Plan Review Details - Permit 16080928
Plan Review Stops For Permit 16080928
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2017-07-27 Cont ID  
Sent By jgomez Date 2017-07-27 Time 14:57 Rev Time 0.00
Received By jgomez Date 2017-07-27 Time 14:57 Sent To  
Notes
2017-07-27 14:58:0407/27/17 MET WITH ALVIN. NEED TO REVISE ENERGY
 CALCULATIONS. NEED CORRECT CALCULATIONS, NOT WORST
 CASE. HE SIGNED OUT ONE COMPLETE SET OF PLANS AND
 PRODUCT APPROVALS. JG.
  
  
 RESIDENTIAL (R3) CHANGE OF USE/ALTERATION THIRD
 BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- MISSING PLANS WITH THE PALM BEACH COUNTY STAMP FOR
 IMPACT FEES. PLEASE BRING COPY OF PLANS THAT WERE
 STAMPED BY PALM BEACH COUNTY. COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- REVISE ENERGY CALCULATIONS SUBMITTED FOR THE GARAGE
 CONVERSION:
 A) OWNER NEEDS TO CERTIFY AT BOTTOM OF FORM AS REQUIRED
 BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). PERMIT CAN NOT BE ISSUED WITHOUT THE ENERGY
 CALCULATIONS.
  
 B) ITEM #5 INDICATES THAT CALCULATIONS ARE NOT DONE FOR
 WORST CASE SCENARIO BUT PAGE 2 OF 4 INDICATES THAT THE
 BUILDING WAS ROTATED 45 DEGREES. ENERGY CALCULATIONS
 NEED TO BE DONE FOR THE ACTUAL ORIENTATION OF THE
 BUILDING. THEY CAN NOT BE ROTATED. REVISE AS REQUIRED.
 SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE; REPEAT COMMENT. NOT ADDRESSED.
  
 C) THE GARAGE FLOOR IS NOT A RAISED FLOOR. SEE PLANS
 AND REVISE ITEM #8 AS REQUIRED. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 D) REVISE WALL INFORMATION ON ITEM #9. ACCORDING TO
 PLANS THE EXISTING STRUCTURE IS CONCRETE BLOCK
 CONSTRUCTION NOT WOOD FRAMED CONSTRUCTION. AND, THE
 OPENINGS LIKE THE EXISTING GARAGE DOOR OPENING IS
 CLOSED WITH WOOD FRAMED CONSTRUCTION. REVISE AS
 REQUIRED. PROVIDE INFORMATION FOR THE TWO TYPES OF
 WALLS TO MATCH PLANS. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 E) REVISE "SPACES" IN FORMATION ON PAGE 2 OF 4. UNIT
 CAN NOT HAVE A KITCHEN. SEE ZONING COMMENTS AND REVISED
 PLANS. REVISE AS REQUIRED. REMOVE THE KITCHEN. SEC.
 R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 F) THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4 DOESN'T
 MATCH PLANS. REVISE THE BUILDING ORIENTATION, TOTAL
 SQUARE FOOTAGE AND OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 G) BUILDER NEEDS TO COMPLETE THE EPL DISPLAY CARD. SEC.
 R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 RESPONSE; REPEAT COMMENT. NOT ADDRESSED.
  
 3- PROVIDE A/C MANUFACTURER'S SPECS FOR 18 SEER A/C
 UNIT AS SPECIFIED ON THE ENERGY CALCULATIONS. SEC.
 R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2017-03-27 Cont ID  
Sent By jgomez Date 2017-03-27 Time 10:36 Rev Time 0.00
Received By jgomez Date 2017-03-27 Time 09:29 Sent To HIST
Notes
2017-03-27 10:37:07RESIDENTIAL (R3) CHANGE OF USE/ALTERATION BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT CONTRACTOR MAY SUBMIT REQUIRED INFORMATION
 AFTER THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO
 AVOID CONFLICTS/DELAYS. REVISION FEES WILL APPLY.
 CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED AT
 THIS TIME OR IF RE-SUBMITTING CORRECT INFORMATION.
  
