Plan Review Details - Permit 16080985
Plan Review Stops For Permit 16080985
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-09-09 Cont ID  
Sent By ccole Date 2016-09-09 Time 12:18 Rev Time 0.00
Received By ccole Date 2016-09-06 Time 16:38 Sent To  
Notes
2016-09-06 16:38:54CCOLE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-06 Cont ID  
Sent By ccole Date 2016-09-06 Time 10:27 Rev Time 0.00
Received By ccole Date 2016-09-01 Time 10:47 Sent To  
Notes
2016-09-02 10:48:08RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-25 Cont ID  
Sent By ccole Date 2016-08-25 Time 07:17 Rev Time 0.00
Received By ccole Date 2016-08-23 Time 11:03 Sent To  
Notes
2016-08-24 11:04:43REVISION ROUTED TO CCOLE

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-09-09 Cont ID  
Sent By ccole Date 2016-09-09 Time 12:05 Rev Time 0.00
Received By ccole Date 2016-09-09 Time 12:05 Sent To  
Notes
2016-09-09 12:11:304TH REVIEW FBC-2014 MECHANICAL
 PERMIT #16080985
 9/9/16
  
 1) PLANS MUST BE SUBMITTED IN DUPLICATE SETS- ONLY ONE
 MECHANICAL PLAN SHEET WAS SUBMITTED.
  
 2) THE PLANS MUST BEAR THE NAME AND SIGNATURE OF THE AC
 CONTRACTOR WHO PREPARED THEM- SECTION 107.2.1 WPB
 AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-09-06 Cont ID  
Sent By ccole Date 2016-09-06 Time 10:26 Rev Time 0.00
Received By ccole Date 2016-09-06 Time 10:26 Sent To  
Notes
2016-09-06 10:31:222ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16080985
 9/6/16
  
 COMMENTS FROM THE 1ST REVIEW (PRINTED BELOW ) WITH THE
 EXCEPTION OF #6 STILL EXIST. ASTRO AIR'S TITLE BLOCK
 HAS BEEN REMOVED FORM THE NEW PLANS HOWEVER, NO
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN IS
 SHOWN ON THE NEW PLANS
  
 1) THE SELECTED AC SYSTEM SHOWN ON THE PLAN IS A
 GOODMAN PACKAGED UNIT SUITABLE FOR OUTDOOR USE ONLY.
 THE ORIGINAL APPROVED PLAN (PERMIT #16020067) CALLED
 FOR REPLACEMENT OF A WATER COOLED HEAT PUMP. IT APPEARS
 THAT THE NEW AC INFORMATION IS A MISTAKE, HOWEVER IF
 THE PACKAGED UNIT IS TO BE INSTALLED, PLEASE PROVIDE
 THE FOLLOWING DETAILS ON THE PLAN: A) SHOW THE LOCATION
 OF THE PROPOSED UNIT AND PROVIDE INSTALLATION DETAILS
 INCLUDING WIND LOAD ENGINEERING PER SECTION 301.15. B)
 PROVIDE A REVISED DUCT LAYOUT PLAN THAT SHOWS THE MAIN
 SUPPLY AND RETURN CONNECTIONS TO THE UNIT. C) PROVIDE A
 CONDENSATE DISPOSAL PLAN.
  
 2) THIS REVISED PLAN APPEARS TO BE REPLACING THE
 ORIGINAL PLAN SUBMITTED UNDER #16020067, HOWEVER SOME
 OF THE INFORMATION ON THE ORIGINAL HAS NOT BEEN PLACED
 ON THE REVISED PLAN, AND NO CLOUDS OR DELTA SYMBOLS ARE
 SHOWN ON THE DRAWINGS TO HIGHLIGHT THE CHANGES. PLEASE
 PROVIDE A COMPLETELY REVISED PLAN.
  
 3) PROVIDE THE SIZE OF THE NEW DUCT IN THE LIVING ROOM,
 AND THE DUCT SIZES IN THE BEDROOMS CONNECTING THE NEW
 DIFFUSERS.
  
 4) PROVIDE A MEANS OF RETURN AIR FROM THE BEDROOMS.
  
 5) FLORIDA ENERGY CONSERVATION CODE-2014: PLEASE REVIEW
 SECTIONS C403.2.7.2 FOR MECHANICAL CLOSET REQUIREMENTS,
 AND SECTION C403.2.7.3.3 FOR REQUIRED SPACE AROUND THE
 AIR HANDLER IN THE MECHANICAL CLOSET. REVISE THE PLANS
 ACCORDINGLY.
  
 6) PLEASE REMOVE THE ASTROAIR TITLE BLOCK FROM THE PLAN
 IF THEY ARE NOT THE CONTRACTOR ON THE PROJECT. REFER TO
 SECTION 107.2.1 WPB AMENDMENTS TO THE FBC: THE
 SUBMITTED PLAN SHALL BEAR THE SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-25 Cont ID  
Sent By ccole Date 2016-08-25 Time 07:17 Rev Time 0.00
Received By ccole Date 2016-08-24 Time 17:14 Sent To  
Notes
2016-08-25 07:40:081ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16080985
 8/25/16
  
 1) THE SELECTED AC SYSTEM SHOWN ON THE PLAN IS A
 GOODMAN PACKAGED UNIT SUITABLE FOR OUTDOOR USE ONLY.
 THE ORIGINAL APPROVED PLAN (PERMIT #16020067) CALLED
 FOR REPLACEMENT OF A WATER COOLED HEAT PUMP. IT APPEARS
 THAT THE NEW AC INFORMATION IS A MISTAKE, HOWEVER IF
 THE PACKAGED UNIT IS TO BE INSTALLED, PLEASE PROVIDE
 THE FOLLOWING DETAILS ON THE PLAN: A) SHOW THE LOCATION
 OF THE PROPOSED UNIT AND PROVIDE INSTALLATION DETAILS
 INCLUDING WIND LOAD ENGINEERING PER SECTION 301.15. B)
 PROVIDE A REVISED DUCT LAYOUT PLAN THAT SHOWS THE MAIN
 SUPPLY AND RETURN CONNECTIONS TO THE UNIT. C) PROVIDE A
 CONDENSATE DISPOSAL PLAN.
  
 2) THIS REVISED PLAN APPEARS TO BE REPLACING THE
 ORIGINAL PLAN SUBMITTED UNDER #16020067, HOWEVER SOME
 OF THE INFORMATION ON THE ORIGINAL HAS NOT BEEN PLACED
 ON THE REVISED PLAN, AND NO CLOUDS OR DELTA SYMBOLS ARE
 SHOWN ON THE DRAWINGS TO HIGHLIGHT THE CHANGES. PLEASE
 PROVIDE A COMPLETELY REVISED PLAN.
  
 3) PROVIDE THE SIZE OF THE NEW DUCT IN THE LIVING ROOM,
 AND THE DUCT SIZES IN THE BEDROOMS CONNECTING THE NEW
 DIFFUSERS.
  
 4) PROVIDE A MEANS OF RETURN AIR FROM THE BEDROOMS.
  
 5) FLORIDA ENERGY CONSERVATION CODE-2014: PLEASE REVIEW
 SECTIONS C403.2.7.2 FOR MECHANICAL CLOSET REQUIREMENTS,
 AND SECTION C403.2.7.3.3 FOR REQUIRED SPACE AROUND THE
 AIR HANDLER IN THE MECHANICAL CLOSET. REVISE THE PLANS
 ACCORDINGLY.
  
 6) PLEASE REMOVE THE ASTROAIR TITLE BLOCK FROM THE PLAN
 IF THEY ARE NOT THE CONTRACTOR ON THE PROJECT. REFER TO
 SECTION 107.2.1 WPB AMENDMENTS TO THE FBC: THE
 SUBMITTED PLAN SHALL BEAR THE SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  