Plan Review Details - Permit 16081110
Plan Review Stops For Permit 16081110
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2018-01-29 Cont ID  
Sent By jgomez Date 2018-01-29 Time 08:44 Rev Time 0.00
Received By jgomez Date 2018-01-29 Time 08:44 Sent To  
Notes
2018-01-29 08:45:02CHRIS POONAI TO: JGOMEZ 01/26/2018 11:46 AM
  
 FROM: CHRIS POONAI
  
 TO: [email protected]
  
 HELLO MR. GOMEZ,
 THIS EMAIL IS TO REQUEST YOU TO APPROVE THE BUILDING
 PERMIT AND THE AIR CONDITIONING WILL BE DONE WITH A
 SEPARATE PERMIT AS THIS IS HOLDING THE MASTER PERMIT
 UP.
 LET ME KNOW IF YOU HAVE ANY QUESTIONS.
  
 REGARDS
 CHRIS
  
  
 BUILDING REVIEW APPROVED WITH PROVISO.
 1- ENERGY CALCULATIONS: BUILDER TO COMPLETE THE ENERGY
 PERFORMANCE LEVEL (EPL) DISPLAY CARD.
  
 MECHANICAL REVIEW PROVISO:
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS UNDER
 A SEPARATE PERMIT.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2018-01-19 Cont ID  
Sent By jgomez Date 2018-01-19 Time 17:20 Rev Time 0.00
Received By jgomez Date 2018-01-19 Time 15:17 Sent To  
Notes
2018-01-19 15:28:34BUILDING REVIEW APPROVED WITH PROVISO.
  
 1- ENERGY CALCULATIONS: BUILDER TO COMPLETE THE ENERGY
 PERFORMANCE LEVEL (EPL) DISPLAY CARD.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2017-11-20 Cont ID  
Sent By jgomez Date 2017-11-20 Time 18:10 Rev Time 0.00
Received By jgomez Date 2017-11-20 Time 12:39 Sent To  
Notes
2017-11-20 12:40:30RESIDENTIAL (R3) ADDITION/ALTERATION FOURTH BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT CONTRACTOR WILL SUBMIT REQUIRED INFORMATION
 PRIOR TO INSPECTIONS TO AVOID CONFLICTS/DELAYS.
 REVISION FEES MAY APPLY. CONTRACTOR TO ADVICE IF THE
 PROVISO OPTION IS PREFERRED AT THIS TIME. NEED TO HAVE
 THE ENERGY CALCULATIONS CERTIFIED BY THE OWNER OF
 LEGALLY DESIGNATED AGENT AND BUILDER NEEDS TO COMPLETE
 THE EPL DISPLAY CARD BEFORE ISSUING PERMIT.
  
  
 1- ENERGY CALCULATIONS FORM R405-2014 SUBMITTED:
 A) OWNER OR LEGALLY DESIGNATED AGENT SHALL CERTIFY AT
 THE BOTTOM OF FORM SUBMITTED AS REQUIRED BY SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD ENCLOSED IN THE ENERGY CALCULATIONS
 PACKAGE. SEC. R405.4.3 FBC-ENERGY CONSERVATION.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS (DOORS,
 WINDOWS AND ROOFING) AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 3- FLAT ROOF NOA 14-1030.02 SUBMITTED:
 A) CLEARLY MARK SPECIFIC APPROVED ASSEMBLY TO BE
 INSTALLED TO VERIFY COMPLIANCE WIT THE DESIGN PRESSURES
 OF SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2
 COPIES) AS REQUIRED BY GENERAL LIMITATION # 7 ON LAST
 PAGE OF NOA SUBMITTED. REQUIRED TO MEET THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT.
  
 4- REVISE SURVEY DRAWN ON 08/06/17. ACCORDING TO FLOOD
 INSURANCE RATE MAP (FIRM) COMMUNITY PANEL NUMBER 120229
 0020B EFFECTIVE DATE MARCH 1, 1979 THIS BUILDING IS
 LOCATED IN FLOOD ZONE "C" NOT "B". REVISE AS REQUIRED.
 SEC. R107.2.1 AND SEC. 107.2.5 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-06-29 Cont ID  
Sent By jgomez Date 2017-06-29 Time 15:18 Rev Time 0.00
Received By jgomez Date 2017-06-28 Time 17:27 Sent To E
Notes
2017-06-28 17:32:34RESIDENTIAL (R3) ADDITION/ALTERATION THIRD BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES THE PLAN
 REVIEW FEE AS REQUIRED BY FLORIDA STATUTE 553.80(2)(B)
 FOR MULTIPLE PLAN REVIEW REJECTIONS.
  
  
 1- NEW ENERGY CALCULATIONS FORM R405-2014 SUBMITTED:
 A) OWNER OR LEGALLY DESIGNATED AGENT SHALL CERTIFY AT
 THE BOTTOM OF FORM SUBMITTED AS REQUIRED BY SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER NAME, BUILDER NAME, PERMIT OFFICE AND
 JURISDICTION. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 C) ITEM #9: PERSON PREPARING THE ENERGY CALCULATIONS TO
 IDENTIFY WHERE ARE THE CONCRETE BLOCK WALLS WITH R5
 INSULATION AND R4.1 INSULATION. ALSO, THE ARE DOESN'T
 MATCH AREA SHOWN ON PLANS. SEE PLANS AND REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) REVISE CEILING INSULATION SPECIFIED ON ITEM #10. THE
 R30 BATT INSULATION DOESN'T FIT ON 2X8 ROOF JOISTS.
 COORDINATE WITH ENGINEER'S REVISE PLANS AND REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E) REVISE THE ROOF TYPE AND ROOF MATERIALS SPECIFIED ON
 PAGE 2 OF 4 TO MATCH PLANS. THE ADDITION IS A FLAT
 ROOF.
  
 F) REVISE THE ORIENTATION OF THE WALLS SHOWN ON PAGE 3
 OF 4 TO MATCH PLANS. THERE ARE NO WALL ON THE WEST
 SIDE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G) REVISE THE ORIENTATION OF THE DOOR SHOWN ON PAGE 3
 OF 4 TO MATCH PLANS. THERE ARE NO DOORS ON THE WEST
 SIDE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 H) REVISE THE ORIENTATION OF THE WINDOW SHOWN ON PAGE 3
 OF 4 TO MATCH PLANS. THERE ARE NO WINDOWS ON THE WEST
 SIDE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 I) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD ENCLOSED IN THE ENERGY CALCULATIONS
 PACKAGE. SEC. R405.4.3 FBC-ENERGY CONSERVATION.
  
