Plan Review Details - Permit 16080942
Plan Review Stops For Permit 16080942
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-12-21 Cont ID  
Sent By jwitmer Date 2016-12-21 Time 08:43 Rev Time 0.00
Received By jwitmer Date 2016-12-21 Time 08:38 Sent To  
Notes
2016-12-21 08:43:09BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080942
 ADD: 1551 N. FLAGLER DR. SUITE # CU01
 CONT: BUTLER CONSTRUCTION CO.
 TEL: 561-832-9700
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: WED. DEC. 21/2016
 ACTION: BUILDING PROVISO
  
 1) PROVISO: 110.3.7.4.3 ALL SHORING AND RESHORING
 PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE
 ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND
 RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED
 AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 2) BUILDING PROVISO: DEFERRED SUBMITTAL. 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS/ MULLIONS
 (C) PANEL WALLS: STOREFRONTS,
  
 3) PROVISO: DEFERRED SUBMITTAL. AT CONTRACTORS OWN
 RISK!!! NANA WALL SYSTEM (DOOR) ARE REQUIRED TO BE
 TESTED FOR WATER INFILTRATION SEE FBC-B 1710.5.1.1
 EXCEPTION # 2.
  
  
 4) DEFERRED SUBMITTALS. FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-12-09 Cont ID  
Sent By jwitmer Date 2016-12-09 Time 10:57 Rev Time 0.00
Received By jwitmer Date 2016-12-09 Time 08:38 Sent To  
Notes
2016-12-09 10:57:20BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080942
 ADD: 1551 N. FLAGLER DR. SUITE # CU01
 CONT: BUTLER CONSTRUCTION CO.
 TEL: 561-832-9700
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: FRI. DEC. 09/2016
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) THRESHOLD BUILDING. THRESHOLD BUILDING / FL S. S.
 553.71(7).
  
 2A) COMPLIED. 109.3.6.1 THRESHOLD INSPECTION PLAN.
  
 2B)2ND REQUEST. SEMI-COMPLIED. THRESHOLD INSPECTOR: WPB
 AMENDMENT 109.3.6.2 W.P.B. THE THRESHOLD INSPECTION
 FORMS ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
 PLEASE NOTE SHEETS 1-3 OF THE THRESHOLD INSPECTION
 AGREEMENT WERE SUBMITTED. MISSING SIGNATURE FORMS PAGES
 4 & 5.
  
 2C)COMPLIED.: W.P.B. AMENDMENT 110.3.7.4. 633 FLORIDA
 STATUTE.
  
 2D) COMPLIED. INSPECTOR RESUME'.
  
 2E) 3RD REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2F) INFORMATIONAL. FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE
 PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN
 E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU
 MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE
 PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE
 OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO
 PRINT MAYBE IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 2G) PROVISO: 110.3.7.4.3 ALL SHORING AND RESHORING
 PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE
 ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND
 RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED
 AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 2H) INFORMATIONAL. PLEASE CALL THE CITY OF WEST PALM
 BEACHS AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN
 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 2I) INFORMATIONAL. 109.3.6 THRESHOLD BUILDINGS,
 OPERATING GUIDELINES FOR THRESHOLD INSPECTORS #26.
 ASSURE THAT THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
 3-5) COMPLIED
  
 6A) BUILDING PROVISO: DEFERRED SUBMITTAL. 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS/ MULLIONS
 (C) PANEL WALLS: STOREFRONTS,
  
 6B) PROVISO: DEFERRED SUBMITTAL. AT CONTRACTORS OWN
 RISK!!! NANA WALL SYSTEM (DOOR) ARE REQUIRED TO BE
 TESTED FOR WATER INFILTRATION SEE FBC-B 1710.5.1.1
 EXCEPTION # 2.
  
  
 7) DEFERRED SUBMITTALS. FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-10-25 Cont ID  
Sent By jwitmer Date 2016-10-25 Time 14:35 Rev Time 0.00
Received By jwitmer Date 2016-10-25 Time 10:07 Sent To  
Notes
2016-10-25 14:35:00BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080942
 ADD: 1551 N. FLAGLER DR. SUITE # CU01
 CONT: BUTLER CONSTRUCTION CO.
 TEL: 561-832-9700
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. OCT. 25/2016
 ACTION: DENIED
  
 1) SHEET 002_LS-ALS1.0:
 1A) COMPLIED.
  
