| 2016-08-30 17:09:43 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE ENGINEERED SITE SPECIFIC DRAWINGS FOR THE |
| | ELEVATOR THAT WERE SUBMITTED FOR PUBLIC RECORD ARE |
| | REQUIRED TO HAVE THE ORIGINAL SEAL AND HANDWRITTEN |
| | SIGNATURE OF THE ENGINEER, COPIES OR OTHER FACSIMILES |
| | ARE NOT ACCEPTABLE. FAC 61G15-23.002 |
| | |
| | 2) THE ELEVATOR DRAWINGS FROM THE DELEGATE ENGINEER ARE |
| | REQUIRED TO BE REVIEWED AND APPROVED BY THE STRUCTURAL |
| | ENGINEER OF RECORD FOR THE PROJECT. THE PLANS THAT ARE |
| | SUBMITTED ARE REQUIRED TO HAVE THE SHOP DRAWING REVIEW |
| | STAMP OF THE ENGINEER OF RECORD. FAC 61G15-31.001 |
| | |
| | 3) THERE IS A PERMIT ( 13040417 ) TO REPLACE THE 1ST |
| | FLOOR WINDOWS & DOORS, 2ND FLOOR DOORS AND EAST FACADE |
| | FIXED WINDOWS THAT HAS EXPIRED. THIS PERMIT WAS ISSUED |
| | PRIOR TO AND IS SEPARATE FROM THE MAIN HOUSE INTERIOR |
| | REMODEL PERMIT ( 13050679 ). THIS IS NOTED ON THE FIRST |
| | PAGE OF THE PLANS FOR PERMIT #13050679. THE WINDOW AND |
| | DOOR REPLACEMENT PERMIT (13040417) IS EXPIRED AND THERE |
| | WERE NO INSPECTIONS PERFORMED BY THE CITY'S INSPECTORS |
| | NOTED IN THE PERMIT RECORDS. THIS PERMIT WAS NOT |
| | COVERED BY THE PRIVATE PROVIDER'S SCOPE OF INSPECTIONS. |
| | THIS ISSUE WILL NEED TO BE RESOLVED BEFORE C.O. CAN BE |
| | ISSUED. IF YOU CAN PRODUCE DOCUMENTATION THAT THE |
| | PRIVATE PROVIDERS INSPECTED THE WINDOWS AND DOORS AT |
| | THE TIME THEY WERE INSTALLED, THE BUILDING OFFICIAL |
| | WILL REVIEW THE DOCUMENTS AND TAKE THEM INTO |
| | CONSIDERATION. OTHERWISE YOU WILL HAVE TO MAKE |
| | ARRANGEMENTS TO HAVE THEM INSPECTED BY THE CITY'S |
| | BUILDING DEPARTMENT. |
| | |
| | 4) THE ELEVATION CERTIFICATE IS ACCEPTABLE. |
| | |
| | |
| | |
| | |