 2- REVISE ROOF SLOPE SHOWN ON THE EXTERIOR ELEVATIONS.
 THE REQUIRED SLOPE IS 1/4" PER FT MIN. SEC. R905.9
 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT.
  
 3- TYPICAL WALL SECTION ON SHEET A-1:
 A) NEED TO PROVIDE ROOF CROSS VENTILATION AS REQUIRED
 BY SEC. R806 FBC-RESIDENTIAL. SPECIFIED VENTS DON'T
 PROVIDE CROSS VENTILATION ON A FLAT ROOF WITH SOLID 2X8
 ROOF JOISTS. REVISE AS REQUIRED.
 RESPONSE: REPEAT COMMENT.
 NOTE:
 ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES THE PLAN
 REVIEW FEE AS REQUIRED BY FLORIDA STATUTE 553.80(2)(B)
 FOR MULTIPLE PLAN REVIEW REJECTIONS.
  
 B) R-30 BATT INSULATION IS 9-1/2" THICK. IT DOESN'T FIT
 ON 2 X 8 ROOF JOISTS. IN ADDITION R-30 INSULATION
 DOESN'T ALLOW FOR THE 1" VENTILATION CLEARANCE AS
 REQUIRED BY SEC. R806.3 FBC-RESIDENTIAL. REVISE AS
 REQUIRED.
 RESPONSE: REPEAT COMMENT.
 NOTE:
 ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES THE PLAN
 REVIEW FEE AS REQUIRED BY FLORIDA STATUTE 553.80(2)(B)
 FOR MULTIPLE PLAN REVIEW REJECTIONS.
  
 C) THE OVERHANG DIMENSION DOESN'T MATCH OVERHANG
 DIMENSION SHOWN ON THE ROOF FRAMING PLAN. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) SINGLE HUNG WINDOWS AS SHOWN ON PLANS. DWGS NO
 08-02476 SUBMITTED DON'T HAVE A FLORIDA PRODUCT
 APPROVAL NUMBER OR MIAMI-DADE NOA NUMBER. PROVIDE
 FLORIDA OR MIAMI-DADE COVER PAGE THAT CORRESPONDS TO
 DRAWINGS SUBMITTED. IF THERE IS NOT CURRENT FLORIDA OR
 MIAMI-DADE APPROVAL, THEN MANUFACTURER MAY APPLY FOR
 LOCAL PRODUCT APPROVAL BY SUBMITTING COMPLETE ORIGINAL
 ENGINEER PACKAGE FOR BUILDING OFFICIAL APPROVAL. ADVICE
 IF APPLYING FOR LOCAL PRODUCT APPROVAL FOR FURTHER
 INSTRUCTIONS.
 RESPONSE: REPEAT COMMENT. PROVIDE FLORIDA PRODUCT
 APPROVAL COVER PAGE THAT CORRESPOND TO DRAWINGS
 SUBMITTED.
  
 B) PRECAST LINTELS AS SPECIFIED ON PLANS.
 RESPONSE: REPEAT COMMENT.
  
 C) SIMPSON STRUCTURAL CONNECTORS AS SPECIFIED ON PLANS.
 PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE SPECIFIED CONNECTOR OR ENGINEER TO
 LIST THE FLORIDA PRODUCT APPROVAL NEXT TO EACH
 SPECIFIED CONNECTOR.
 RESPONSE: REPEAT COMMENT.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS (DOORS,
 WINDOWS AND ROOFING) AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
 RESPONSE: REPEAT COMMENT.
  
 6- FLAT ROOF NOA 14-1030.02 SUBMITTED:
 A) CLEARLY MARK SPECIFIC APPROVED ASSEMBLY TO BE
 INSTALLED TO VERIFY COMPLIANCE WIT THE DESIGN PRESSURES
 OF SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2
 COPIES) AS REQUIRED BY GENERAL LIMITATION # 7 ON LAST
 PAGE OF NOA SUBMITTED. REQUIRED TO MEET THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT.
  
 7- ROOF FRAMING PLAN: SPECIFY HOW ARE THE ROOF JOISTS
 CONNECTED TO THE "EXISTING CONCRETE BEAM". SEC. R301.1
 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT.
 NOTE:
 ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES THE PLAN
 REVIEW FEE AS REQUIRED BY FLORIDA STATUTE 553.80(2)(B)
 FOR MULTIPLE PLAN REVIEW REJECTIONS.
  
 8- THE SCOPE OF WORK IS NOT ALTERATION LEVEL 2. REVISE
 INFORMATION AT THE BOTTOM RIGHT OF SHEET A-1. THIS IS
 AN ADDITION. SEC. 507 FBC-EXISTING BUILDING, 5TH
 EDITION (2014).
 RESPONSE: REPEAT COMMENT.
  
 ****ENGINEER OF RECORD TO PROVIDE RESPONSE LETTER
 ADDRESSING EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-02-15 Cont ID  
Sent By jgomez Date 2017-02-15 Time 14:58 Rev Time 0.00
Received By jgomez Date 2017-02-14 Time 17:31 Sent To  
Notes
2017-02-14 17:52:33 
 05/24/17 MET W/ CONTRACTOR (JUNIOR) TO GO OVER
 COMMENTS. EXISTING ADDITION IN QUESTION WAS CLARIFIED.
 IT WAS BUILT LONG TIME AGO AND SHOWN ON THE GREEN CARD.
 JG.
  
  
 RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 THERE IS A CONFLICT WITH PERMIT #14100767 AND PLANS
 SUBMITTED NOW FOR THE BEDROOM ADDITION. PERMIT
 #14100767 WAS FOR AN STORAGE ROOM. PLANS SUBMITTED NOW
 INDICATE THAT THIS AREA IS LIVABLE AREA (NO STORAGE).
 IN 2014 PERMIT APPLICATION AND PLANS WERE SUBMITTED TO
 RE-OPEN EXPIRED PERMIT #99120889. PERMIT #14100767 WAS
 NEVER ISSUED. IT WAS ABANDONED. NEED TO INVESTIGATE IF
 THE WORK WAS DONE. THERE ARE NO PERMITS OR INSPECTIONS
 FOR THE WORK IN THIS AREA. FEES FOR WORK WITHOUT PERMIT
 MAY APPLY.
  
