Plan Review Details - Permit 16081241
Plan Review Stops For Permit 16081241
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-12-30 Cont ID  
Sent By shill Date 2016-12-30 Time 16:44 Rev Time 0.00
Received By shill Date 2016-12-30 Time 16:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-09-06 Cont ID  
Sent By shill Date 2016-09-06 Time 10:16 Rev Time 0.00
Received By shill Date 2016-09-06 Time 09:55 Sent To  
Notes
2016-09-06 10:16:32****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. WIND DESIGN CRITERIA IS NOT CLEAR. SEE FBC 1603.1.4.
 GENERAL NOTE 2 DOES NOT STATE WHETHER THIS WAS DESIGNED
 TO VULT OR VASD.
  
 2. PLEASE EXPLAIN THE RATIONALE OF DESIGNING TO RISK
 CATEGORY 1, FBC TABLE 1604.5, OR REVISE TO A MINIMUM
 RISK CATEGORY II.
  
 3. DELEGATED ENGINEERING AND SHOP DRAWINGS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL, FBC
 107. THE ARCHITECT'S PLAN (A0) EXCLUDES THE FENCE FROM
 THIS PERMIT. PLEASE REVISE PLAN AND HAVE ENGINEERING
 REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL.
  
 4. GENERAL NOTE 7 REFERS TO THE SECTION FOR RESIDENTIAL
 SWIMMING POOLS (FBC 454.2.17). SEE DEFINITIONS; A POOL
 ASSOCIATED WITH FIVE OR MORE RESIDENTIAL UNITS IS
 CONSIDERED A PUBLIC SWIMMING POOL, FBC 454.1. THE POOL
 FENCE IS TO COMPLY WITH FBC 454.1.3.1.9.
  
 5. FBC TABLE 1004.1.2, POOL DECK AREA SHOULD UTILIZE 15
 SF PER PERSON FOR THE POOL DECK RATHER THAN 50 SF PER
 PERSON, PLEASE REVISE OCCUPANT LOAD CALCULATIONS.
  
 6. REVISE PLAN TO INCLUDE THE OCCUPANCY CLASSIFICATION
 FOR THE POOL AND PLAYGROUND AREAS (A5), FBC 303.6.
  
 7. FBC 1008.2, GATES IN THE MEANS OF EGRESS ARE TO
 CONFORM TO THE REQUIREMENTS FOR DOORS. FBC 1008.1.10,
 PANIC DEVICES ARE REQUIRED IN ASSEMBLY OCCUPANCY WITH
 AN OCCUPANT LOAD OF 50 OR MORE.
  
 8. AS TWO MEANS OF EGRESS ARE REQUIRED FROM BOTH AREAS,
 IT APPEARS THAT BOTH THE POOL AREA AND THE PLAYGROUND
 AREA UTILIZE THE POOL CABANA AS A MEANS OF EGRESS. ONLY
 ONE DOOR IS SHOWN; IS THE OTHER SIDE OPEN? OR IS THE
 FRONT DOOR A GATE? EITHER REVISE PLAN TO PROVIDE A
 SECOND MEANS OF EGRESS FOR EACH AREA OR REVISE PLAN TO
 SHOW HOW THE POOL CABANA COMPLIES AS A MEANS OF EGRESS
 (PANIC DEVICES ON THE EXIT, INCLUDE DOOR WIDTHS). SEE
 ALSO FBC 1027.1 WHICH STATES "THE EXIT DISCHARGE SHALL
 NOT REENTER A BUILDING." IF THE CABANA IS TO BE A PART
 OF THE EXIT STRATEGY, PLEASE SEND AN EMAIL PRIOR TO
 RESUBMITTAL TO CONFIRM THAT THIS WILL BE PERMITTED IN
 THIS CASE.
  
 9. REVISE PLAN TO INCLUDE WIDTH OF ALL GATES IN THE
 MEANS OF EGRESS, FBC 107, FBC 10.
  
 10. REVISE PLAN TO SHOW ACCESSIBLE ROUTE TO THE PUBLIC
 WAY; SEE FBC 1007.1, FBC 5TH EDITION ACCESSIBILITY 207,
 IBC 2000 1003.2.13, IBC 2003 1007.2.
  
 11. FBC 107, THE APPLICATION IS FOR SIX GATES AND
 FENCING. PLEASE NOTE THE GATES; THE SAME GRAPHIC WAS
 USED FOR BOTH GATES AND DOORS ON THE PLAN. LOCATION OF
 THE SIX GATES IS NOT CLEAR.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-01-03 Cont ID  
Sent By wjolin Date 2017-01-03 Time 11:21 Rev Time 0.00
Received By wjolin Date 2017-01-03 Time 08:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-09-07 Cont ID  
Sent By wjolin Date 2016-09-07 Time 09:15 Rev Time 0.00
Received By wjolin Date 2016-09-07 Time 09:06 Sent To  
Notes
2016-09-07 09:15:254316 BRAXTON AVENUE
 PERMIT #16081241
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE PERMANENT WEATHERPROOF EXIT SIGNS ON EACH EACH
 EXIT GATE.
  
 DOORS/GATES SERVING AN ASSEMBLY SPACE WITH AN OCCUPANT
 LOAD OF 50 OR MORE PERSONS SHALL BE EQUIPPED WITH PANIC
 HARDWARE.
  
 THE OCCUPANT LOAD FOR THE POOL DECK SPACE IS
 INCORRECTLY CALCULATED USING AN OCCUPANT LOAD FACTOR OF
 50 SQ.FT. PER PERSON. PER NFPA 101 TABLE 7.3.1.2 AN
 OCCUPANT LOAD FACTOR OF 30 SQ.FT. PER PERSON SHALL BE
 USED.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-04 Cont ID  
Sent By lmarchan Date 2017-01-04 Time 13:36 Rev Time 0.00
Received By lmarchan Date 2016-12-21 Time 09:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-07 Cont ID  
Sent By lmarchan Date 2016-09-07 Time 09:28 Rev Time 0.00
Received By lmarchan Date 2016-08-30 Time 14:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2016-12-30 Cont ID  
Sent By shill Date 2016-12-30 Time 16:48 Rev Time 0.00
Received By shill Date 2016-12-30 Time 16:48 Sent To  
Notes
2016-12-30 15:30:0612-30-16 NEW DRAWINGS SUBMITTED FOR SIGNATURES, IN
 LIBRARY WITH PERMIT APP.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2016-09-06 Cont ID  
Sent By shill Date 2016-09-06 Time 10:16 Rev Time 0.00
Received By shill Date 2016-09-06 Time 10:16 Sent To  
Notes
2016-09-06 10:18:52****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. AS BOTH THE LIFE SAFETY PLAN AND THE ENGINEERING
 NEED TO BE REVISED, A NEW ORIGINAL HARD COPY OF THE
 ENGINEERING AND NEW DIGITALLY SIGNED AND SEALED LIFE
 SAFETY PLAN WILL BE REQUIRED (OR ANY OTHER METHOD
 PERMITTED BY FLORIDA STATUTE).
  
  
2016-08-31 14:01:38ORIGINAL HARD COPIES IN LIBRARY

Review Stop Z ZONING
Rev No 2 Status P Date 2017-01-03 Cont ID  
Sent By llouie Date 2017-01-03 Time   Rev Time 0.00
Received By llouie Date 2017-01-03 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-09-02 Cont ID  
Sent By njwira Date 2016-09-02 Time 14:39 Rev Time 0.00
Received By njwira Date 2016-09-02 Time 14:39 Sent To B
Notes
***NONE***