| Plan Review Stops For Permit 16080928 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2017-07-27 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-07-27 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-07-27 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2017-07-27 14:58:04 | 07/27/17 MET WITH ALVIN. NEED TO REVISE ENERGY | | | CALCULATIONS. NEED CORRECT CALCULATIONS, NOT WORST | | | CASE. HE SIGNED OUT ONE COMPLETE SET OF PLANS AND | | | PRODUCT APPROVALS. JG. | | | | | | | | | RESIDENTIAL (R3) CHANGE OF USE/ALTERATION THIRD | | | BUILDING REVIEW CHECKLIST. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- MISSING PLANS WITH THE PALM BEACH COUNTY STAMP FOR | | | IMPACT FEES. PLEASE BRING COPY OF PLANS THAT WERE | | | STAMPED BY PALM BEACH COUNTY. COUNTY IMPACT FEE | | | ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. | | | | | | 2- REVISE ENERGY CALCULATIONS SUBMITTED FOR THE GARAGE | | | CONVERSION: | | | A) OWNER NEEDS TO CERTIFY AT BOTTOM OF FORM AS REQUIRED | | | BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION | | | (2014). PERMIT CAN NOT BE ISSUED WITHOUT THE ENERGY | | | CALCULATIONS. | | | | | | B) ITEM #5 INDICATES THAT CALCULATIONS ARE NOT DONE FOR | | | WORST CASE SCENARIO BUT PAGE 2 OF 4 INDICATES THAT THE | | | BUILDING WAS ROTATED 45 DEGREES. ENERGY CALCULATIONS | | | NEED TO BE DONE FOR THE ACTUAL ORIENTATION OF THE | | | BUILDING. THEY CAN NOT BE ROTATED. REVISE AS REQUIRED. | | | SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION | | | (2014). | | | RESPONSE; REPEAT COMMENT. NOT ADDRESSED. | | | | | | C) THE GARAGE FLOOR IS NOT A RAISED FLOOR. SEE PLANS | | | AND REVISE ITEM #8 AS REQUIRED. SEC. R103.2 FBC-ENERGY | | | CONSERVATION, 5TH EDITION (2014). | | | | | | D) REVISE WALL INFORMATION ON ITEM #9. ACCORDING TO | | | PLANS THE EXISTING STRUCTURE IS CONCRETE BLOCK | | | CONSTRUCTION NOT WOOD FRAMED CONSTRUCTION. AND, THE | | | OPENINGS LIKE THE EXISTING GARAGE DOOR OPENING IS | | | CLOSED WITH WOOD FRAMED CONSTRUCTION. REVISE AS | | | REQUIRED. PROVIDE INFORMATION FOR THE TWO TYPES OF | | | WALLS TO MATCH PLANS. SEC. R103.2 FBC-ENERGY | | | CONSERVATION, 5TH EDITION (2014). | | | | | | E) REVISE "SPACES" IN FORMATION ON PAGE 2 OF 4. UNIT | | | CAN NOT HAVE A KITCHEN. SEE ZONING COMMENTS AND REVISED | | | PLANS. REVISE AS REQUIRED. REMOVE THE KITCHEN. SEC. | | | R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). | | | | | | F) THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4 DOESN'T | | | MATCH PLANS. REVISE THE BUILDING ORIENTATION, TOTAL | | | SQUARE FOOTAGE AND OVERHANG DEPTH AND SEPARATION TO | | | MATCH PLANS. SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH | | | EDITION (2014). | | | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. | | | | | | G) BUILDER NEEDS TO COMPLETE THE EPL DISPLAY CARD. SEC. | | | R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). | | | RESPONSE; REPEAT COMMENT. NOT ADDRESSED. | | | | | | 3- PROVIDE A/C MANUFACTURER'S SPECS FOR 18 SEER A/C | | | UNIT AS SPECIFIED ON THE ENERGY CALCULATIONS. SEC. | | | R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). | | | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMITT OLD | | | DRAWINGS FOR REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2017-03-27 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-03-27 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-03-27 |
Time |
09:29 |
Sent To |
HIST |
|
| Notes |
| 2017-03-27 10:37:07 | RESIDENTIAL (R3) CHANGE OF USE/ALTERATION BUILDING | | | REVIEW CHECKLIST. | | | CODE: FBC 5TH EDITION (2014). | | | | | | NOTE: | | | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO | | | MEANS THAT CONTRACTOR MAY SUBMIT REQUIRED INFORMATION | | | AFTER THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO | | | AVOID CONFLICTS/DELAYS. REVISION FEES WILL APPLY. | | | CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED AT | | | THIS TIME OR IF RE-SUBMITTING CORRECT INFORMATION. | | | | | | 1- REVISE ENERGY CALCULATIONS SUBMITTED FOR THE GARAGE | | | CONVERSION: THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF | | | 4 DOESN'T MATCH PLANS. THERE ARE NO WINDOWS ON THE | | | NORTH SIDE AND OVERHANG SEPARATION IS INCORRECT. REVISE | | | AS REQUIRED TO MATCH PLANS. SEC. R101.5.1.1.2 | | | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). | | | | | | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS | | | FOR REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2017-02-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-02-06 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-02-03 |