  
 1- BASED ON THE PRESCRIPTIVE ENERGY CALCULATIONS FORM
 R402-2014 SUBMITTED THE FOLLOWING ITEMS ARE REQUIRED:
 A) CONCRETE BLOCK WALL TO HAVE INSULATION ON THE
 INTERIOR AND EXTERIOR SIDE OF THE WALL. SEE TABLE R402A
 OF FORM R402-2014 SUBMITTED. ENGINEER OF RECORD TO
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW
 THE INSULATION IS GOING TO BE INSTALLED ON BOTH SIDES
 OF THE WALL. SEC. R103.2 FBC-ENERGY CONSERVATION.
  
 B) NEED R-30 CEILING INSULATION. SEE TABLE R402A FOR
 MANDATORY REQUIREMENTS. R-30 BATT INSULATION DOESN'T
 FIT ON 2X8 ROOF JOISTS. R-30 BATT INSULATION IS ABOUT
 9-1/2" THICK. ALSO, NEED AT LEAST 1" CLEARANCE BETWEEN
 THE INSULATION AND THE ROOF SHEATHING FOR ROOF
 VENTILATION AS REQUIRED BY SEC. R806.3 FBC-RESIDENTIAL.
 REVISE PLANS AS REQUIRED.
  
  
 2- ENERGY CALCULATIONS PRESCRIPTIVE FORM R402-2014
 SUBMITTED: (NOTE: IF ITEMS REQUIRED BY TABLE R402A CAN
 NOT BE INSTALLED, THEN THIS PRESCRIPTIVE METHOD CAN NOT
 BE USED).
 A) CALCULATIONS NEED TO BE CERTIFIED AND DATED BY THE
 OWNER AT THE BOTTOM OF FORM AS REQUIRED BY SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) PROVIDE THE NAME OF THE PERSON WHO PREPARED THE
 ENERGY CALCULATIONS AND DATE IT WAS SIGNED AS REQUIRED
 BY SEC. 107.2.1 CITY AMENDMENTS.
  
 C) COMPLETE WINDOWS ITEM # 6(A) AND #6(B) AS REQUIRED
 BY SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014). NOTE: SEE TABLE R402A FOR MANDATORY
 REQUIREMENTS.
  
 D) COMPLETE FLOOR ITEM #8 AS REQUIRED BY SEC.
 R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). NOTE: SEE TABLE R402A FOR MANDATORY
 REQUIREMENTS.
  
 E) COMPLETE WALL ITEM #9 AS REQUIRED BY SEC.
 R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). NOTE: NEED INSULATION ON THE INTERIOR SIDE AND
 EXTERIOR SIDE OF THE CONCRETE BLOCK WALL. SEE TABLE
 R402A FOR MANDATORY REQUIREMENTS.
  
 F) COORDINATE CEILING R-VALUE ON ITEM #10 WITH REVISED
 INFORMATION REQUIRED BY ITEM #1(B) ABOVE. NOTE: IF R-30
 INSULATION CAN NOT BE INSTALLED, THEN THE PRESCRIPTIVE
 ENERGY CALCULATIONS FORM R402-2014 CAN NOT BE USED.
 SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION.
  
 G) COMPLETE ALL THE INFORMATION ON COOLING SYSTEM ITEM
 #12 (A) AND (B) AS REQUIRED BY SEC. R101.5.1.1.1
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 H) COMPLETE ALL THE INFORMATION ON HEATING SYSTEM ITEM
 #13 (A) AND (B) AS REQUIRED BY SEC. R101.5.1.1.1
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 I) COMPLETE ALL THE INFORMATION HVAC SIZING
 CALCULATIONS ON ITEM # 14 AS REQUIRED BY SEC.
 R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 J) COMPLETE ALL THE INFORMATION ON WATER HEATING SYSTEM
 ITEM #15 AS REQUIRED BY SEC. R101.5.1.1.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 K) COMPLETE ALL THE INFORMATION ON TABLES R402A AND
 TABLE R402B AS REQUIRED BY SEC. R101.5.1.1.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 L) BASED ON PLANS SUBMITTED, IT LOOKS LIKE THERE IS A
 LIVABLE AREA ADJACENT TO THE PROPOSED ADDITION. THIS
 AREA WAS NOT PERMITTED AND INSPECTED. COORDINATE WITH
 INTRODUCTORY NOTE ON TOP OF THIS SHEET AND ITEM #3
 BELOW. ENERGY CALCULATIONS NEED TO BE REVISED TO
 INCLUDE THE ADJACENT ROOM. SEC. R101.5.1.1.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 NOTE:
 LABEL FOR DOORS AND WINDOWS SHOWING THE U-FACTOR AND
 SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL
 BE REQUIRED FOR INSPECTION.
  
  
 3- THE WEST WALL IS BLOCKED TO ALLOW FOR THE PROPOSED
 ADDITION. CLEARLY IDENTIFY ON PLANS THE ROOM (OR ROOMS)
 THAT ARE ADJACENT TO THE PROPOSED ADDITION. IF THERE IS
 ANY BEDROOM LOCATED ADJACENT TO THE PROPOSED ADDITION,
 THEN COMPLIANCE WITH THE EGRESS REQUIREMENTS NEED TO BE
 PROVIDED. SEC. R310 FBC-RESIDENTIAL, 5TH EDITION
 (2014).
 RESPONSE: AREA ADJACENT TO THE PROPOSED ADDITION IS
 SUPPOSED TO BE STORAGE NOT LIVABLE AREA. (SEE
 INTRODUCTORY NOTE ON TOP OF THIS SHEET REGARDING
 CONFLICT WITH ABANDONED PERMITS). NEED TO PROVIDE
 COMPLETE PLANS/DETAILS/ SPECIFICATIONS AND PRODUCT
 APPROVALS FOR THE AREA ADJACENT TO THE PROPOSED
 ADDITION. ADDITIONAL COMMENTS MAY ARISE BASED ON THE
 INFORMATION SUBMITTED AND VALUATION NEED TO BE UPDATED
 AS WELL TO INCLUDE THE ADDITONAL SCOPE OF WORK.
  
 4- REVISE ROOF SLOPE SHOWN ON THE EXTERIOR ELEVATIONS.
 THE REQUIRED SLOPE IS 1/4" PER FT MIN. SEC. R905.9
 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT.
  
 5- TYPICAL WALL SECTION ON SHEET A-1:
 A) NEED TO PROVIDE ROOF CROSS VENTILATION AS REQUIRED
 BY SEC. R806 FBC-RESIDENTIAL. SPECIFIED VENTS DON'T
 PROVIDE CROSS VENTILATION ON THE TYPE OF PROPOSED ROOF
 (FLAT). NOTE: THE 2"X8" BRACING SHOWN ON THE ROOF
 FRAMING PLAN IS ALSO BLOCKING THE CROSS VENTILATION.
 NEED TO PROVIDE AT LEAST 1" VENT AND INSULATION
 CLEARANCE AS REQUIRED BY SEC. R806.3 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT. SPECIFIED VENTS DON'T PROVIDE
 CROSS VENTILATION. THEY ONLY PROVIDE VENTILATION WHERE
 THE VENT IS LOCATED. THIS TYPE OF ROOF NEEDS CONTINUOUS
 VENT. ALSO, R-30 BATT INSULATION IS 9-1/2" THICK. IT
 DOESN'T FIT ON 2 X 8 ROOF JOISTS. IN ADDITION R-30
 INSULATION DOESN'T ALLOW FOR THE 1" VENT INSULATION
 CLEARANCE. REVISE AS REQUIRED. COORDINATE WITH THE
 REQUIRED REVISED ENERGY CALCULATIONS AND ITEM #1(B)
 ABOVE.
  
 B) SPECIFY THE WALL INSULATION. NOTE: COORDINATE WITH
 THE ENERGY CALCULATIONS AND COMMENT # 1(A) ABOVE. SEC.
 R103.2 FBC-ENERGY CONSERVATION.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) SINGLE HUNG WINDOWS AS SHOWN ON PLANS. DWGS NO
 08-02476 SUBMITTED DON'T HAVE A FLORIDA PRODUCT
 APPROVAL NUMBER OR MIAMI-DADE NOA NUMBER. PROVIDE
 FLORIDA OR MIAMI-DADE COVER PAGE THAT CORRESPONDS TO
 DRAWINGS SUBMITTED. IF THERE IS NOT CURRENT FLORIDA OR
 MIAMI-DADE APPROVAL, THEN MANUFACTURER MAY APPLY FOR
 LOCAL PRODUCT APPROVAL BY SUBMITTING COMPLETE ORIGINAL
 ENGINEER PACKAGE FOR BUILDING OFFICIAL APPROVAL. ADVICE
 IF APPLYING FOR LOCAL PRODUCT APPROVAL FOR FURTHER
 INSTRUCTIONS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED. PROVIDE
 FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPOND TO
 DRAWINGS SUBMITTED.
  
 B) PRECAST LINTELS AS SPECIFIED ON PLANS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 C) SIMPSON STRUCTURAL CONNECTORS AS SPECIFIED ON PLANS.
 PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE SPECIFIED CONNECTOR OR ENGINEER TO
 LIST THE FLORIDA PRODUCT APPROVAL NEXT TO EACH
 SPECIFIED CONNECTOR.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS (DOORS,
 WINDOWS AND ROOFING) AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 8- FLAT ROOF NOA 14-1030.02 SUBMITTED:
 A) CLEARLY MARK SPECIFIC APPROVED ASSEMBLY TO BE
 INSTALLED TO VERIFY COMPLIANCE WIT THE DESIGN PRESSURES
 OF SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2
 COPIES) AS REQUIRED BY GENERAL LIMITATION # 7 ON LAST
 PAGE OF NOA SUBMITTED. REQUIRED TO MEET THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 9- ROOF FRAMING PLAN: SPECIFY HOW ARE THE ROOF JOISTS
 CONNECTED TO THE "EXISTING CONCRETE BEAM". SEC. R301.1
 FBC-RESIDENTIAL. NOTE: ACCORDING TO PLANS SUBMITTED ON
 EXPIRED PERMIT #14100767 THE EXISTING ROOM IS WOOD
 FRAME CONSTRUCTION NOT CONCRETE BLOCK. NOTE: COORDINATE
 WITH THE INTRODUCTORY NOTE ON THE TOP OF THIS SHEET AND
 ITEM # 3 ABOVE.
  
 10- REVISE INFILL DETAIL ON SHEET A-1. NOTE: ACCORDING
 TO PLANS SUBMITTED ON EXPIRED PERMIT #14100767 THE
 EXISTING ROOM IS WOOD FRAME CONSTRUCTION NOT CONCRETE
 BLOCK. NOTE: COORDINATE WITH THE INTRODUCTORY NOTE ON
 THE TOP OF THIS SHEET AND ITEM # 3 ABOVE. SEC. 107.2.1
 CITY AMENDMENTS.
  
 11- THE SCOPE OF WORK IS NOT ALTERATION LEVEL 2. REVISE
 INFORMATION AT THE BOTTOM RIGHT OF SHEET A-1. SEE
 CHAPTER 5 OF FBC-EXISTING BUILDING, 5TH EDITION (2014)
 AND REFERENCE THE CORRECT CLASSIFICATION OF WORK FOR
 THE PROPOSED WORK AS REQUIRED BY SEC. 501.1
 FBC-EXISTING BUILDING.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-09-16 Cont ID  
Sent By awooten Date 2016-09-16 Time 11:36 Rev Time 0.00
Received By jgomez Date 2016-09-16 Time 10:36 Sent To  
Notes
2016-09-16 11:40:13RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
 NOTE: THIS MAY BE DONE LATER WHEN PERMIT IS READY TO BE
 ISSUED.
  
 2- PROVIDE ENERGY CALCULATIONS (2 COPIES). SEC.
 R101.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 NOTE: COORDINATE WITH INFORMATION SHOWN ON PLANS TO
 AVOID CONFLICTS OR DELAYS.
  