 1B) THE SUBMITTED SURVEY IS DATED 08/08/2002 DOES NOT
 REFLECT THE CURRENT BUILDING CONFIGURATION ON THE LOT.
 THE SURVEY SHOWS A SALES TRAILER, PARKING LOT AND CHAIN
 LINK FENCE SURROUNDING THE PROPERTY. THE SURVEY IS NOT
 SIGNED NOR SEALED BY A FLORIDA LICENSED SURVEYOR.
 THE SECOND ISSUE IS THE REQUEST FOR A CURRENT ELEVATION
 CERTIFICATE. THE FORM SUBMITTED IS THE STANDARD FLOOD
 HAZARD DETERMINATION FORM (SFHDF). THE CURRENT
 ELEVATION FORM (FORM OMB NO. 1660-0008/ EXPIRATION
 DATE: NOV. 30/ 2018) IS 6 PAGES IN LENGTH.
  
 1ST ROUND COMMENTS. PLEASE PROVIDE A SURVEY OF THE
 PROPERTY WITH THE FLOOD ZONE DELINEATION LINES SHOWN.
 THE PROPERTY APPRAISERS WEB SITE SHOWS THEA5 FLOOD
 DELINEATION LINE CUTTING THROUGH THE BUILDING. THE
 CITIES FLOOD MAPS SHOW THE DELINEATION LINE DEFINITELY
 ON THE PROPERTY. IF THE SURVEY SHOWS ANY OF THE
 BUILDING BEING LOCATED IN THE A5 FLOOD ZONE THEN FLOOD
 ELEVATION CERTIFICATES WILL BE REQUIRED.
  
 FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION
 (FREEBOARD).
  
 THE RESPONSE INDICATES THE EXISTING FLOOR IS AT AN
 ELEVATION OF 8 FEET. NEW AREAS OF THE PROPOSED SLAB TO
 BE FINISHED AT THE SAME LEVEL, SHEET 003_A1.01. NOR
 014_S-2 SHOW IF THE 8 FEET IS VERTICAL DATUM OF NGVD
 1929 OR NAVD 1988. 3 FLOOD ELEVATION CERTIFICATES WILL
 BE REQUIRED.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED
 FINISH FLOOR HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD
 ZONE CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL
 EXTERIOR ATTENDANTS A/C PADS OR OTHER SLABS FOR
 GENERATORS
 FEMA NEW FORM AVAILABLE JUNE 13/2016.
 OMB NO. 1660-0008
 EXPIRATION DATE: NOV. 30/2018
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 2) SHEET S1 & S2 SHOW THERE IS STRUCTURAL WORK INVOLVED
 AND THIS IS A HIGH-RISE BUILDING MEETING THE DEFINITION
 FOR A THRESHOLD BUILDING. THRESHOLD BUILDING / FL S. S.
 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
  
 2A) 2ND REQUEST. 109.3.6.1 THRESHOLD INSPECTION PLAN.
 THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED)
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 2B)2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE
 THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT
 BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO
 THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT
 ISSUANCE WILL TAKE PLACE.
  
 2C)2ND REQUEST. THRESHOLD BLDG., REQUIRED STATEMENT:
 W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 2D) 2ND REQUEST. UNTIL FORMS ARE FILLED OUT 100%
 SUBMITTED FOR REVIEW AND APPROVAL THIS COMMENT STANDS.
 FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME'
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 2E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2F)INFORMATIONAL. FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE
 PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN
 E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU
 MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE
 PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE
 OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO
 PRINT MAYBE IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 2G) 2ND REQUEST. 110.3.7.4.3 ALL SHORING AND RESHORING
 PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE
 ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND
 RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED
 AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 2H) INFORMATIONAL. PLEASE CALL THE CITY OF WEST PALM
 BEACHS AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN
 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 2I) INFORMATIONAL. 109.3.6 THRESHOLD BUILDINGS,
 OPERATING GUIDELINES FOR THRESHOLD INSPECTORS #26.
 ASSURE THAT THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
 3A) 2ND REQUEST . SHEET 013_S-1 DETAILS 1&2 SHOW THE
 NEW CONCRETE COLUMNS AND BEAM. THE DETAIL ALSO SHOWS A
 NEW L* X 4 ? INCH ANGLE THAT BOLTS INTO THE POST
 TENSIONED SLAB AND NEW BEAM. THE QUESTION IS DOES THE
 STEEL (REBAR) IN THE COLUMNS AND BEAM CONTINUE OR IS IT
 CUT OFF WHERE THE CONCRETE IS CUT, HOW IS LAP
 DEVELOPED? ACI 318 2.7 DEVELOPMENT AND SPLICES OF
 REINFORCING.
 1ST ROUND OF COMMENTS. THERE ARE ONLY 2 STRUCTURAL
 SHEETS, 013_S-1 & 014_S-2. PLEASE NOTE THERE ARE NO
 DEMOLITION SHEETS SHOWING WHAT STRUCTURAL MEMBERS ARE
 BEING REMOVED NOR HOW WHEN REMOVING THE STRUCTURAL
 BEAM, HOW TO HANDLE THE EXISTING BEAM STEEL, IS IT TO
 BE CUT, IS IT TO BE SAVED FOR THE PROPER LAPS REQUIRED
 FOR THE BEAM? ACI 318 2.7 DEVELOPMENT AND SPLICES OF
 REINFORCING.
  