 1- REVISE ENERGY CALCULATIONS SUBMITTED FOR THE GARAGE
 CONVERSION: THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF
 4 DOESN'T MATCH PLANS. THERE ARE NO WINDOWS ON THE
 NORTH SIDE AND OVERHANG SEPARATION IS INCORRECT. REVISE
 AS REQUIRED TO MATCH PLANS. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-02-06 Cont ID  
Sent By jgomez Date 2017-02-06 Time 11:02 Rev Time 0.00
Received By jgomez Date 2017-02-03 Time 18:20 Sent To  
Notes
2017-02-03 18:36:26RESIDENTIAL (R3) CHANGE OF USE/ALTERATION THIRD
 BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- MISSING PLANS WITH THE PALM BEACH COUNTY STAMP FOR
 IMPACT FEES. PLEASE BRING COPY OF PLANS THAT WERE
 STAMPED BY PALM BEACH COUNTY. COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- REVISE ENERGY CALCULATIONS SUBMITTED FOR THE GARAGE
 CONVERSION:
 A) OWNER NEEDS TO CERTIFY AT BOTTOM OF FORM AS REQUIRED
 BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). PERMIT CAN NOT BE ISSUED WITHOUT THE ENERGY
 CALCULATIONS.
  
 B) ITEM #5 INDICATES THAT CALCULATIONS ARE NOT DONE FOR
 WORST CASE SCENARIO BUT PAGE 2 OF 4 INDICATES THAT THE
 BUILDING WAS ROTATED 45 DEGREES. ENERGY CALCULATIONS
 NEED TO BE DONE FOR THE ACTUAL ORIENTATION OF THE
 BUILDING. THEY CAN NOT BE ROTATED. REVISE AS REQUIRED.
 SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE; REPEAT COMMENT. NOT ADDRESSED.
  
 C) THE GARAGE FLOOR IS NOT A RAISED FLOOR. SEE PLANS
 AND REVISE ITEM #8 AS REQUIRED. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 D) REVISE WALL INFORMATION ON ITEM #9. ACCORDING TO
 PLANS THE EXISTING STRUCTURE IS CONCRETE BLOCK
 CONSTRUCTION NOT WOOD FRAMED CONSTRUCTION. AND, THE
 OPENINGS LIKE THE EXISTING GARAGE DOOR OPENING IS
 CLOSED WITH WOOD FRAMED CONSTRUCTION. REVISE AS
 REQUIRED. PROVIDE INFORMATION FOR THE TWO TYPES OF
 WALLS TO MATCH PLANS. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 E) REVISE "SPACES" IN FORMATION ON PAGE 2 OF 4. UNIT
 CAN NOT HAVE A KITCHEN. SEE ZONING COMMENTS AND REVISED
 PLANS. REVISE AS REQUIRED. REMOVE THE KITCHEN. SEC.
 R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 F) THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4 DOESN'T
 MATCH PLANS. REVISE THE BUILDING ORIENTATION, TOTAL
 SQUARE FOOTAGE AND OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 G) BUILDER NEEDS TO COMPLETE THE EPL DISPLAY CARD. SEC.
 R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 RESPONSE; REPEAT COMMENT. NOT ADDRESSED.
  
 3- PROVIDE A/C MANUFACTURER'S SPECS FOR 18 SEER A/C
 UNIT AS SPECIFIED ON THE ENERGY CALCULATIONS. SEC.
 R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-11-16 Cont ID  
Sent By jgomez Date 2016-11-16 Time 08:19 Rev Time 0.00
Received By jgomez Date 2016-11-16 Time 07:39 Sent To  
Notes
2016-11-16 08:20:06RESIDENTIAL (R3) CHANGE OF USE/ALTERATION SECOND
 BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 ORIGINAL COMMENT:
 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. R101.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 NOTE: NEED ENERGY CALCULATIONS FOR EACH SEPARATE
 STRUCTURE.
  