Time |
18:20 |
Sent To |
|
|
| Notes |
| 2017-02-03 18:36:26 | RESIDENTIAL (R3) CHANGE OF USE/ALTERATION THIRD | | | BUILDING REVIEW CHECKLIST. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- MISSING PLANS WITH THE PALM BEACH COUNTY STAMP FOR | | | IMPACT FEES. PLEASE BRING COPY OF PLANS THAT WERE | | | STAMPED BY PALM BEACH COUNTY. COUNTY IMPACT FEE | | | ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. | | | | | | 2- REVISE ENERGY CALCULATIONS SUBMITTED FOR THE GARAGE | | | CONVERSION: | | | A) OWNER NEEDS TO CERTIFY AT BOTTOM OF FORM AS REQUIRED | | | BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION | | | (2014). PERMIT CAN NOT BE ISSUED WITHOUT THE ENERGY | | | CALCULATIONS. | | | | | | B) ITEM #5 INDICATES THAT CALCULATIONS ARE NOT DONE FOR | | | WORST CASE SCENARIO BUT PAGE 2 OF 4 INDICATES THAT THE | | | BUILDING WAS ROTATED 45 DEGREES. ENERGY CALCULATIONS | | | NEED TO BE DONE FOR THE ACTUAL ORIENTATION OF THE | | | BUILDING. THEY CAN NOT BE ROTATED. REVISE AS REQUIRED. | | | SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION | | | (2014). | | | RESPONSE; REPEAT COMMENT. NOT ADDRESSED. | | | | | | C) THE GARAGE FLOOR IS NOT A RAISED FLOOR. SEE PLANS | | | AND REVISE ITEM #8 AS REQUIRED. SEC. R103.2 FBC-ENERGY | | | CONSERVATION, 5TH EDITION (2014). | | | | | | D) REVISE WALL INFORMATION ON ITEM #9. ACCORDING TO | | | PLANS THE EXISTING STRUCTURE IS CONCRETE BLOCK | | | CONSTRUCTION NOT WOOD FRAMED CONSTRUCTION. AND, THE | | | OPENINGS LIKE THE EXISTING GARAGE DOOR OPENING IS | | | CLOSED WITH WOOD FRAMED CONSTRUCTION. REVISE AS | | | REQUIRED. PROVIDE INFORMATION FOR THE TWO TYPES OF | | | WALLS TO MATCH PLANS. SEC. R103.2 FBC-ENERGY | | | CONSERVATION, 5TH EDITION (2014). | | | | | | E) REVISE "SPACES" IN FORMATION ON PAGE 2 OF 4. UNIT | | | CAN NOT HAVE A KITCHEN. SEE ZONING COMMENTS AND REVISED | | | PLANS. REVISE AS REQUIRED. REMOVE THE KITCHEN. SEC. | | | R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). | | | | | | F) THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4 DOESN'T | | | MATCH PLANS. REVISE THE BUILDING ORIENTATION, TOTAL | | | SQUARE FOOTAGE AND OVERHANG DEPTH AND SEPARATION TO | | | MATCH PLANS. SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH | | | EDITION (2014). | | | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. | | | | | | G) BUILDER NEEDS TO COMPLETE THE EPL DISPLAY CARD. SEC. | | | R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). | | | RESPONSE; REPEAT COMMENT. NOT ADDRESSED. | | | | | | 3- PROVIDE A/C MANUFACTURER'S SPECS FOR 18 SEER A/C | | | UNIT AS SPECIFIED ON THE ENERGY CALCULATIONS. SEC. | | | R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). | | | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMITT OLD | | | DRAWINGS FOR REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2016-11-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-11-16 |
Time |
08:19 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-11-16 |
Time |
07:39 |
Sent To |
|
|
| Notes |
| 2016-11-16 08:20:06 | RESIDENTIAL (R3) CHANGE OF USE/ALTERATION SECOND | | | BUILDING REVIEW CHECKLIST. | | | CODE: FBC 5TH EDITION (2014). | | | | | | ORIGINAL COMMENT: | | | 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED | | | BY SEC. R101.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION | | | (2014). | | | NOTE: NEED ENERGY CALCULATIONS FOR EACH SEPARATE | | | STRUCTURE. | | | | | | RESPONSE: | | | ONLY THE ENERGY CALCULATIONS FOR THE MAIN HOUSE WERE | | | SUBMITTED. THERE WERE NOT CALCULATIONS SUBMITTED FOR | | | THE GARAGE THAT IS PROPOSED TO BE CONVERTED TO LIVING | | | SPACE. NEED TO PROVIDE THE ENERGY CALCULATIONS FOR THE | | | GARAGE CONVERSION. | | | NOTE: AFTER LOOKING AT THE HISTORIC REVIEW COMMENTS, IT | | | LOOKS LIKE THE MAIN HOUSE IS A CONTRIBUTING HISTORIC | | | BUILDING. ENERGY CALCULATIONS ARE NOT REQUIRED FOR THE | | | MAIN HOUSE. THE GARAGE BUILDING IS NOT A HISTORIC | | | CONTRIBUTING BUILDING. ENERGY CALCULATIONS ARE REQUIRED | | | FOR THE GARAGE BUILDING. PERMIT CAN NOT BE ISSUED | | | WITHOUT THE COMPLETE ENERGY CALCULATIONS. SEC. | | | R103.1.1.2 