 3B) COMPLIED.
  
 4) COMPLIED. SHEET 013_S-1 UNDER THE WIND DESIGN
 CRITERIA THE PLANS LIST THIS AS AN C EXPOSURE, YOU CAN
 SHOOT A VECTOR OUT TO THE NNE OVER WATER FOR 5,822 FEET
 BEFORE HITTING LAND AND A VECTOR TO THE SSE FOR 6,363
 FEET OVER WATER UNTIL YOU HIT LAND. THIS QUALIFIES THE
 EXPOSURE TO BE CONSIDERED AN D EXPOSURE. SEE THE 2014
 FBC-B 1609.4.2 EXPOSURE D. EXPOSURE D SHALL APPLY WHERE
 THE GROUND SURFACE ROUGHNESS, AS DEFINED BY SURFACE
 ROUGHNESS D, PREVAILS IN THE UPWIND DIRECTION FOR A
 DISTANCE OF AT LEAST 5,000 FEET (1524 M) OR 20 TIMES
 THE HEIGHT OF THE BUILDING, WHICHEVER IS GREATER.
  
 5) 2ND REQUEST. THE QH(ULT)= 68.1
 QH(ALL.)= 40.9
 PLEASE NOTE THE MEAN ROOF HEIGHT IS NOT GIVEN NOR AT
 WHAT SQUARE FOOTAGE THESE PRESSURES ARE TAKEN. PLEASE
 PROVIDE THE SQ. FT. AND HEIGHT OF THE BUILDING THESE
 PRESSURES ARE FOR. PRESSURES TAKEN AT 15 FT/ FOR 10 SQ.
 FT. EXPOSURE D -49.92 VASD /NEGATIVE PRESSURE FOR 100
 SQ. FT. @15 FT. ELE. EXPOSURE D ARE -43.04 VASD. PLEASE
 NOTE THE NEGATIVE PRESSURES ARE SUPPOSED TO BE TAKEN
 FROM THE ROOF LINE(QH), THE POSITIVE PRESSURES THE
 HEIGHT ABOVE GRADE TO THE OPENING (QZ). PLEASE PROVIDE
 IN A TABLE FORM IN VASD FOR 10, 20, 50 & 100 SQ. FT.
 PLEASE EXPLAIN HOW THESE PRESSURES WERE DERIVED.
  
 1ST ROUND OF COMMENTS. PLEASE PROVIDE THE PRESSURES IN
 VASD SINCE THE PRODUCT APPROVALS ARE IN VASD. PLEASE
 NOTE THE ADJUSTMENT FACTORS TABLE 1609.7.2 FOR HEIGHT
 AND EXPOSURE. PRESSURES ARE TO BE TAKEN FROM ASCE 7-10
 SINCE THE BUILDING IS ABOVE 60 FEET IN HEIGHT.
  
 6A) DEFERRED SUBMITTAL. 2014 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS/ MULLIONS
 (C) PANEL WALLS: STOREFRONTS,
  
 6B)DEFERRED SUBMITTAL. AT CONTRACTORS OWN RISK!!! NANA
 WALL SYSTEM (DOOR) ARE REQUIRED TO BE TESTED FOR WATER
 INFILTRATION SEE FBC-B 1710.5.1.1 EXCEPTION # 2.
  
 6C) COMPLIED.
  