 3- THE WEST WALL IS BLOCKED TO ALLOW FOR THE PROPOSED
 ADDITION. CLEARLY IDENTIFY ON PLANS THE ROOM (OR ROOMS)
 THAT ARE ADJACENT TO THE PROPOSED ADDITION. IF THERE IS
 ANY BEDROOM LOCATED ADJACENT TO THE PROPOSED ADDITION,
 THEN COMPLIANCE WITH THE EGRESS REQUIREMENTS NEED TO BE
 PROVIDED. SEC. R310 FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 4- FOUNDATION PLAN ON SHEET A-1 IS NOT CLEAR. THERE IS
 NOT FOOTING MF-16 AT THE CORNER WHERE THE NEW SHOWER IS
 GOING TO BE INSTALLED. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS. SEC. R301.1 FBC-RESIDENTIAL.
  
 5- FLOOR PLANS ON SHEET A-1 DOESN'T SPECIFY SIZE OF ALL
 DOORS AND WINDOWS. PROVIDE COMPLETE INFORMATION. SEC.
 107.2.1 CITY AMENDMENTS.
  
 6- REVISE ROOF SLOPE SHOWN ON THE ROOF FRAMING PLAN,
 TYPICAL WALL SECTION AND EXTERIOR ELEVATIONS. THE
 REQUIRED SLOPE IS 1/4" PER FT MIN. SEC. R905.9
 FBC-RESIDENTIAL.
  
 7- TYPICAL WALL SECTION ON SHEET A-1:
 A) PROVIDE COMPLETE SPECIFICATIONS FOR THE ROOF
 SHEATHING FASTENING AS REQUIRED BY SEC. R803.2.1.3.1
 FBC-RESIDENTIAL. NEED TO SPECIFY NAIL SPACING FOR EACH
 ZONE. AND, CLARIFY WHERE IS SHEET C2 REFERENCED ON THE
 WALL SECTION?.
  
 B) NEED TO PROVIDE ROOF CROSS VENTILATION AS REQUIRED
 BY SEC. R806 FBC-RESIDENTIAL. SPECIFIED VENTS DON'T
 PROVIDE CROSS VENTILATION ON THE TYPE OF PROPOSED ROOF
 (FLAT). NOTE: THE 2"X8" BRACING SHOWN ON THE ROOF
 FRAMING PLAN IS ALSO BLOCKING THE CROSS VENTILATION.
 NEED TO PROVIDE AT LEAT 1" VENT AND INSULATION
 CLEARANCE AS REQUIRED BY SEC. R806.3 FBC-RESIDENTIAL.
  
 C) SPECIFY THE ROOF INSULATION. NOTE: COORDINATE WITH
 THE ENERGY CALCULATIONS AND ITEM # 7(B) ABOVE. SEC.
 R103.2 FBC-ENERGY CONSERVATION.
  
 D) SPECIFY THE WALL INSULATION. NOTE: COORDINATE WITH
 THE ENERGY CALCULATIONS. SEC. R103.2 FBC-ENERGY
 CONSERVATION.
  
 8- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) SINGLE HUNG WINDOWS AS SHOWN ON PLANS. DWGS NO
 08-02476 SUBMITTED DON'T HAVE A FLORIDA PRODUCT
 APPROVAL NUMBER OR MIAMI-DADE NOA NUMBER. PROVIDE
 FLORIDA OR MIAMI-DADE COVER PAGE THAT CORRESPONDS TO
 DRAWINGS SUBMITTED. IF THERE IS NOT CURRENT FLORIDA OR
 MIAMI-DADE APPROVAL, THEN MANUFACTURER MAY APPLY FOR
 LOCAL PRODUCT APPROVAL BY SUBMITTING COMPLETE ORIGINAL
 ENGINEER PACKAGE FOR BUILDING OFFICIAL APPROVAL. ADVICE
 IF APPLYING FOR LOCAL PRODUCT APPROVAL FOR FURTHER
 INSTRUCTIONS.
  
 B) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 C) SIMPSON STRUCTURAL CONNECTORS AS SPECIFIED ON PLANS.
 PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE SPECIFIED CONNECTOR OR ENGINEER TO
 LIST THE FLORIDA PRODUCT APPROVAL NEXT TO EACH
 SPECIFIED CONNECTOR.
  
 9- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 10- FLAT ROOF NOA 14-1030.02 SUBMITTED:
 A) CLEARLY MARK SPECIFIC APPROVED ASSEMBLY TO BE
 INSTALLED TO VERIFY COMPLIANCE WIT THE DESIGN PRESSURES
 OF SEC. R301.1 FBC-RESIDENTIAL.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2
 COPIES) AS REQUIRED BY GENERAL LIMITATION # 7 ON LAST
 PAGE OF NOA SUBMITTED. REQUIRED TO MEET THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
  
 11- PROVIDE SPECIFICATIONS FOR CARBON MONOXIDE ALARMS
 WITHIN ALL BEDROOMS AS REQUIRED BY SEC. R315
 FBC-RESIDENTIAL.
  
 12- INFORMATION SHOWN ON WINDOW/DOOR BUCK DETAIL AND
 DOOR HEAD/JAMB SHOWN ON SHEET A-2 IS NOT CLEAR AND
 DOESN'T MATCH. IT LOOKS LIKE IT'S FOR TWO DIFFERENT
 PROJECTS. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-06-30 Cont ID  
Sent By jleahy Date 2017-06-30 Time 09:58 Rev Time 0.00
Received By jleahy Date 2017-06-30 Time 09:58 Sent To  
Notes
2017-06-29 15:16:09NEW DRAWINGS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-02-21 Cont ID  
Sent By rlecky Date 2017-02-21 Time 13:14 Rev Time 0.00
Received By rlecky Date 2017-02-21 Time 12:27 Sent To  
Notes
2017-02-21 13:14:58PLANS WERE ACCEPTED WITH THE FOLLOWING :
  
 PROVISO:
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE BUILDING HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE, A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. FBC R314, 315
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94; FBC E3609
  