FBC-ENERGY CONSERVATION. | | | | | | 2- SINCE THE ENERGY CALCULATIONS FOR THE GARAGE | | | BUILDING WERE NOT SUBMITTED, THEN CONTRACTOR MAY USE | | | THE FOLLOWING COMMENTS DONE FOR THE ENERGY CALCULATIONS | | | SUBMITTED FOR THE MAIN HOUSE TO MAKE SURE GARAGE | | | REQUIRED ENERGY CALCULATIONS ARE COMPLETE AND CORRECT. | | | A) COMPLETE ALL THE INFORMATION ON TOP OF FORM | | | INCLUDING OWNER NAME, BUILDER NAME, PERMIT OFFICE AND | | | JURISDICTION NUMBER. SEC. R101.5.1.1.2 FBC-ENERGY | | | CONSERVATION, 5TH EDITION (2014). | | | | | | B) REVISE ITEM #1. THIS IS NOT NEW CONSTRUCTION. SEC. | | | R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION | | | (2014). | | | | | | C) ENERGY CALCULATIONS NEED TO BE DONE FOR THE ACTUAL | | | ORIENTATION OF THE BUILDING. THEY CAN NOT BE DONE FOR | | | THE WORST CASED SCENARIO. REVISE ITEM #5. SEC. R103.2 | | | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). | | | | | | D) NEED TO PROVIDE PROOF OF THE WINDOWS AND DOORS | | | U-FACTOR AND SHGC FACTOR SPECIFIED ON ITEM #7. SEC. | | | R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). | | | NOTE: THIS IS REQUIRED WHEN THE ENERGY CALCULATIONS USE | | | FACTORS OTHER THAN THE DEFAULT FACTORS. | | | | | | E) NEED TO REVISE THE ROOF TYPE AND MATERIALS SHOWN ON | | | PAGE 2 OF 4. THIS BUILDING HAS GABLE AND FLAT ROOFS | | | (NOT HIP). SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH | | | EDITION (2014). | | | | | | F) DOORS INFORMATION SHOWN ON PAGE 3 OF 4 DOESN'T MATCH | | | PLANS AND PRODUCT APPROVALS SUBMITTED. SEC. R103.2 | | | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). | | | | | | G) THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4 DOESN'T | | | MATCH PLANS. REVISE THE BUILDING ORIENTATION, TOTAL | | | SQUARE FOOTAGE AND OVERHANG DEPTH AND SEPARATION TO | | | MATCH PLANS. SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH | | | EDITION (2014). | | | | | | H) BUILDER NEEDS TO COMPLETE THE EPL DISPLAY CARD. SEC. | | | R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). | | | | | | I) BUILDER NEEDS TO COMPLETE THE INSPECTION CHECKLIST | | | (TABLE 402.4.11 SUBMITTED). SEC. R405.4.2 FBC-ENERGY | | | CONSERVATION, 5TH EDITION (2014). | | | | | | ORIGINAL COMMENT: | | | 3- VALUATION DECLARED IN THE PERMIT IS TOO LOW BASED ON | | | THE SCOPE OF WORK SHOWN ON PLANS. VALUATION TO INCLUDE | | | ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT | | | AND ALL DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC. | | | 109.3 CITY AMENDMENTS. REVISE VALUATION AS REQUIRED. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | 4- PROVIDE PRODUCT APPROVAL ( 2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.002(33) FOR: | | | ORIGINAL COMMENT: | | | A)ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON | | | DETAILS SUBMITTED. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. PROVIDE THE FLORIDA | | | PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE | | | SPECIFIED CONNECTOR OR DESIGN PROFESSIONAL TO LIST THE | | | FLORIDA PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED | | | CONNECTOR. | | | | | | ORIGINAL COMMENT: | | | 5- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS | | | (INCLUDING THE ONES ALREADY SUBMITTED) AS REQUIRED BY | | | SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | NEW COMMENT: | | | 6- PLANS WERE REVISED. PLANS SHOW WINDOW HEATING AND | | | COOLING UNIT INSTEAD OF SPLIT A/C UNIT. REMOVABLE | | | WINDOW UNIT IS NOT ALLOWED TO PROVIDE HEATING AS | | | REQUIRED BY SEC. R303.9 FBC-RESIDENTIAL. REVISE PLANS | | | SHOWING THE HEATING AND COOLING UNIT IN A PERMANENT | | | FRAMED SPACE. REVISE FLOOR PLAN AND EXTERIOR ELEVATION | | | ACCORDINGLY. AND PROVIDE FRAMING DETAILS AND | | | SPECIFICATIONS. SEC. R301.1 FBC-RESIDENTIAL. | | | | | | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS | | | FOR REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-09-19 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-09-19 |
Time |
08:21 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-09-16 |
Time |
18:48 |
Sent To |
|
|
| Notes |
