| 2016-09-10 09:18:50 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16090054 |
| | ADD: 415 CLEMATIS ST. SUITE # 230 |
| | CONT: CUTTING EDGE BUILDING |
| | TEL: 561-625-4545 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. SEPT. 10/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A.01 THE FLOOR PLANS INDICATE (2) PASS THRU |
| | WINDOWS AND COUNTERS, THE DETAILS FOR BOTH WINDOWS |
| | INDICATE A SECTION A04/01-2. THERE IS NO SHEET 4 NOR IS |
| | THERE ON THE SHEET INDEX ON THE COVERSHEET. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | FBC-B SAFETY GLAZING 2406.1. |
| | FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF DINING |
| | SURFACES AND WORK SURFACES SHALL BE 28 INCHES (710 MM) |
| | MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 2)SHEET A.01. IN THE X-RAY ROOM THERE IS ALSO A WINDOW |
| | DETAIL WINDOW A-04/03/4. THERE IS NO SHEET 4 NOR IS |
| | THERE ON THE SHEET INDEX ON THE COVERSHEET. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | FBC-B 465 CONTROL OF RADIATION HAZARDS. |
| | |
| | 3) SHEET A.01 THERE IS NO INFORMATION AS TO SAFE GUARDS |
| | FOR RADIATION CONTROL FOR THE FLOOR, WALLS NOR THE |
| | FLOOR/ CEILING ABOVE. |
| | 465.5.1 SHIELDING. |
| | 465.6 DOORS, INTERLOCKS, AND WARNING SYSTEMS. |
| | 465.7 RADIATION MONITORING DEVICES. |
| | |
| | 4) IN REVIEWING SHEET A.01 THERE IS A NOTE ON THE PLANS |
| | INDICATING SEE THE DOOR SCHEDULE SHEET A-2 . NO SUCH |
| | SHEET ,NO DOOR SCHEDULE, NOT ABLE TO CHECK THE WIDTH OF |
| | DOORS, FBC-B 1008.1.1. DOOR # 1 IS EXISTING / |
| | RELOCATED, DOOR # 19 IS NEW PLEASE PROVIDE THE FIRE |
| | RATING FOR EACH DOOR AND HARDWARE AS WELL AS A COMPLETE |
| | SCHEDULE FOR THE REMAINDER OF THE DOORS. |
| | |
| | 5) SHEET A-03 THE RESTROOM ELEVATIONS SHOW THE WATER |
| | CLOSE GRAB BARS CENTER LINED AT 36 INCHES. PLEASE |
| | REVIEW THE 2014 FBC-ACCESS. CODE 609.4. THE HEIGHT OF |
| | THE GRAB BARS IS MEASURED FROM THE TOP OF THE GRASPING |
| | SURFACE NOT CENTERLINE. |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |