Plan Review Details - Permit 16081247
Plan Review Stops For Permit 16081247
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-02-09 Cont ID  
Sent By cthroop Date 2017-02-09 Time 12:47 Rev Time 0.00
Received By cthroop Date 2017-02-09 Time 11:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-10-20 Cont ID  
Sent By cthroop Date 2016-10-20 Time 13:18 Rev Time 0.00
Received By cthroop Date 2016-10-20 Time 10:06 Sent To ENG
Notes
2016-10-20 14:16:41BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
 1. DESIGNER OF RECORD TO REVIEW, SIGN AND SEAL ALL
 SUBMITTAL DOCUMENTS.
 2. DESIGN SHALL COMPLY WITH THE PROVISIONS OF CHPT.
 1612, FLOOD HAZARD CONSTRUCTION.
 3. PROVIDE DESIGN WIND LOADS PER CHPT. 1603.
 4. PROVIDE ACCESS PER FBC ACCESSIBILITY.
 5. PROVIDE SITE PLAN TO DEMONSTRATE SEPERATION PER FBC
 424.4.
 6. PROVIDE PLAN VIEW OF ASSEMBLED EQUIPTMENT.
 7. PROVIDE FOUNDATION DETAILS PER FBC CHPT 18.
 8. PROVIDE MANUFATURER'S INSTALLATION INSTRUCTIONS FOR
 PLAY SURFACE.
  
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES& 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES& 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE
 SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS
 AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS
 TO BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL. ELECTRONIC MEDIA
 DOCUMENTS SHALL BE SUBMITTED WHEN REQUIRED BY THE
 BUILDING OFFICIAL, AND MAY REQUIRE ONLY ONE SET OF
 SUBMITTALS.
  
 SECTION 1612 FLOOD LOADS
 1612.1 GENERAL.
 WITHIN FLOOD HAZARD AREAS AS ESTABLISHED IN SECTION
 1612.3, ALL NEW CONSTRUCTION OF BUILDINGS, STRUCTURES
 AND PORTIONS OF BUILDINGS AND STRUCTURES, INCLUDING
 SUBSTANTIAL IMPROVEMENT AND RESTORATION OF SUBSTANTIAL
 DAMAGE TO BUILDINGS AND STRUCTURES, SHALL BE DESIGNED
 AND CONSTRUCTED TO RESIST THE EFFECTS OF FLOOD HAZARDS
 AND FLOOD LOADS. FOR BUILDINGS THAT ARE LOCATED IN MORE
 THAN ONE FLOOD HAZARD AREA, THE PROVISIONS ASSOCIATED
 WITH THE MOST RESTRICTIVE FLOOD HAZARD AREA SHALL
 APPLY.
  
 WIND DESIGN LOADS
 FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 402.1 GENERAL.
 ACCESSIBLE ROUTES SHALL COMPLY WITH 402.
 402.2 COMPONENTS.
 ACCESSIBLE ROUTES SHALL CONSIST OF ONE OR MORE OF THE
 FOLLOWING COMPONENTS: WALKING SURFACES WITH A RUNNING
 SLOPE NOT STEEPER THAN 1:20, DOORWAYS, RAMPS, CURB
 RAMPS EXCLUDING THE FLARED SIDES, ELEVATORS, AND
 PLATFORM LIFTS. ALL COMPONENTS OF AN ACCESSIBLE ROUTE
 SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF
 CHAPTER 4 AND 208.3.1.
  
 1008.1 GENERAL.
 PLAY AREAS SHALL COMPLY WITH 1008.
 1008.2 ACCESSIBLE ROUTES.
 ACCESSIBLE ROUTES SERVING PLAY AREAS SHALL COMPLY WITH
 CHAPTER 4 AND 1008.2 AND SHALL BE PERMITTED TO USE THE
 EXCEPTIONS IN 1008.2.1 THROUGH 1008.2.3. WHERE
 ACCESSIBLE ROUTES SERVE GROUND LEVEL PLAY COMPONENTS,
 THE VERTICAL CLEARANCE SHALL BE 80 INCHES HIGH (2030
 MM) MINIMUM.
  
 424.4 SEPARATION.
 CHILDREN?S PLAY STRUCTURES SHALL HAVE A HORIZONTAL
 SEPARATION FROM BUILDING WALLS, PARTITIONS AND FROM
 ELEMENTS OF THE MEANS OF EGRESS OF NOT LESS THAN 5 FEET
 (1524 MM). CHILDREN?S PLAYGROUND STRUCTURES SHALL HAVE
 A HORIZONTAL SEPARATION FROM OTHER CHILDREN?S PLAY
 STRUCTURES OF NOT LESS THAN 20 FEET (6090 MM).
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2017-02-09 Cont ID  
Sent By skennedy Date 2017-02-09 Time 11:02 Rev Time 0.00
Received By skennedy Date 2017-02-09 Time 11:02 Sent To  
Notes
2017-02-09 11:02:40OK, REVIEW BY VINCE NOEL.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2016-11-28 Cont ID  
Sent By mgonzale Date 2016-11-28 Time   Rev Time 1.00
Received By mgonzale Date 2016-11-28 Time   Sent To I
Notes
2016-11-28 17:30:50ADDRESS PLANNING'S COMMENTS.
  
 ADA ACCESSABILITY IS PARAMOUNT.
 SITE MUST CONFORM TO DEPARTMENT OF JUSTICE ADA
 STANDARDS FOR ACCESSIBLE DESIGN
 (HTTP://WWW.ADA.GOV/2010ADASTANDARDS_INDEX.HTM)
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-09 Cont ID  
Sent By cthroop Date 2017-02-09 Time 12:47 Rev Time 0.00
Received By cthroop Date 2017-01-20 Time 13:47 Sent To  
Notes
2017-01-23 13:48:00RESUB ROUTED TO JROACH VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-29 Cont ID  
Sent By cpuell Date 2016-11-29 Time 11:20 Rev Time 0.00
Received By cpuell Date 2016-08-30 Time 12:36 Sent To  
Notes
2016-08-31 12:36:469/29/16 - RESUB RECEIVED, ROUTED TO ZONING AGAIN
 ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2017-02-03 Cont ID  
Sent By jroach Date 2017-02-03 Time 10:32 Rev Time 0.00
Received By jroach Date 2017-02-03 Time 10:32 Sent To ENG
Notes
2017-01-23 14:49:18ROUTED TO JOHN ROACH

Review Stop Z ZONING
Rev No 1 Status F Date 2016-09-02 Cont ID  
Sent By jroach Date 2016-09-02 Time 09:37 Rev Time 0.00
Received By jroach Date 2016-09-01 Time 08:31 Sent To ENG
Notes
2016-09-02 09:38:07ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 09.02.2016
 PERMIT NO.: 16081247
 ADDRESS: 4801 DREHER TRAIL
 CONTRACTOR/CONTACT: DON AHLIN
 TELEPHONE NO.: 321.775.0600
 SCOPE OF REVIEW: NEW PLAYGROUND
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE PROVIDE TWO (2) COPIES OF A CURRENT AND
 ACCURATE SURVEY.
  
 2. PLEASE NOTE ON THE SITE PLAN THE EXACT LOCATION /
 CONFIGURATION OF THE PLAYGROUND, ALONG WITH ALL OTHER
 IMPROVEMENTS THAT ARE PROPOSED AS PART OF THE
 PLAYGROUND INSTALLATION (I.E. FENCING, GATES, ETC.).
  
 3. IT APPEARS THAT THERE ARE UTILITIES IN THE AREA OF
 THE PROPOSED INSTALLATION, INCLUDING SANITARY AND WATER
 LINES. PLEASE CONFIRM THEIR LOCATION AND ENSURE THAT
 THERE IS NO ISSUE WITH THE PLACEMENT OF THE EQUIPMENT
 RELATIVE TO THE LOCATION OF THE UTILITY LINES.
  
 4. PLEASE VERIFY IF ANY EXISTING LANDSCAPE MATERIAL IS
 PROPOSED TO BE REMOVED OR RELOCATED. IF SO, ADDITIONAL
 PERMITS / MODIFICATIONS MAY BE REQUIRED.
  
 5. THE DIMENSIONS IDENTIFIED FOR THE "PLAYGROUND AREA"
 DO NOT SEEM TO CORRESPOND TO THE ACTUAL DIMENSIONS OF
 THE SPACE OUTLINED. BASED UPON PREVIOUS PERMIT
 DRAWINGS, THERE IS ONLY APPROXIMATELY 18 FEET BETWEEN
 THE RAMP/WALKWAY AND THE FRONT OF THE BUILDING...THE
 DIMENSION PROVIDED ON THE SITE PLAN FOR THE PLAYGROUND
 INDICATES 25 FEET. ENSURE THAT THE AREA IDENTIFIED AND
 ALL DIMENSIONS ARE ACCURATE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  