| 2016-09-16 18:49:11 | RESIDENTIAL (R3) CHANGE OF USE/ALTERATION BUILDING | | | REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED | | | BY SEC. R101.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION | | | (2014). | | | NOTE: NEED ENERGY CALCULATIONS FOR EACH SEPARATE | | | STRUCTURE. | | | | | | 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) | | | FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED | | | PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY | | | IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT | | | CODE. | | | | | | 3- SCOPE OF WORK ON SHEET A-1 CALLS FOR "REPAIR OF 3 | | | EXISTING FIRE DAMAGED TRUSSES PER ROOF PLAN. PROVIDE | | | COMPLETE DETAILS AND SPECIFICATIONS FOR THE TRUSSES | | | REPAIRS. SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION | | | (2014). | | | | | | 4- WINDOW SCHEDULE ON SHEET A-2: WINDOWS #3 AND #4 | | | DON'T COMPLY WITH EGRESS REQUIREMENTS. REVISE STATEMENT | | | SPECIFYING "SINGLE HUNG EGRESS SIZED". SEC. R310 | | | FBC-RESIDENTIAL. | | | | | | 5- VALUATION DECLARED IN THE PERMIT IS TOO LOW BASED ON | | | THE SCOPE OF WORK SHOWN ON PLANS. VALUATION TO INCLUDE | | | ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT | | | AND ALL DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC. | | | 109.3 CITY AMENDMENTS. REVISE VALUATION AS REQUIRED. | | | | | | 6- PROVIDE PRODUCT APPROVAL ( 2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.002(33) FOR: | | | A) PLASTIC SOFFIT VENT AS SPECIFIED ON THE TYPICAL WALL | | | SECTION ON SHEET D1. | | | | | | B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON | | | DETAILS SUBMITTED. | | | | | | 7- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS | | | (INCLUDING THE ONES ALREADY SUBMITTED) AS REQUIRED BY | | | SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS | | | FOR REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2017-02-15 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2017-02-15 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2017-02-15 |
Time |
09:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2016-11-01 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-11-01 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-11-01 |
Time |
11:33 |
Sent To |
|
|
| Notes |
| 2016-11-01 12:08:40 | 2ND ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA RES BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. PRIOR COMMENTS ADDRESSED. BASED ON NEW SERVICE | | | ARRANGEMENT SHOWN, THE MAIN BREAKERS MUST BE GROUPED IN | | | ONE LOCATION PER FBC RES E3601.7 AND THE SHOW A | | | GROUNDING ELECTRODE ARRANGEMENT AT THE SEPARATE | | | STRUCTURE. SEPARATE STRUCTURE MUST STILL BE MCB PANEL | | | TYPE NOT A MLO. | | | 2. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | | QUESTIONS OR CONCERNS. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-09-22 |
|
|
Cont ID |
|
| Sent By |
njwira |
Date |
2016-09-19 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2016-09-22 |
Time |
15:44 |
Sent To |
I |
|
| Notes |
| 2016-09-22 18:54:25 | ELECTRICAL REVIEW NOTES | | | REVIEWED FOR COMPLIANCE WITH: | | | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) | | | | | | PROJECT NAME: | | | JOB ADDRESS: 3912 GREENWOOD AVENUE | | | DESCRIPTION: INTERIOR RENOVATIONS | | | MASTER PERMIT: 16080928 | | | | | | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. | | | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF | | | SUBMITTED CORRECTIONS. | | | | | | 1. AN ELECTRICAL SUB PERMIT IS REQUIRED. | | | 2. THIS PROPERTY IS ZONED SINGLE FAMILY AND THEREFORE | | | JUST LIKE THE SECOND KITCHEN IS NOT ALLOWED, NEITHER IS | | | THE SECOND ELECTRICAL METER. CORRECT THE PLANS | | | ACCORDINGLY. | | | 3. THE RISER DIAGRAM AS SUBMITTED DOES NOT COMPLY WITH | | | CODE REQUIREMENTS, AND DOES NOT SPECIFICALLY REFLECT | | | THE SITE CONDITIONS AS SHOWN ON PLANS. YOU ARE ONLY | | | ALLOWED ONE SERVICE LATERAL OR DROP. | | | 4. THE CORRECTED RISER MUST INCLUDE THE INTER-SYSTEM | | | BONDING TERMINAL AND CONDUCTOR INSULATION TYPE, AND | | | PANEL TYPE. INDOOR OR OUTDOOR ETC. | | | 5. CORRECT THE PANEL SCHEDULE TO SHOW THE OVERCURRENT | | | PROTECTION FOR THE SUB PANEL (B). | | | 6. BOTH PANEL SCHEDULES INDICATE LOCATION AS IN THE | | | GARAGE; THIS DOES NOT MATCH THE DRAWINGS. | | | 7. ACCORDING TO THE SAME PANEL SCHEDULES THEY CALL FOR | | | FLUSH MOUNTED PANELS, YET THE DRAWINGS INDICATE A | | | SURFACE MOUNTED. | | | 8. CORRECT THE LOAD CALCS TO MATCH THE CORRECTED RISER | | | AND SITE DEMANDS. | | | 9. WATER HEATER IS REQUIRED IN THE DWELLING. YOU SHOW | | | AS OPTIONAL. YOU HAVE TO DECIDE AS THE