 7) DEFERRED SUBMITTALS. FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 8) COMPLIED.
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-26 Cont ID  
Sent By jwitmer Date 2016-08-26 Time 13:43 Rev Time 0.00
Received By jwitmer Date 2016-08-26 Time 07:15 Sent To  
Notes
2016-08-26 13:43:48BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080942
 ADD: 1551 N. FLAGLER DR. SUITE # CU01
 CONT: BUTLER CONSTRUCTION CO.
 TEL: 561-832-9700
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. AUGUST 26/2016
 ACTION: DENIED
  
 1) SHEET 002_LS-ALS1.0:
 1A) PLEASE NOTE THE CODE ANALYSIS UNDER THE TYPE OF
 CONSTRUCTION LIST THIS AS AN CONSTRUCTION TYPE VB/
 FULLY SPRINKLERED BUILDING. UNDER THE 2014 FBC-B TABLE
 503 FOR A TYPE VB /SPRINKLERED BUILDING WITH THE ONE
 STORY INCREASE THIS TENANT SPACE COULD BE IN A 3 STORY
 BUILDING. PLEASE NOTE GOOGLE EARTH SHOWS THIS TO BE
 WHAT APPEARS TO BE A 14 STORY HIGH-RISE. TABLE 503 FOR
 14 STORY BUILDING FOR A BUSINESS, R2 OR ASSEMBLY
 OCCUPANCIES WOULD ALL REQUIRE THIS BUILDING TO BE A
 CONSTRUCTION TYPE IA.
  
 1B) PLEASE PROVIDE A SURVEY OF THE PROPERTY WITH THE
 FLOOD ZONE DELINEATION LINES SHOWN. THE PROPERTY
 APPRAISERS WEB SITE SHOWS THEA5 FLOOD DELINEATION LINE
 CUTTING THROUGH THE BUILDING. THE CITIES FLOOD MAPS
 SHOW THE DELINEATION LINE DEFINITELY ON THE PROPERTY.
 IF THE SURVEY SHOWS ANY OF THE BUILDING BEING LOCATED
 IN THE A5 FLOOD ZONE THEN FLOOD ELEVATION CERTIFICATES
 WILL BE REQUIRED.
  
 FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED
 FINISH FLOOR HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD
 ZONE CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL
 EXTERIOR ATTENDANTS A/C PADS OR OTHER SLABS FOR
 GENERATORS
 FEMA NEW FORM AVAILABLE JUNE 13/2016.
 OMB NO. 1660-0008
 EXPIRATION DATE: NOV. 30/2018
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 2) SHEET S1 & S2 SHOW THERE IS STRUCTURAL WORK INVOLVED
 AND THIS IS A HIGH-RISE BUILDING MEETING THE DEFINITION
 FOR A THRESHOLD BUILDING. THRESHOLD BUILDING / FL S. S.
 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
  
 2A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
  
 2C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 2D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 2E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2F) FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, PLEASE
 E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING ISSUED,
 THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE APPROVED
 AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS,
 TWO SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1)
 FOR THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE IN BLACK
 & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 2G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 2H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 2I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
 3A) THERE ARE ONLY 2 STRUCTURAL SHEETS, 013_S-1 &
 014_S-2. PLEASE NOTE THERE ARE NO DEMOLITION SHEETS
 SHOWING WHAT STRUCTURAL MEMBERS ARE BEING REMOVED NOR
 HOW WHEN REMOVING THE STRUCTURAL BEAM, HOW TO HANDLE
 THE EXISTING BEAM STEEL, IS IT TO BE CUT, IS IT TO BE
 SAVED FOR THE PROPER LAPS REQUIRED FOR THE BEAM? ACI
 318 2.7 DEVELOPMENT AND SPLICES OF REINFORCING.
  
 3B) THE PLANS ARE SILENT AS TO SHEET 014_S-2 WHERE THE
 NEW NANA WALL SYSTEM IS BEING INSTALLED ARE THE
 EXTERIOR STAIR AND HANDRAIL/ GUARDRAIL SYSTEMS EXISTING
 OR NEW? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) SHEET 013_S-1 UNDER THE WIND DESIGN CRITERIA THE
 PLANS LIST THIS AS AN C EXPOSURE, YOU CAN SHOOT A
 VECTOR OUT TO THE NNE OVER WATER FOR 5,822 FEET BEFORE
 HITTING LAND AND A VECTOR TO THE SSE FOR 6,363 FEET
 OVER WATER UNTIL YOU HIT LAND. THIS QUALIFIES THE
 EXPOSURE TO BE CONSIDERED AN D EXPOSURE. SEE THE 2014
 FBC-B 1609.4.2 EXPOSURE D. EXPOSURE D SHALL APPLY WHERE
 THE GROUND SURFACE ROUGHNESS, AS DEFINED BY SURFACE
 ROUGHNESS D, PREVAILS IN THE UPWIND DIRECTION FOR A
 DISTANCE OF AT LEAST 5,000 FEET (1524 M) OR 20 TIMES
 THE HEIGHT OF THE BUILDING, WHICHEVER IS GREATER.
  
 5) PLEASE PROVIDE THE PRESSURES IN VASD SINCE THE
 PRODUCT APPROVALS ARE IN VASD. PLEASE NOTE THE
 ADJUSTMENT FACTORS TABLE 1609.7.2 FOR HEIGHT AND
 EXPOSURE. PRESSURES ARE TO BE TAKEN FROM ASCE 7-10
 SINCE THE BUILDING IS ABOVE 60 FEET IN HEIGHT.
  
 6A) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS/ MULLIONS
 (C) PANEL WALLS: STOREFRONTS,
  
 6B) NANA WALL SYSTEM (DOOR) ARE REQUIRED TO BE TESTED
 FOR WATER INFILTRATION SEE FBC-B 1710.5.1.1 EXCEPTION #
 2.
  
 6C) PLEASE PROVIDE HOW COMPLIANCE WITH THE 2014 ENERGY
 CODE C401.2.1/ C402.3.
  
 7) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) PLEASE NOTE SHEET 022_LS-ALS1.0 SHOWS STEPS UP TO
 THE NANA DOOR SYSTEM, THIS IS NOT AN ACCESSIBLE
 ENTRANCE, PLEASE PROVIDE SIGNAGE TO THE ACCESSIBLE
 ENTRY. 2014 FBC-ACCESSIBILITY CODE 216.3 DIRECTIONAL
 AND INFORMATIONAL SIGNS. SIGNS THAT PROVIDE DIRECTION
 TO OR INFORMATION ABOUT INTERIOR SPACES AND FACILITIES
 OF THE SITE SHALL COMPLY WITH 703.5.
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-11-01 Cont ID  
Sent By vperez Date 2016-11-01 Time 15:19 Rev Time 0.00
Received By vperez Date 2016-11-01 Time 15:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-30 Cont ID  
Sent By albarran Date 2016-08-30 Time 17:00 Rev Time 0.00
Received By albarran Date 2016-08-30 Time 15:14 Sent To  
Notes
2016-08-30 17:01:16ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 DESCRIPTION: RENO OF EXISTING SPACE TO INCLUDE MEP,
 FIRE ALARM & FIRE SPRINKLERS.
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. CORRECT LIGHTING FIXTURE SCHEDULE DESCRIPTION FOR F1
 FIXTURE.
 2. CORRECT ELECTRICAL SPECIFICATIONS PART 1 NOTE C TO
 READ THE 2011 EDITION OF THE NEC.
 3. CORRECT ELECTRICAL SPECIFICATIONS PART 2 NOTE D. TO
 REMOVE SCH 40 LIMITATION AS THERE ARE CONDITIONS WHICH
 CALL FOR SCH 80.
 4. CORRECT ELECTRICAL SPECIFICATIONS PART 3 NOTE C TO
 READ THE 2011 EDITION OF THE NEC.
 5. PER FBC-EC405.2.1.1 EACH INDIVIDUAL AREA SHALL HAVE
 INDEPENDENT MANUAL OVERRIDE AND/OR OCCUPANCY SENSOR.
 AREAS 104, 103, 101, 106A, 117, 112, 107, 116 ARE
 LACKING THIS.
 6. PER FBC-EC405.2.2.3 DAYLIGHT ZONES SHALL BE
 ESTABLISHED AND LIGHTING CONTROLLED INDEPENDENTLY OF
 GENERAL AREA LIGHTING. CORRECT LIGHTING LAYOUT
 ACCORDINGLY.
 7. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THIS LIGHT
 SHALL NOT BE CONTROLLED BY AUTOMATIC MEANS ONLY. THIS
 PENDANT LIGHT MAY NOT BE AUTOMATICALLY CONTROLLED AND
 SHALL BE SUFFICIENT TO PROVIDE AMPLE LIGHTING TO WORK
 INSIDE THE ELECTRICAL PANELS.
 8. FBC-E 405.7.1: AT THE LEAST 50% OF ALL 125-VOLT, 15-
 AND 20-AMPERE RECEPTACLES SHALL BE AUTOMATICALLY
 CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN
 OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE
 INSTALLED IN MODULAR PARTITIONS. (SEE ASHRAE STANDARD
 90.1)
 9. FIRE ALARM WORK SHALL BE COMPLETED UNDER SEPARATE
 PERMIT AND SUBMITTAL.
 10. FBC-E 405.7.1: AT THE LEAST 50% OF ALL 125-VOLT,
 15- AND 20-AMPERE RECEPTACLES SHALL BE AUTOMATICALLY
 CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN
 OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE
 INSTALLED IN MODULAR PARTITIONS. (SEE ASHRAE STANDARD
 90.1)
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-10-05 Cont ID  
Sent By wjolin Date 2016-10-05 Time 13:55 Rev Time 0.00
Received By wjolin Date 2016-10-05 Time 13:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-08-26 Cont ID  
Sent By wjolin Date 2016-08-26 Time 08:13 Rev Time 0.00
Received By wjolin Date 2016-08-26 Time 08:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-12-21 Cont ID  
Sent By jwitmer Date 2016-12-21 Time 08:43 Rev Time 0.00
Received By jwitmer Date 2016-12-15 Time 16:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-12-09 Cont ID  
Sent By jwitmer Date 2016-12-09 Time 10:57 Rev Time 0.00
Received By jwitmer Date 2016-11-21 Time 17:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-01 Cont ID  
Sent By vperez Date 2016-11-01 Time 15:21 Rev Time 0.00
Received By vperez Date 2016-11-01 Time 15:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status P Date 2016-09-20 Cont ID  
Sent By tklarge Date 2016-09-20 Time 08:22 Rev Time 0.00
Received By tklarge Date 2016-08-22 Time 16:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-10-12 Cont ID  
Sent By ccole Date 2016-10-12 Time 14:27 Rev Time 0.00
Received By ccole Date 2016-10-12 Time 14:27 Sent To  
Notes
2016-10-12 14:29:46MECHANICAL PROVISO
 10/12/16
  