 RESPONSE:
 ONLY THE ENERGY CALCULATIONS FOR THE MAIN HOUSE WERE
 SUBMITTED. THERE WERE NOT CALCULATIONS SUBMITTED FOR
 THE GARAGE THAT IS PROPOSED TO BE CONVERTED TO LIVING
 SPACE. NEED TO PROVIDE THE ENERGY CALCULATIONS FOR THE
 GARAGE CONVERSION.
 NOTE: AFTER LOOKING AT THE HISTORIC REVIEW COMMENTS, IT
 LOOKS LIKE THE MAIN HOUSE IS A CONTRIBUTING HISTORIC
 BUILDING. ENERGY CALCULATIONS ARE NOT REQUIRED FOR THE
 MAIN HOUSE. THE GARAGE BUILDING IS NOT A HISTORIC
 CONTRIBUTING BUILDING. ENERGY CALCULATIONS ARE REQUIRED
 FOR THE GARAGE BUILDING. PERMIT CAN NOT BE ISSUED
 WITHOUT THE COMPLETE ENERGY CALCULATIONS. SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 2- SINCE THE ENERGY CALCULATIONS FOR THE GARAGE
 BUILDING WERE NOT SUBMITTED, THEN CONTRACTOR MAY USE
 THE FOLLOWING COMMENTS DONE FOR THE ENERGY CALCULATIONS
 SUBMITTED FOR THE MAIN HOUSE TO MAKE SURE GARAGE
 REQUIRED ENERGY CALCULATIONS ARE COMPLETE AND CORRECT.
 A) COMPLETE ALL THE INFORMATION ON TOP OF FORM
 INCLUDING OWNER NAME, BUILDER NAME, PERMIT OFFICE AND
 JURISDICTION NUMBER. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 B) REVISE ITEM #1. THIS IS NOT NEW CONSTRUCTION. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 C) ENERGY CALCULATIONS NEED TO BE DONE FOR THE ACTUAL
 ORIENTATION OF THE BUILDING. THEY CAN NOT BE DONE FOR
 THE WORST CASED SCENARIO. REVISE ITEM #5. SEC. R103.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 D) NEED TO PROVIDE PROOF OF THE WINDOWS AND DOORS
 U-FACTOR AND SHGC FACTOR SPECIFIED ON ITEM #7. SEC.
 R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 NOTE: THIS IS REQUIRED WHEN THE ENERGY CALCULATIONS USE
 FACTORS OTHER THAN THE DEFAULT FACTORS.
  
 E) NEED TO REVISE THE ROOF TYPE AND MATERIALS SHOWN ON
 PAGE 2 OF 4. THIS BUILDING HAS GABLE AND FLAT ROOFS
 (NOT HIP). SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 F) DOORS INFORMATION SHOWN ON PAGE 3 OF 4 DOESN'T MATCH
 PLANS AND PRODUCT APPROVALS SUBMITTED. SEC. R103.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 G) THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4 DOESN'T
 MATCH PLANS. REVISE THE BUILDING ORIENTATION, TOTAL
 SQUARE FOOTAGE AND OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 H) BUILDER NEEDS TO COMPLETE THE EPL DISPLAY CARD. SEC.
 R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 I) BUILDER NEEDS TO COMPLETE THE INSPECTION CHECKLIST
 (TABLE 402.4.11 SUBMITTED). SEC. R405.4.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 ORIGINAL COMMENT:
 3- VALUATION DECLARED IN THE PERMIT IS TOO LOW BASED ON
 THE SCOPE OF WORK SHOWN ON PLANS. VALUATION TO INCLUDE
 ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT
 AND ALL DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC.
 109.3 CITY AMENDMENTS. REVISE VALUATION AS REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 4- PROVIDE PRODUCT APPROVAL ( 2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 ORIGINAL COMMENT:
 A)ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 DETAILS SUBMITTED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. PROVIDE THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE
 SPECIFIED CONNECTOR OR DESIGN PROFESSIONAL TO LIST THE
 FLORIDA PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED
 CONNECTOR.
  