LOAD CALCS FOR | | | THIS HAVE TO BE INCLUDED. FURTHERMORE INDICATE WHETHER | | | THEY ARE GOING TO BE GAS OR ELECTRIC. | | | 10. CORRECT THE LOAD CALCS FOR PANEL B TO REMOVE THE | | | RANGE LOAD AND CIRCUIT. | | | 11. SHEET M1 SHOWS THE POWER REQUIREMENTS FOR THE HVAC | | | EQUIPMENT IS 208/230; THE HOUSE SERVICE IS 120/240 | | | CORRECT THIS ACCORDINGLY. | | | 12. GAS METER SHALL BE FURTHER THAN 10? FROM EITHER THE | | | ELECTRICAL PANEL OR METER SOCKET. | | | 13. SHEET M1 REFLECTS A SECOND GAS METER ON THE | | | EXTERIOR OF THE GARAGE WHICH DOES NOT APPEAR ON SHEET | | | E1. WHICH IS CORRECT? | | | 14. BOXES USED AT LUMINAIRE OR LAMPHOLDER OUTLETS IN A | | | CEILING SHALL BE REQUIRED TO SUPPORT A LUMINAIRE | | | WEIGHING A MINIMUM OF 50 LB. ADD THIS TO THE NOTES ON | | | CEILING BOXES ON PAGE. | | | 15. BOXES USED FOR THE SOLE SUPPORT OF CEILING FANS | | | SHALL BE MARKED BY THE MANUFACTURER AS SUITABLE FOR THE | | | PURPOSE, AND INDICATE THE WEIGHT LIMITATIONS BUT SHALL | | | NOT BE USED TO SUPPORT PADDLE FANS HEAVIER THAN 70 LBS. | | | 16. IN DWELLING UNITS, AT LEAST ONE RECEPTACLE OUTLET | | | SHALL BE INSTALLED IN BATHROOMS WITHIN 3 FT. OF THE | | | OUTSIDE EDGE OF EACH BASIN. | | | 17. YOU SHALL MARK THE PLANS WITH THE DRAWING SCALE | | | USED AND THE COMPASS ARROW. | | | 18. THE PLANS SHOW THE HVAC EQUIPMENT INSIDE THE ATTIC. | | | AT LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR | | | CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE | | | THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT | | | REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE | | | PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. | | | I SUGGEST THAT THIS SWITCH HAVE A PILOT LIGHT TO | | | INDICATE IF THE ATTIC LIGHT IS ON. | | | 19. A 125 VOLT, SINGLE-PHASE, 15 OR 20-AMPERE-RATED | | | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE | | | LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE | | | RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE | | | EQUIPMENT. | | | 20. BECAUSE THE BATHROOMS DO NOT HAVE WINDOWS, THE | | | EXHAUST FAN IS REQUIRED THEREFORE IT SHALL COME ON | | | WHENEVER THE ROOM IS OCCUPIED AND THUS CONNECTED TO THE | | | LIGHT SWITCH. IF THE FAN IS LESS THAT 50CFM IT SHALL | | | HAVE CONTINUOUS OPERATION AND THUS BE NON-SWITCHED. | | | 21. IN ALL AREAS SPECIFIED IN 210.52, ALL 125-VOLT, 15 | | | AND 20 AMPERE RECEPTACLES SHALL BE LISTED TAMPER | | | RESISTANT RECEPTACLES. | | | 22. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, | | | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN | | | FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, | | | LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATIONS ROOMS, | | | CLOSETS, HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE | | | PROTECTED BY A COMBINATION TYPE ARC-FAULT CIRCUIT | | | INTERRUPTER INSTALLED TO PROVIDE PROTECTION OF THE | | | BRANCH CIRCUIT. | | | 23. PERMANENTLY CONNECTED APPLIANCES OF OVER 300 VA OR | | | 1/8 HP REQUIRE A DISCONNECT WITHIN SIGHT OF THE | | | APPLIANCE. THIS APPLIES TO BOTH WATER HEATERS AND HVAC | | | EQUIPMENT. | | | 24. BECAUSE OF THE GAS APPLIANCES YOU ARE TO COMPLY | | | WITH THE CARBON MONOXIDE DETECTOR REQUIREMENTS. | | | 25. A MINIMUM OF 75% OF THE LAMPS IN PERMANENTLY | | | INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY | | | LAMPS OR A MINIMUM OF 75% OF THE PERMANENTLY INSTALLED | | | LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH EFFICIENCY | | | LAMPS | | | | | | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | | GREATLY APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | PH: 561-805-6746 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2016-09-22 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-09-22 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-09-22 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2016-09-22 15:42:16 | GAS PLAN REVIEW | | | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | | THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE | | | REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK. | | | PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT | | | SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE | | | SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE | | | FBC-R, SEC. G2404.3. | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL | | | GAS SEC. 301.3. | | | | | | A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
4 |
Status |
F |
Date |
2017-03-27 |
|
|
Cont ID |
|
| Sent By |
destabro |
Date |
2017-03-27 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
destabro |
Date |
2017-03-27 |
Time |
16:32 |
Sent To |
B |
|
| Notes |
| 2017-04-13 10:18:09 | 4/13/2017 - APPLICANT REQUESTED NEW REVIEW BASED ON | | | REVISED PLANS WITH PERMIT. NO NEW PLANS WERE PROVIDED. | | | THE ONES INCLUDED WITH THE PERMIT DATE FROM FEBRUARY | | | (2017) AND STILL CONTAIN WINDOW ALTERATIONS AND CHANGES | | | TO THE GARAGE THAT REQUIRE A COA. THIS PERMIT WILL NOT | | | BE APPROVED AS IT STANDS CURRENTLY. THE APPLICANT WILL | | | EITHER NEED TO SUBMIT A COA FOR THE PROPOSED WORK, OR | | | LEAVE THE WINDOW OPENINGS UNALTERED IN SIZE (AND ALL | | | INTACT; THE PLANS REQUIRED THE REMOVAL OF THE NW ONE TO | | | INSTALL A METER). ADDITIONALLY, THE GARAGE MUST BE | | | MAINTAINED IN APPEARANCE, AND CANNOT BE STUCCO'D OVER | | | TO CREATE AN ACCESSORY UNIT. ADDITIONALLY, THE | | | APPLICANT SHOULD BE AWARE THAT ALTHOUGH THE SECONDARY | | | UNIT DOES NOT HAVE A STOVE/OVEN, AND IT IS TECHNICALLY | | | PERMITTED, HE WILL NOT BE GRANTED A RENTAL LICENSE FOR | | | THE THIS UNIT. QUESTIONS MAY BE DIRECTED TO FRIEDERIKE | | | MITTNER, AT 561.822.1457. | | 2017-03-27 16:32:50 | 3/27/2017 - PLANS STILL REFLECT WORK THAT REQUIRES A | | | COA - PERMIT FAILED UNTIL APPLICANT SUBMITS COA AND | | | SPEAKS TO HISTORIC PRESERVATION SECTION. DLE | | 2017-03-27 14:45:08 | ROUTED TO DESIREE ESTABROOK |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
3 |
Status |
F |
Date |
2017-03-14 |
|
|
Cont ID |
|
| Sent By |
destabro |
Date |
2017-03-14 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
destabro |
Date |
2017-03-14 |
Time |
15:10 |
Sent To |
B |
|
| Notes |
| 2017-03-14 15:12:33 | 3/14/2017 - FAILED TO SUBMIT COA OR ADDRESS HISTORIC | | | COMMENTS. |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
F |
Date |
2016-11-04 |
|
|
Cont ID |
|
| Sent By |
destabro |
Date |
2016-11-04 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
destabro |
Date |
2016-11-04 |
Time |
14:31 |
Sent To |
Z |
|
| Notes |
| 2016-11-04 14:35:10 | 11/4/16 - COA REQUIRED FOR PROPOSED WORK. REPLACEMENT | | | WINDOWS AND GARAGE CONVERSION STILL REQUIRE REVIEW, AND | | | COMMENTS FROM HISTORIC WERE NOT ADDRESSED. DLE |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-09-23 |
|
|
Cont ID |
|
| Sent By |
destabro |
Date |
2016-09-23 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
destabro |
Date |
2016-09-23 |
Time |
10:39 |
Sent To |
B |
|
| Notes |
| 2016-09-23 10:44:09 | 9/23/16 - APPLICANT PREVIOUSLY ADVISED THAT THIS IS A | | | CONTRIBUTING PROPERTY TO THE NORTHWOOD HILLS HISTORIC | | | DISTRICT. NEW SIDING, WINDOW REPLACEMENTS, AND ANY | | | OTHER EXTERIOR WORK WILL REQUIRE A COA AND HISTORIC | | | REVIEW. PROPOSED SCOPE OF WORK DOES NOT FOLLOW THE | | | DESIGN GUIDELINES FOR THIS HISTORIC DISTRICT. QUESTIONS | | | MAY BE DIRECTED TO EITHER FRIEDERIKE MITTNER OR DESIREE | | | ESTABROOK, HISTORIC PRESERVATION PLANNERS, AT | | | 561.822.1457. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2017-03-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-03-29 |
Time |
07:27 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-03-21 |
Time |
14:08 |
Sent To |
|
|
| Notes |
| 2017-03-27 14:09:22 | 03/27/17 PLANS SENT TO ZONING SHELF FOR HISTORIC | | | REVIEW. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-03-15 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2017-03-15 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-01-26 |
Time |
11:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-01-27 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2017-01-27 |
Time |
11:50 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2016-10-20 |
Time |
11:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-09-22 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2016-09-22 |
Time |
18:58 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2016-08-22 |
Time |
13:06 |
Sent To |
|
|
| Notes |
| 2016-09-22 18:58:30 | 9/22/16-FAILED MULTIPLE TRADE REVIEWS. CONTRACTOR | | | NOTIFIED VIA EMAIL. FILE SENT TO LARGE DENIED B DRAWER. | | | MA | | 2016-08-23 13:07:02 | R25 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2017-03-27 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-11-16 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-11-16 |
Time |
09:25 |
Sent To |
|
|
| Notes |
| 2016-11-16 09:26:50 | NO IMPACT FEES DUE. MU-2016-25851 DATED 10/18/16. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2016-09-19 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-09-19 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-09-19 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2016-09-19 11:08:25 | 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) | | | FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED | | | PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY | | | IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT | | | CODE. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2017-03-27 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-03-27 |
Time |
13:28 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-03-27 |
Time |
10:38 |
Sent To |
HIST |
|
| Notes |
| 2017-03-27 10:37:57 | RESIDENTIAL (R3) CHANGE OF USE/ALTERATION MECHANICAL | | | REVIEW CHECKLIST. | | | CODE: FBC 5TH EDITION (2014). | | | | | | NOTE: | | | MECHANICAL REVIEW MAY BE APPROVED WITH PROVISO. PROVISO | | | MEANS THAT CONTRACTOR MAY SUBMIT REQUIRED INFORMATION | | | AFTER THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO | | | AVOID CONFLICTS/DELAYS. REVISION FEES WILL APPLY. | | | CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED AT | | | THIS TIME OR IF RE-SUBMITTING CORRECT INFORMATION. | | | | | | 1- REVISED EQUIPMENT CALCULATIONS FOR THE REAR | | | STRUCTURE NEEDS TO BE REVISED. SELECTED EQUIPMENT NEEDS | | | TO BE CHANGED. "THE CORRESPONDING LATENT CAPACITY OF | | | THE EQUIPMENT SHALL NOT BE LESS THAN THE CALCULATED | | | LATENT LOAD". SEC. R403.6.1.1 FBC-ENERGY CONSERVATION, | | | 5TH EDITION (2014). | | | | | | 2- EQUIPMENT SHOWN ON DRAWING M1 FOR THE REAR STRUCTURE | | | DOESN'T MATCH EQUIPMENT SHOWN ON THE REVISED EQUIPMENT | | | SIZING CALCULATIONS. REVISE AS REQUIRED TO MATCH , | | | INCLUDING THE SEER. SEC. R403.6.1.1 FBC-ENERGY | | | CONSERVATION. | | | | | | 3- ONLY THE SUMMARY SHEET OF THE EQUIPMENT SIZING | | | CALCULATIONS WAS SUBMITTED. PROVIDE THE COMPLETE | | | EQUIPMENT SIZING CALCULATIONS FOR THE MAIN HOUSE AND | | | FOR THE REAR STRUCTURE. SEC. R403.6.1.1 FBC-ENERGY | | | CONSERVATION. | | | | | | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMITT OLD | | | DRAWINGS FOR REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2017-02-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-02-06 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-02-06 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2017-02-06 11:16:34 | RESIDENTIAL (R3) CHANGE OF USE/ALTERATION THIRD | | | MECHANICAL REVIEW CHECKLIST. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- PROVIDE EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY | | | SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION | | | (2014). PROVIDE THE EQUIPMENT MANUFACTURER AND MODEL | | | NUMBER OF THE OUTDOOR AND INDOOR UNITS AND THE AHRI | | | LISTING. NOTE: ALL EQUIPMENT INFORMATION TO MATCH | | | EQUIPMENT INFORMATION SHOWN ON DRAWING M1 SUBMITTED. | | | NOTE: NEED EQUIPMENT SIZING CALCULATIONS FOR EACH | | | SEPARATE STRUCTURE. | | | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. | | | NEED TO PROVIDE THE COMPLETE EQUIPMENT SIZING | | | CALCULATIONS FOR EACH BUILDING. ONLY A ONE SUMMARY FOR | | | THE MAIN HOUSE WAS SUBMITTED. PROVIDE COMPLETE LOAD | | | CALCULATIONS FOR EACH BUILDING. | | | | | | 2- PROVIDE MANUFACTURER'S INFORMATION FOR THE A/C UNIT | | | SPECIFIED FOR THE GARAGE CONVERSION SHOWING THE SEER | | | SPECIFIED ON PLANS. SEC. R103.2 FBC-ENERGY | | | CONSERVATION, 5TH EDITION (2014). | | | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. | | | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMITT OLD | | | DRAWINGS FOR REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2016-11-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-11-16 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-11-16 |
Time |
10:22 |
Sent To |
P |
|
| Notes |
| 2016-11-16 10:26:25 | RESIDENTIAL (R3) CHANGE OF USE/ALTERATION SECOND | | | MECHANICAL REVIEW CHECKLIST. | | | CODE: FBC 5TH EDITION (2014). | | | | | | ORIGINAL COMMENT: | | | 1- PROVIDE EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY | | | SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION | | | (2014). PROVIDE THE EQUIPMENT MANUFACTURER AND MODEL | | | NUMBER OF THE OUTDOOR AND INDOOR UNITS AND THE AHRI | | | LISTING. NOTE: ALL EQUIPMENT INFORMATION TO MATCH | | | EQUIPMENT INFORMATION SHOWN ON DRAWING M1 SUBMITTED. | | | CHECK CFM'S SPECIFIED FOR UNIT #1 AND UNIT #2. WHY THE | | | GUEST HOUSE HAS MORE CFM'S THAN THE MAIN HOUSE? | | | NOTE: NEED EQUIPMENT SIZING CALCULATIONS FOR EACH | | | SEPARATE STRUCTURE. | | | | | | RESPONSE: | | | NEED TO PROVIDE THE COMPLETE EQUIPMENT SIZING | | | CALCULATIONS FOR EACH BUILDING. ONLY A ONE SUMMARY FOR | | | THE MAIN HOUSE WAS SUBMITTED. PROVIDE COMPLETE LOAD | | | CALCULATIONS FOR EACH BUILDING. | | | | | | NEW COMMENT: | | | 2- PROVIDE MANUFACTURER'S INFORMATION FOR THE A/C UNIT | | | SPECIFIED FOR THE GARAGE CONVERSION SHOWING THE SEER | | | SPECIFIED ON PLANS. SEC. R103.2 FBC-ENERGY | | | CONSERVATION, 5TH EDITION (2014). | | | | | | | | | | | | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS | | | FOR REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-09-19 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-09-19 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-09-19 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2016-09-19 15:17:18 | RESIDENTIAL (R3) CHANGE OF USE/ALTERATION MECHANICAL | | | REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- PROVIDE EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY | | | SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION | | | (2014). PROVIDE THE EQUIPMENT MANUFACTURER AND MODEL | | | NUMBER OF THE OUTDOOR AND INDOOR UNITS AND THE AHRI | | | LISTING. NOTE: ALL EQUIPMENT INFORMATION TO MATCH | | | EQUIPMENT INFORMATION SHOWN ON DRAWING M1 SUBMITTED. | | | CHECK CFM'S SPECIFIED FOR UNIT #1 AND UNIT #2. WHY THE | | | GUEST HOUSE HAS MORE CFM'S THAN THE MAIN HOUSE? | | | NOTE: NEED EQUIPMENT SIZING CALCULATIONS FOR EACH | | | SEPARATE STRUCTURE. | | | | | | 2- BALANCE RETURN INFORMATION FOR BEDROOM #2 IS NOT | | | CLEAR. CLEARLY SPECIFY SIZE OF TRANSFER DUCT FOR | | | BEDROOM #2. SEE SIZE OF GRILLE SPECIFIED. AND, PROVIDE | | | DETAILS SHOWING HOW IS IT GOING TO BE INSTALLED WITHOUT | | | INTERFERING WITH THE AIR HANDLER UNIT ABOVE. SEC. | | | M1602.4 FBC-RESIDENTIAL. 5TH EDITION (2014). | | | | | | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS | | | FOR REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2017-02-14 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-02-14 |
Time |
17:01 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-02-14 |
Time |
16:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2016-11-22 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-11-22 |
Time |
17:08 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-11-22 |
Time |
17:08 |
Sent To |
|
|
| Notes |
| 2016-11-22 17:10:12 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. PLUMBING PAGES MISSING FROM NEW SET OF PLANS , | | | PLEASE PROVIDE PLUMBING RISER DIAGRAMS. PER WPB AMEND | | | TO FBC 107.2.1 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2016-09-22 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-09-22 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-09-22 |
Time |
15:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2017-03-14 |
|
|
Cont ID |
|
| Sent By |
njwira |
Date |
2017-02-07 |
Time |
|
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2017-02-07 |
Time |
13:49 |
Sent To |
I |
|
| Notes |
| 2017-02-07 15:50:42 | 2/7/17- PASSED | | | NO 2ND KITCHEN OR UNIT PERMITTED | | | LANDSCAPE PERMIT REQUIRED | | | | | | PLEASE CONTACT | | | NATHAN WIRA | | | [email protected] | | | (561)822-1442 | | | | | 2017-02-03 18:39:31 | NEED RE-STAMP. TWO NEW SET OF DRAWINGS SUBMITTED. JG. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2016-11-14 |
|
|
Cont ID |
|
| Sent By |
njwira |
Date |
2016-11-14 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2016-11-07 |
Time |
08:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2016-09-19 |
|
|
Cont ID |
|
| Sent By |
nwair |
Date |
2016-09-07 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2016-08-26 |
Time |
15:50 |
Sent To |
E |
|
| Notes |
| 2016-09-19 10:45:24 | CANNOT HAVE A SECOND UNIT WITH A SECOND KITCHEN. | | | | | | PLEASE CONTACT | | | NATHAN WIRA | | | [email protected] | | | (561)822-1442 | | | |
|
|