 1) A REVISION TO THE APPROVED PLANS IS REQUIRED TO
 PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE NEW AND
 RELOCATED HEAT PUMPS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-09-07 Cont ID  
Sent By ccole Date 2016-09-07 Time 09:42 Rev Time 0.00
Received By ccole Date 2016-09-07 Time 09:42 Sent To  
Notes
2016-09-07 09:57:551ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16080942
 9/7/16
  
 1) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR
 SYSTEMS OF THE NEW HP-1 EM-072, AND THE RELOCATED
 EM-072- SECTION 606.2.1.
  
 2) VERIFY MINIMUM 10' CLEARANCE FOR THE O/A INTAKES TO
 THE DRIVE OR ROADWAYS- SECTION 401.4.
  
 3) CLARIFYHPOW AIR IS BEING RETURNED TO THE EM-048 HEAT
 PUMP UNIT.
  
 4) PLACE TAGS AT THE RETURN AIR GRILLS.
  
 5) PROVIDE THE FLEX DUCT SIZES ON THE MECHANICAL PLAN,
 OR RELOCATE THE SCHEDULE FROM M6.1 TO M2.1.
  
 6) PROVIDE A WATER PIPING LAYOUT PLAN SHOWING NEW AND
 EXISTING PIPINGS, POINTS OF CONNECTIONS, LOCATIONS AND
 TYPES OF CONTROL VALVES, AND PIPE SIZES AND
 SPECIFICATIONS.
  
 7) PROVIDE A CONDENSATE DISPOSAL PLAN.
  
 7) SUBMIT SPECS AND/OR AN NOA FOR THE GREENHECK WALL
 CAP.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-09-20 Cont ID  
Sent By tklarge Date 2016-09-20 Time 08:22 Rev Time 0.00
Received By tklarge Date 2016-09-20 Time 06:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2016-11-10 Cont ID  
Sent By skennedy Date 2016-11-10 Time 09:49 Rev Time 0.00
Received By skennedy Date 2016-11-10 Time 09:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2016-09-20 Cont ID  
Sent By tklarge Date 2016-09-20 Time 09:59 Rev Time 0.00
Received By tklarge Date 2016-09-20 Time 09:59 Sent To  
Notes
***NONE***