 ORIGINAL COMMENT:
 5- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 (INCLUDING THE ONES ALREADY SUBMITTED) AS REQUIRED BY
 SEC. 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 NEW COMMENT:
 6- PLANS WERE REVISED. PLANS SHOW WINDOW HEATING AND
 COOLING UNIT INSTEAD OF SPLIT A/C UNIT. REMOVABLE
 WINDOW UNIT IS NOT ALLOWED TO PROVIDE HEATING AS
 REQUIRED BY SEC. R303.9 FBC-RESIDENTIAL. REVISE PLANS
 SHOWING THE HEATING AND COOLING UNIT IN A PERMANENT
 FRAMED SPACE. REVISE FLOOR PLAN AND EXTERIOR ELEVATION
 ACCORDINGLY. AND PROVIDE FRAMING DETAILS AND
 SPECIFICATIONS. SEC. R301.1 FBC-RESIDENTIAL.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-09-19 Cont ID  
Sent By jgomez Date 2016-09-19 Time 08:21 Rev Time 0.00
Received By jgomez Date 2016-09-16 Time 18:48 Sent To  
Notes
2016-09-16 18:49:11RESIDENTIAL (R3) CHANGE OF USE/ALTERATION BUILDING
 REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. R101.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 NOTE: NEED ENERGY CALCULATIONS FOR EACH SEPARATE
 STRUCTURE.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 3- SCOPE OF WORK ON SHEET A-1 CALLS FOR "REPAIR OF 3
 EXISTING FIRE DAMAGED TRUSSES PER ROOF PLAN. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR THE TRUSSES
 REPAIRS. SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 4- WINDOW SCHEDULE ON SHEET A-2: WINDOWS #3 AND #4
 DON'T COMPLY WITH EGRESS REQUIREMENTS. REVISE STATEMENT
 SPECIFYING "SINGLE HUNG EGRESS SIZED". SEC. R310
 FBC-RESIDENTIAL.
  
 5- VALUATION DECLARED IN THE PERMIT IS TOO LOW BASED ON
 THE SCOPE OF WORK SHOWN ON PLANS. VALUATION TO INCLUDE
 ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT
 AND ALL DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC.
 109.3 CITY AMENDMENTS. REVISE VALUATION AS REQUIRED.
  
 6- PROVIDE PRODUCT APPROVAL ( 2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) PLASTIC SOFFIT VENT AS SPECIFIED ON THE TYPICAL WALL
 SECTION ON SHEET D1.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 DETAILS SUBMITTED.
  
