPER-RESISTANT IN ACCORDANCE WITH NEC 406.12

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2017-02-13 Cont ID  
Sent By fmittner Date 2017-02-13 Time 14:52 Rev Time 0.00
Received By fmittner Date 2017-02-13 Time 14:52 Sent To  
Notes
2017-02-06 17:54:37NEED RE-STAMP. REVISED DRAWINGS SUBMITTED. JG.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2016-09-21 Cont ID  
Sent By fmittner Date 2016-09-21 Time 08:31 Rev Time 0.00
Received By fmittner Date 2016-09-21 Time 08:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-15 Cont ID  
Sent By gjohnson Date 2017-02-15 Time 17:41 Rev Time 0.00
Received By gjohnson Date 2017-01-30 Time 16:50 Sent To  
Notes
2017-01-30 16:50:53R02

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-03 Cont ID  
Sent By jgomez Date 2016-10-03 Time 18:37 Rev Time 0.00
Received By jgomez Date 2016-09-06 Time 12:59 Sent To  
Notes
2016-09-06 12:59:22R08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-02-06 Cont ID  
Sent By jgomez Date 2017-02-06 Time 17:40 Rev Time 0.00
Received By jgomez Date 2017-02-06 Time 17:40 Sent To  
Notes
2017-02-06 17:42:22NO FEES DUE. MU-2017-2260.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-10-03 Cont ID  
Sent By jgomez Date 2016-10-03 Time 18:35 Rev Time 0.00
Received By jgomez Date 2016-10-03 Time 18:35 Sent To  
Notes
2016-10-03 18:35:481- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-02-15 Cont ID  
Sent By gjohnson Date 2017-02-15 Time 17:41 Rev Time 0.00
Received By gjohnson Date 2017-02-15 Time 17:41 Sent To  
Notes
2017-02-06 17:55:13NEED RE-STAMP. REVISED DRAWINGS SUBMITTED. JG

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-09-28 Cont ID  
Sent By gjohnson Date 2016-09-28 Time 13:48 Rev Time 0.00
Received By gjohnson Date 2016-09-28 Time 13:48 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2017-02-08 Cont ID  
Sent By jgomez Date 2017-02-08 Time 15:52 Rev Time 0.00
Received By jgomez Date 2017-02-08 Time 15:52 Sent To  
Notes
2017-02-08 15:52:37ROOFING REVIEW APPROVED WITH PROVISO:
  
  
 1- PROVIDE PRODUCT APPROVAL FOR METAL ROOF AS SPECIFIED
 ON PLANS.
 2- DESIGNER OF RECORD TO APPROVE IN WRITING ALL PRODUCT
 APPROVALS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-10-04 Cont ID  
Sent By jgomez Date 2016-10-04 Time 16:38 Rev Time 0.00
Received By jgomez Date 2016-10-04 Time 16:38 Sent To  
Notes
2016-10-04 16:39:011- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A)METAL ROOF AS SPECIFIED ON STEM WALL/FLOOR JOIST
 SECTION SUBMITTED.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2017-02-13 Cont ID  
Sent By fmittner Date 2017-02-13 Time 14:53 Rev Time 0.00
Received By fmittner Date 2017-02-13 Time 14:52 Sent To  
Notes
2017-02-06 17:54:53NEED RE-STAMP. REVISED DRAWINGS SUBMITTED. JG

Review Stop Z ZONING
Rev No 1 Status P Date 2016-09-21 Cont ID  
Sent By fmittner Date 2016-09-21 Time 08:31 Rev Time 0.00
Received By fmittner Date 2016-09-21 Time 08:31 Sent To  
Notes
***NONE***