| 2016-08-30 13:30:49 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | COMMENTS: |
| | |
| | 1. PLEASE NOTE THAT PER FBC 105.3.1.2(5)- FLORIDA |
| | STATUE 471.003(2)(H) AN ELECTRICAL CONTRACTOR CANNOT |
| | DESIGN ELECTRICAL SERVICE AS VOLTAGE IS ABOVE 240V. |
| | RISER SHOWS A 3PHASE 240V (480V PHASE TO PHASE. PLANS |
| | TO BE DESIGN BY ENGINEER FOR THIS PROJECT. |
| | 2. PLEASE SHOW AIC CALCULATION BASED ON INFORMATION |
| | PROVIDED BY FPL UTILITY FOR APPROVAL. NEC 110.24 FBC |
| | 107. LABEL EQUIPMENT AIC RATINGS. |
| | 3. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO |
| | INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC |
| | 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE |
| | VERBIAGE IN CODE. |
| | 4. LABEL SERVICE EQUIPMENT TO BE RATED FOR SERVICE |
| | ENTRANCE. NEC 230.66 |
| | 5. CLARIFY GENERATOR RECEPTACLE SHOWN. WILL THERE BE A |
| | PERMANENT GENERATOR INSTALLED, PLEASE CLARIFY. FBC |
| | 107.3.5 |
| | 6. NEUTRAL CONDUCTOR BROUGHT TO SERVICE IS REDUCED. |
| | PROVIDE A NEUTRAL CALCULATION REGARDLESS OF LOAD OR |
| | SHOW UPSIZED. |
| | 7. PROVIDE A WP/GFCI RECEPTACLE AT THE SERVICE. NEC |
| | 590.6 |
| | 8. SHOW AN INTERSYSTEM BONDING TERMINAL PER NEC 250.94 |
| | 9. SHOW CONDUIT AND CONDUCTOR SIZE TO PUMPS AND FROM |
| | METER TO MAIN DISCONNECTS. FBC 107.3.5 |
| | 10. HIGH LEG MARKINGS TO BE PROVIDED PER NEC 110.15 AND |
| | 408.3F1 PROVIDE NOTE ON RISER DIAGRAM |
| | 11. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL |
| | FREE TO CONTACT ME SHOULD YOU HAVE ANY |
| | |
| | |
| | VALENTINO PEREZ |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6717 |
| | [email protected] |
| | |