 7- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 (INCLUDING THE ONES ALREADY SUBMITTED) AS REQUIRED BY
 SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-02-15 Cont ID  
Sent By vperez Date 2017-02-15 Time 09:09 Rev Time 0.00
Received By vperez Date 2017-02-15 Time 09:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-11-01 Cont ID  
Sent By vperez Date 2016-11-01 Time 11:33 Rev Time 0.00
Received By vperez Date 2016-11-01 Time 11:33 Sent To  
Notes
2016-11-01 12:08:402ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PRIOR COMMENTS ADDRESSED. BASED ON NEW SERVICE
 ARRANGEMENT SHOWN, THE MAIN BREAKERS MUST BE GROUPED IN
 ONE LOCATION PER FBC RES E3601.7 AND THE SHOW A
 GROUNDING ELECTRODE ARRANGEMENT AT THE SEPARATE
 STRUCTURE. SEPARATE STRUCTURE MUST STILL BE MCB PANEL
 TYPE NOT A MLO.
 2. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-09-22 Cont ID  
Sent By njwira Date 2016-09-19 Time 10:45 Rev Time 0.00
Received By albarran Date 2016-09-22 Time 15:44 Sent To I
Notes
2016-09-22 18:54:25ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME:
 JOB ADDRESS: 3912 GREENWOOD AVENUE
 DESCRIPTION: INTERIOR RENOVATIONS
 MASTER PERMIT: 16080928
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. AN ELECTRICAL SUB PERMIT IS REQUIRED.
 2. THIS PROPERTY IS ZONED SINGLE FAMILY AND THEREFORE
 JUST LIKE THE SECOND KITCHEN IS NOT ALLOWED, NEITHER IS
 THE SECOND ELECTRICAL METER. CORRECT THE PLANS
 ACCORDINGLY.
 3. THE RISER DIAGRAM AS SUBMITTED DOES NOT COMPLY WITH
 CODE REQUIREMENTS, AND DOES NOT SPECIFICALLY REFLECT
 THE SITE CONDITIONS AS SHOWN ON PLANS. YOU ARE ONLY
 ALLOWED ONE SERVICE LATERAL OR DROP.
 4. THE CORRECTED RISER MUST INCLUDE THE INTER-SYSTEM
 BONDING TERMINAL AND CONDUCTOR INSULATION TYPE, AND
 PANEL TYPE. INDOOR OR OUTDOOR ETC.
 5. CORRECT THE PANEL SCHEDULE TO SHOW THE OVERCURRENT
 PROTECTION FOR THE SUB PANEL (B).
 6. BOTH PANEL SCHEDULES INDICATE LOCATION AS IN THE
 GARAGE; THIS DOES NOT MATCH THE DRAWINGS.
 7. ACCORDING TO THE SAME PANEL SCHEDULES THEY CALL FOR
 FLUSH MOUNTED PANELS, YET THE DRAWINGS INDICATE A
 SURFACE MOUNTED.
 8. CORRECT THE LOAD CALCS TO MATCH THE CORRECTED RISER
 AND SITE DEMANDS.
 9. WATER HEATER IS REQUIRED IN THE DWELLING. YOU SHOW
 AS OPTIONAL. YOU HAVE TO DECIDE AS THE LOAD CALCS FOR
 THIS HAVE TO BE INCLUDED. FURTHERMORE INDICATE WHETHER
 THEY ARE GOING TO BE GAS OR ELECTRIC.
 10. CORRECT THE LOAD CALCS FOR PANEL B TO REMOVE THE
 RANGE LOAD AND CIRCUIT.
 11. SHEET M1 SHOWS THE POWER REQUIREMENTS FOR THE HVAC
 EQUIPMENT IS 208/230; THE HOUSE SERVICE IS 120/240
 CORRECT THIS ACCORDINGLY.
 12. GAS METER SHALL BE FURTHER THAN 10? FROM EITHER THE
 ELECTRICAL PANEL OR METER SOCKET.
 13. SHEET M1 REFLECTS A SECOND GAS METER ON THE
 EXTERIOR OF THE GARAGE WHICH DOES NOT APPEAR ON SHEET
 E1. WHICH IS CORRECT?
 14. BOXES USED AT LUMINAIRE OR LAMPHOLDER OUTLETS IN A
 CEILING SHALL BE REQUIRED TO SUPPORT A LUMINAIRE
 WEIGHING A MINIMUM OF 50 LB. ADD THIS TO THE NOTES ON
 CEILING BOXES ON PAGE.
 15. BOXES USED FOR THE SOLE SUPPORT OF CEILING FANS
 SHALL BE MARKED BY THE MANUFACTURER AS SUITABLE FOR THE
 PURPOSE, AND INDICATE THE WEIGHT LIMITATIONS BUT SHALL
 NOT BE USED TO SUPPORT PADDLE FANS HEAVIER THAN 70 LBS.
 16. IN DWELLING UNITS, AT LEAST ONE RECEPTACLE OUTLET
 SHALL BE INSTALLED IN BATHROOMS WITHIN 3 FT. OF THE
 OUTSIDE EDGE OF EACH BASIN.
 17. YOU SHALL MARK THE PLANS WITH THE DRAWING SCALE
 USED AND THE COMPASS ARROW.
 18. THE PLANS SHOW THE HVAC EQUIPMENT INSIDE THE ATTIC.
 AT LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE
 PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING.
 I SUGGEST THAT THIS SWITCH HAVE A PILOT LIGHT TO
 INDICATE IF THE ATTIC LIGHT IS ON.
 19. A 125 VOLT, SINGLE-PHASE, 15 OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT.
 20. BECAUSE THE BATHROOMS DO NOT HAVE WINDOWS, THE
 EXHAUST FAN IS REQUIRED THEREFORE IT SHALL COME ON
 WHENEVER THE ROOM IS OCCUPIED AND THUS CONNECTED TO THE
 LIGHT SWITCH. IF THE FAN IS LESS THAT 50CFM IT SHALL
 HAVE CONTINUOUS OPERATION AND THUS BE NON-SWITCHED.
 21. IN ALL AREAS SPECIFIED IN 210.52, ALL 125-VOLT, 15
 AND 20 AMPERE RECEPTACLES SHALL BE LISTED TAMPER
 RESISTANT RECEPTACLES.
 22. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS,
 LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATIONS ROOMS,
 CLOSETS, HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE
 PROTECTED BY A COMBINATION TYPE ARC-FAULT CIRCUIT
 INTERRUPTER INSTALLED TO PROVIDE PROTECTION OF THE
 BRANCH CIRCUIT.
 23. PERMANENTLY CONNECTED APPLIANCES OF OVER 300 VA OR
 1/8 HP REQUIRE A DISCONNECT WITHIN SIGHT OF THE
 APPLIANCE. THIS APPLIES TO BOTH WATER HEATERS AND HVAC
 EQUIPMENT.
 24. BECAUSE OF THE GAS APPLIANCES YOU ARE TO COMPLY
 WITH THE CARBON MONOXIDE DETECTOR REQUIREMENTS.
 25. A MINIMUM OF 75% OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY
 LAMPS OR A MINIMUM OF 75% OF THE PERMANENTLY INSTALLED
 LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH EFFICIENCY
 LAMPS
  