 A DISCONNECT IS REQUIRED AT THE INTERIOR AND EXTERIOR
 AC UNITS. FBC E4101.5
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-805-6654(OFFICE)
 561-373-3701(CELL)
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-09-13 Cont ID  
Sent By albarran Date 2016-09-13 Time 10:58 Rev Time 0.00
Received By albarran Date 2016-09-13 Time 10:09 Sent To  
Notes
2016-09-13 11:00:33ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 JOB ADDRESS: 7604 MARTIN AVE.
 DESCRIPTION: BUILD-OUT AS PER PLANS
 MASTER PERMIT: 16081110
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. YOU SHALL SUBMIT A SITE PLAN SHOWING THE LOCATION OF
 THE ELECTRIC METER AND ASSOCIATED APPARATUS AND THE
 ELECTRIC UTILITY SERVICE POLE. INDICATE ON IT IF THE
 SERVICE IS UNDERGROUND OR OVERHEAD. FURTHERMORE YOU
 SHALL SHOW THE LOCATION OF THE EXISTING PANEL. INDICATE
 IF THERE IS A DISCONNECT ON THE EXTERIOR OF THE
 RESIDENCE.
 2. YOU SHALL SUBMIT A SITE SPECIFIC ELECTRICAL RISER
 DIAGRAM MATCHING THE ABOVE MENTIONED.
 3. NOTE THAT IT IS THE AMBIENT CONDITIONS WHICH
 DETERMINE CONDUCTOR INSULATION TYPE AND NOT THE WIRE
 GAUGE. ALL CONDUCTORS EXPOSED TO DAMP OR WET LOCATIONS
 SHALL BE LISTED ACCORDINGLY REGARDLESS OF GAUGE.
 CORRECT NOTE 8 OF THE ELECTRICAL NOTES.
 4. FBC-R3706.2 NEC 408.4(A) REQUIRES THAT YOU PROVIDE A
 PANEL SCHEDULE OR CIRCUIT DIRECTORY LEGIBLY INDICATING
 THE SPECIFIC PURPOSE OF EVERY CIRCUIT. THIS APPLIES TO
 ALL PANELS OF THE HOME. INDICATE WHETHER MAIN BREAKER
 OR MAIN LUG ONLY.
 5. FBC-ER3901.12 NEC 210.63 HVAC EQUIPMENT SERVICE
 OUTLET. A 125 VOLT, SINGLE-PHASE, 15 OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT AND THE DEVICE LISTED WEATHER-RESISTANT AS
 INDICATED BY FBC-R4002.9.
 6. FBC-RE3901.2.1 NEC 210.52 (A)(1) SPACING.
 RECEPTACLES SHALL BE INSTALLED SUCH THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL
 SPACE IS MORE THAN 6 FT. FROM A RECEPTACLE OUTLET. THIS
 INCLUDES THE DISTANCE FROM THE EDGE OF THE WALL.
 7. FBC-RE3901.2.2 NEC 210.52 (A)(2) WALL SPACE. ANY
 WALL SPACE 2 FT. OR MORE IN WIDTH SHALL REQUIRE A
 RECEPTACLE. THIS APPLIES TO WALL SPACE BETWEEN BATHROOM
 AND CLOSET.
 8. FBC-RE3905.8 NEC 314.27(D) PADDLE FANS. BOXES USED
 FOR THE SOLE SUPPORT OF CEILING FANS SHALL BE MARKED BY
 THE MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND
 INDICATE THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED
 TO SUPPORT PADDLE FANS HEAVIER THAN 70 LBS. THIS CAN BE
 ADDRESSED WITH A BLOCK NOTE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2018-01-29 Cont ID  
Sent By jgomez Date 2018-01-29 Time 09:10 Rev Time 0.00
Received By jgomez Date 2018-01-29 Time 08:46 Sent To  
Notes
2018-01-29 08:44:36CHRIS POONAI TO: JGOMEZ 01/26/2018 11:46 AM
  
 FROM: CHRIS POONAI
  
 TO: [email protected]
  
 HELLO MR. GOMEZ,
 THIS EMAIL IS TO REQUEST YOU TO APPROVE THE BUILDING
 PERMIT AND THE AIR CONDITIONING WILL BE DONE WITH A
 SEPARATE PERMIT AS THIS IS HOLDING THE MASTER PERMIT
 UP.
 LET ME KNOW IF YOU HAVE ANY QUESTIONS.
  
 REGARDS
 CHRIS
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-01-19 Cont ID  
Sent By jgomez Date 2018-01-19 Time 17:23 Rev Time 0.00
Received By jgomez Date 2018-01-09 Time 13:21 Sent To I
Notes
2018-01-10 13:21:56RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-11-21 Cont ID  
Sent By jgomez Date 2017-11-21 Time 15:00 Rev Time 0.00
Received By jgomez Date 2017-11-13 Time 12:54 Sent To I
Notes
2017-11-13 12:54:48RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-06-30 Cont ID  
Sent By jleahy Date 2017-06-30 Time 09:58 Rev Time 0.00
Received By jleahy Date 2017-06-14 Time 11:23 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-21 Cont ID  
Sent By rlecky Date 2017-02-21 Time 13:19 Rev Time 0.00
Received By rlecky Date 2017-02-07 Time 14:35 Sent To  
Notes
2017-02-08 14:36:25R19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-14 Cont ID  
Sent By cpuell Date 2016-10-14 Time 08:38 Rev Time 0.00
Received By cpuell Date 2016-08-26 Time 10:28 Sent To  
Notes
2016-08-29 10:28:40R17
 *TRAVELLING WITH 16081109*

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2017-11-20 Cont ID  
Sent By jgomez Date 2017-11-20 Time 15:41 Rev Time 0.00
Received By jgomez Date 2017-11-20 Time 15:24 Sent To  
Notes
2017-11-20 15:43:19$180.65 PAID. MU-2016-031146.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2017-06-29 Cont ID  
Sent By jgomez Date 2017-06-29 Time 16:23 Rev Time 0.00
Received By jgomez Date 2017-06-29 Time 07:02 Sent To  
Notes
2017-06-29 16:23:201- PROVIDE COPY OF PAID RECEIPT. $180.65 DUE.
 MU-2016-31146.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-02-14 Cont ID  
Sent By jgomez Date 2017-02-14 Time 18:38 Rev Time 0.00
Received By jgomez Date 2017-02-14 Time 18:38 Sent To  
Notes
2017-02-14 18:40:181- PROVIDE COPY OF PAID RECEIPT. $180.65 DUE.
 MU-2016-31146.
  
 NOTE:
 THERE IS A CONFLICT WITH PERMIT #14100767 AND PLANS
 SUBMITTED NOW FOR THE BEDROOM ADDITION. PERMIT
 #14100767 WAS FOR AN STORAGE ROOM. PLANS SUBMITTED NOW
 INDICATE THAT THIS AREA IS LIVABLE AREA (NO STORAGE).
 IN 2014 PERMIT APPLICATION AND PLANS WERE SUBMITTED TO
 RE-OPEN EXPIRED PERMIT #99120889. PERMIT #14100767 WAS
 NEVER ISSUED. IT WAS ABANDONED. NEED TO INVESTIGATE IF
 THE WORK WAS DONE. THERE ARE NO PERMITS OR INSPECTIONS
 FOR THE WORK IN THIS AREA. FEES FOR WORK WITHOUT PERMIT
 MAY APPLY.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-09-16 Cont ID  
Sent By jgomez Date 2016-09-16 Time 11:41 Rev Time 0.00
Received By jgomez Date 2016-09-16 Time 11:17 Sent To  
Notes
2016-09-16 11:41:211- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
 NOTE: THIS MAY BE DONE LATER WHEN PERMIT IS READY TO BE
 ISSUED.
  

Review Stop M MECHANICAL (A/C)
Rev No 6 Status N Date 2018-01-29 Cont ID  
Sent By jgomez Date 2018-01-29 Time 08:45 Rev Time 0.00
Received By jgomez Date 2018-01-29 Time 07:54 Sent To  
Notes
2018-01-29 08:46:15CHRIS POONAI TO: JGOMEZ 01/26/2018 11:46 AM
  
 FROM: CHRIS POONAI
  
 TO: [email protected]
  
 HELLO MR. GOMEZ,
 THIS EMAIL IS TO REQUEST YOU TO APPROVE THE BUILDING
 PERMIT AND THE AIR CONDITIONING WILL BE DONE WITH A
 SEPARATE PERMIT AS THIS IS HOLDING THE MASTER PERMIT
 UP.
 LET ME KNOW IF YOU HAVE ANY QUESTIONS.
  
 REGARDS
 CHRIS
  
  
  
 MECHANICAL REVIEW PROVISO:
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS UNDER
 A SEPARATE PERMIT.
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2018-01-19 Cont ID  
Sent By jgomez Date 2018-01-19 Time 17:24 Rev Time 0.00
Received By jgomez Date 2018-01-19 Time 17:24 Sent To  
Notes
2018-01-19 17:25:54RESIDENTIAL (R3) ADDITION/ALTERATION FIFTH MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS (2
 COPIES) AS REQUIRED BY SEC. R403.6.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 NOTE: ONLY THE SUMMARY SHEET WAS SUBMITTED. NEED TO
 PROVIDE COMPLETE CALCULATIONS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
  
 2- THE EQUIPMENT LISTED IN THE CALCULATIONS SUBMITTED
 DOESN'T COMPLY WITH SEC. R403.6.1.1 FBC-ENERGY
 CONSERVATION. "THE CORRESPONDING LATENT CAPACITY OF THE
 EQUIPMENT SHALL NOT BE LESS THAN THE CALCULATED LATENT
 LOAD". REVISE EQUIPMENT AS REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
  
 3- EQUIPMENT CALCULATIONS SUBMITTED ARE MISSING THE
 PUBLISHED AHRI REFERENCE. SEC.R403.6.1.1 FBC-ENERGY
 CONSERVATION. PROVIDE THE AHRI NUMBER.
  
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2017-11-21 Cont ID  
Sent By jgomez Date 2017-11-21 Time 15:00 Rev Time 0.00
Received By jgomez Date 2017-11-21 Time 15:00 Sent To I
Notes
2017-11-21 15:01:47RESIDENTIAL (R3) ADDITION/ALTERATION FOURTH MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
  
 NOTE:
 MECHANICAL REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT CONTRACTOR WILL SUBMIT REQUIRED INFORMATION
 PRIOR TO INSPECTIONS TO AVOID CONFLICTS/DELAYS.
 REVISION FEES MAY APPLY. CONTRACTOR TO ADVICE IF THE
 PROVISO OPTION IS PREFERRED AT THIS TIME.
  
  
  
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS (2
 COPIES) AS REQUIRED BY SEC. R403.6.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 NOTE: ONLY THE SUMMARY SHEET WAS SUBMITTED. NEED TO
 PROVIDE COMPLETE CALCULATIONS.
  
 2- THE EQUIPMENT LISTED IN THE CALCULATIONS SUBMITTED
 DOESN'T COMPLY WITH SEC. R403.6.1.1 FBC-ENERGY
 CONSERVATION. "THE CORRESPONDING LATENT CAPACITY OF THE
 EQUIPMENT SHALL NOT BE LESS THAN THE CALCULATED LATENT
 LOAD". REVISE EQUIPMENT AS REQUIRED.
  
 3- EQUIPMENT CALCULATIONS SUBMITTED ARE MISSING THE
 PUBLISHED AHRI REFERENCE. SEC.R403.6.1.1 FBC-ENERGY
 CONSERVATION. PROVIDE THE AHRI NUMBER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-06-29 Cont ID  
Sent By jgomez Date 2017-06-29 Time 16:25 Rev Time 0.00
Received By jgomez Date 2017-06-29 Time 16:25 Sent To  
Notes
2017-06-29 16:33:28RESIDENTIAL (R3) ADDITION/ALTERATION THIRD MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS (2
 COPIES) AS REQUIRED BY SEC. R403.6.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 NOTE: ONLY THE SUMMARY SHEET WAS SUBMITTED. NEED TO
 PROVIDE COMPLETE CALCULATIONS.
  
 2- THE EQUIPMENT LISTED IN THE CALCULATIONS SUBMITTED
 DOESN'T COMPLY WITH SEC. R403.6.1.1 FBC-ENERGY
 CONSERVATION. "THE CORRESPONDING LATENT CAPACITY OF THE
 EQUIPMENT SHALL NOT BE LESS THAN THE CALCULATED LATENT
 LOAD". REVISE EQUIPMENT AS REQUIRED.
  
