| 2016-09-12 08:59:29 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16081292/ PERMIT 16081296 TO BE |
| | VOIDED! |
| | ADD: 201 NARCISSUS ST. SUITE # 905/906 |
| | CONT: PHILIP E. JOHNSON, INC. |
| | TEL: 561-366-1034 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. SEPT. 12/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE 2 PERMITS WERE SUBMITTED FOR THE COMBINING OF |
| | SUITES 905 & 906. TO ACCOMPLISH THIS AN UNITY OF |
| | PROPERTY IS REQUIRED. PERMIT 16081296 WILL BE VOIDED |
| | AND THE FUNDS MOVED OVER TO PERMIT 16081292. |
| | UNITY OF TITLE. |
| | THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL |
| | BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM |
| | 'THE SITE'. A 'UNITY OF TITLE' SHALL BE RECORDED AT THE |
| | COUNTY COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY |
| | OF TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY LINE |
| | REQUIREMENTS MAY BE DEEMED NOT APPLICABLE. SEE WEBSITE |
| | FOR APPLICATION: |
| | HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP |
| | "APPLICATION FOR UNITY OF TITLE" |
| | HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45 |
| | -38-UNITYOFTITLE3.PDF |
| | VINCENT J NOEL |
| | SURVEYOR/REAL ESTATE SUPERVISOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33401 |
| | PHONE: 494-1040 EXT: 1096 |
| | FAX: 494-1116 |
| | E-MAIL: [email protected] |
| | ********************************************* |
| | MANUEL JULIAN GONZALEZ |
| | ENGINEERING PROJECT COORDINATOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 |
| | DIRECT: (561) 494-1085 |
| | FAX: (561) 494-1116 |
| | MOBILE: (561) 644-7301 |
| | EMAIL: [email protected] |
| | |
| | 2) THE FLOOR PLAN INDICATES THE USE OF ENGINEERED WOOD |
| | FLOORING THROUGH OUT THE UNIT AND THE USE OF MARBLE, |
| | TILE AND OR TRAVERTINE IN THE BATHROOMS. FOR BOTH TYPES |
| | OF FLOOR FINISHES (3) REPORTS WILL BE REQUIRED FOR THE |
| | ENGINEERED WOOD FLOORS AND 3 REPORTS FOR THE MARBLE, |
| | TILE AND OR TRAVERTINE PRODUCTS. |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2014) |
| | FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| | HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES |
| | TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| | LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| | CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 2C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |