Plan Review Details - Permit 16081202
Plan Review Stops For Permit 16081202
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-11-14 Cont ID  
Sent By rmcdouga Date 2016-11-14 Time 17:59 Rev Time 0.00
Received By rmcdouga Date 2016-11-14 Time 17:52 Sent To  
Notes
2016-11-14 17:59:50PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PREVIOUS COMMENTS WERE NOT ADDRESSED.
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE INSTALLATION DRAWINGS ARE REQUIRED TO HAVE THE
 FLORIDA ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN
 SIGNATURE, COPIES OR OTHER FACSIMILES ARE NOT
 ACCEPTABLE. FAC 61G15 - 23.002 DIGITAL SIGNATURES ARE
 ONLY ACCEPTABLE FOR ELECTRONICALLY TRANSMITTED PLANS
 AND DOCUMENTS.
  
 2) SPECIFY THE SIZE OF THE ROOF TOP COLLECTOR ON THE
 PLANS. FBC 107.2.1
  
 3) SPECIFY THE TILT UP ANGLE ABOVE THE ROOF PLANE OF
 THE ROOF TOP COLLECTOR ON THE PLANS. IF IT IS GREATER
 THAN 15 DEGREES ABOVE THE ROOF PLANE, SUBMIT SITE
 SPECIFIC ENGINEERING. FBC 107.2.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-09-02 Cont ID  
Sent By rmcdouga Date 2016-09-02 Time 07:51 Rev Time 0.00
Received By rmcdouga Date 2016-09-02 Time 06:46 Sent To  
Notes
2016-09-02 07:51:43PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE INSTALLATION DRAWINGS ARE REQUIRED TO HAVE THE
 FLORIDA ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN
 SIGNATURE, COPIES OR OTHER FACSIMILES ARE NOT
 ACCEPTABLE. FAC 61G15 - 23.002 DIGITAL SIGNATURES ARE
 ONLY ACCEPTABLE FOR ELECTRONICALLY TRANSMITTED PLANS
 AND DOCUMENTS.
  
 2) SPECIFY THE SIZE OF THE ROOF TOP COLLECTOR ON THE
 PLANS. FBC 107.2.1
  
 3) SPECIFY THE TILT UP ANGLE ABOVE THE ROOF PLANE OF
 THE ROOF TOP COLLECTOR ON THE PLANS. IF IT IS GREATER
 THAN 15 DEGREES ABOVE THE ROOF PLANE, SUBMIT SITE
 SPECIFIC ENGINEERING. FBC 107.2.1

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-14 Cont ID  
Sent By rmcdouga Date 2016-11-14 Time 17:59 Rev Time 0.00
Received By rmcdouga Date 2016-11-07 Time 10:09 Sent To  
Notes
2016-11-08 10:10:08RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-02 Cont ID  
Sent By rmcdouga Date 2016-09-02 Time 07:51 Rev Time 0.00
Received By rmcdouga Date 2016-08-30 Time 12:35 Sent To  
Notes
2016-08-31 12:35:23ROUTED TO PLUMBING INBOX

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-11-14 Cont ID  
Sent By tklarge Date 2016-11-14 Time 06:21 Rev Time 0.00
Received By tklarge Date 2016-11-14 Time 06:01 Sent To  
Notes
2016-11-14 06:18:55THE PLUMBING COMMENTS FROM THE PREVIOUS REVIEW HAVE NOT
 BEEN ADDRESSED.
 1) SUBMIT TWO SETS OF PLANS THAT ARE SIGNED AND SEALED
 BY THE ENGINEER PER THE FL. ADMIN. CODE RULE
 61G15-23.001 AND THE NOTE IN THE TOP RIGHT CORNER ON
 SHT.1LDR-DHW.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-09-02 Cont ID  
Sent By tklarge Date 2016-09-02 Time 04:20 Rev Time 0.00
Received By tklarge Date 2016-09-02 Time 03:24 Sent To  
Notes
2016-09-02 04:07:411) THE PLANS SHALL BE SIGNED AND SEALED BY THE DESIGN
 PROFESSIONAL OF RECORD PER THE FL. ADMIN. CODE RULE
 61G15-23.001 AND THE NOTE IN THE TOP RIGHT CORNER ON
 SHT.1LDR-DHW.
 2) SHOW THE CAPACITY OF THE EXPANSION TANK.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  