 3- EQUIPMENT CALCULATIONS SUBMITTED ARE MISSING THE
 PUBLISHED AHRI REFERENCE. SEC.R403.6.1.1 FBC-ENERGY
 CONSERVATION. PROVIDE THE AHRI NUMBER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-02-15 Cont ID  
Sent By jgomez Date 2017-02-15 Time 16:08 Rev Time 0.00
Received By jgomez Date 2017-02-15 Time 07:45 Sent To  
Notes
2017-02-15 16:10:15RESIDENTIAL (R3) ADDITION/ALTERATION SECOND MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS (2 COPIES) AS
 REQUIRED BY SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
 NOTE: EQUIPMENT LISTED ON THE EQUIPMENT SIZING
 CALCULATIONS TO MATCH EQUIPMENT SHOWN ON-PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-09-20 Cont ID  
Sent By jgomez Date 2016-09-20 Time 15:57 Rev Time 0.00
Received By jgomez Date 2016-09-20 Time 15:56 Sent To Z
Notes
2016-09-20 16:00:27RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS (2 COPIES) AS
 REQUIRED BY SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-06-29 Cont ID  
Sent By jgomez Date 2017-06-29 Time 15:16 Rev Time 0.00
Received By jgomez Date 2017-06-29 Time 15:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-02-15 Cont ID  
Sent By jgomez Date 2017-02-15 Time 16:04 Rev Time 0.00
Received By jgomez Date 2017-02-15 Time 07:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-09-20 Cont ID  
Sent By jgomez Date 2016-09-20 Time 15:56 Rev Time 0.00
Received By jgomez Date 2016-09-20 Time 15:50 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status P Date 2018-01-19 Cont ID  
Sent By jgomez Date 2018-01-19 Time 17:22 Rev Time 0.00
Received By jgomez Date 2018-01-19 Time 17:22 Sent To  
Notes
2018-01-19 17:23:42FLAT ROOF NOA 14-0529.02 FROM CERTAIN TEED.

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2017-11-21 Cont ID  
Sent By jgomez Date 2017-11-21 Time 14:59 Rev Time 0.00
Received By jgomez Date 2017-11-21 Time 14:58 Sent To  
Notes
2017-11-21 14:59:591- FLAT ROOF NOA 14-1030.02 SUBMITTED:
 A) CLEARLY MARK SPECIFIC APPROVED ASSEMBLY TO BE
 INSTALLED TO VERIFY COMPLIANCE WIT THE DESIGN PRESSURES
 OF SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2
 COPIES) AS REQUIRED BY GENERAL LIMITATION # 7 ON LAST
 PAGE OF NOA SUBMITTED. REQUIRED TO MEET THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2017-06-29 Cont ID  
Sent By jgomez Date 2017-06-29 Time 16:24 Rev Time 0.00
Received By jgomez Date 2017-06-29 Time 16:24 Sent To  
Notes
2017-06-29 16:25:021- FLAT ROOF NOA 14-1030.02 SUBMITTED:
 A) CLEARLY MARK SPECIFIC APPROVED ASSEMBLY TO BE
 INSTALLED TO VERIFY COMPLIANCE WIT THE DESIGN PRESSURES
 OF SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2
 COPIES) AS REQUIRED BY GENERAL LIMITATION # 7 ON LAST
 PAGE OF NOA SUBMITTED. REQUIRED TO MEET THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2017-02-15 Cont ID  
Sent By jgomez Date 2017-02-15 Time 16:06 Rev Time 0.00
Received By jgomez Date 2017-02-15 Time 16:06 Sent To  
Notes
2017-02-15 16:06:431- FLAT ROOF NOA 14-1030.02 SUBMITTED:
 A) CLEARLY MARK SPECIFIC APPROVED ASSEMBLY TO BE
 INSTALLED TO VERIFY COMPLIANCE WIT THE DESIGN PRESSURES
 OF SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2
 COPIES) AS REQUIRED BY GENERAL LIMITATION # 7 ON LAST
 PAGE OF NOA SUBMITTED. REQUIRED TO MEET THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-09-16 Cont ID  
Sent By jgomez Date 2016-09-16 Time 17:11 Rev Time 0.00
Received By jgomez Date 2016-09-16 Time 16:58 Sent To  
Notes
2016-09-16 17:11:411- FLAT ROOF NOA 14-1030.02 SUBMITTED:
 A) CLEARLY MARK SPECIFIC APPROVED ASSEMBLY TO BE
 INSTALLED TO VERIFY COMPLIANCE WIT THE DESIGN PRESSURES
 OF SEC. R301.1 FBC-RESIDENTIAL.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2
 COPIES) AS REQUIRED BY GENERAL LIMITATION # 7 ON LAST
 PAGE OF NOA SUBMITTED. REQUIRED TO MEET THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2017-11-15 Cont ID  
Sent By ajones Date 2017-11-15 Time 13:17 Rev Time 0.00
Received By ajones Date 2017-11-14 Time 12:00 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2017-06-16 Cont ID  
Sent By jleahy Date 2017-06-30 Time 09:58 Rev Time 0.00
Received By njwira Date 2017-06-15 Time 14:29 Sent To M
Notes
2017-06-16 14:56:27MUST PROVIDE TWO(2)COPIES OF A SURVEY SHOWING THAT THE
 ADDITION MEETS SETBACKS. CURRENT SURVEY SHOWS EXISTING
 SHOW HOW FAR ADDITION WILL BE FROM THE PROPERTY LINES
  
  
 PLEASE CONTACT
 NATHAN WIRA- ZONING TECHNICIAN
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING
 DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST.
 WEST PALM BEACH, FL 33402
 OFFICE HOURS: M-F 8AM - 5PM
 (561)822-1442
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2017-02-16 Cont ID  
Sent By njwira Date 2017-02-16 Time 15:57 Rev Time 0.00
Received By njwira Date 2017-02-16 Time 14:46 Sent To  
Notes
2017-02-16 15:58:152/16/17- FAILED
  
 PLEASE INDICATE WHERE ADDITION IS GOING ON THE SURVEY.
  
  
 PLEASE CONTACT
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING
 DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST.
 WEST PALM BEACH, FL 33402
 OFFICE HOURS: M-F 8AM - 5PM
 (561)822-1442
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-09-22 Cont ID  
Sent By awooten Date 2016-09-22 Time 16:55 Rev Time 0.00
Received By njwira Date 2016-09-21 Time 13:59 Sent To I
Notes
2016-09-22 16:54:329/22/16- FAILED
  
 PLEASE PROVIDE A SITE PLAN OR SURVEY SHOWING WHERE THIS
 IS GOING ON THE PROPERTY.
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  