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-09-22 Cont ID  
Sent By gjohnson Date 2016-09-22 Time 15:39 Rev Time 0.00
Received By gjohnson Date 2016-09-22 Time 15:39 Sent To  
Notes
2016-09-22 15:42:16GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 4 Status F Date 2017-03-27 Cont ID  
Sent By destabro Date 2017-03-27 Time 16:32 Rev Time 0.00
Received By destabro Date 2017-03-27 Time 16:32 Sent To B
Notes
2017-04-13 10:18:094/13/2017 - APPLICANT REQUESTED NEW REVIEW BASED ON
 REVISED PLANS WITH PERMIT. NO NEW PLANS WERE PROVIDED.
 THE ONES INCLUDED WITH THE PERMIT DATE FROM FEBRUARY
 (2017) AND STILL CONTAIN WINDOW ALTERATIONS AND CHANGES
 TO THE GARAGE THAT REQUIRE A COA. THIS PERMIT WILL NOT
 BE APPROVED AS IT STANDS CURRENTLY. THE APPLICANT WILL
 EITHER NEED TO SUBMIT A COA FOR THE PROPOSED WORK, OR
 LEAVE THE WINDOW OPENINGS UNALTERED IN SIZE (AND ALL
 INTACT; THE PLANS REQUIRED THE REMOVAL OF THE NW ONE TO
 INSTALL A METER). ADDITIONALLY, THE GARAGE MUST BE
 MAINTAINED IN APPEARANCE, AND CANNOT BE STUCCO'D OVER
 TO CREATE AN ACCESSORY UNIT. ADDITIONALLY, THE
 APPLICANT SHOULD BE AWARE THAT ALTHOUGH THE SECONDARY
 UNIT DOES NOT HAVE A STOVE/OVEN, AND IT IS TECHNICALLY
 PERMITTED, HE WILL NOT BE GRANTED A RENTAL LICENSE FOR
 THE THIS UNIT. QUESTIONS MAY BE DIRECTED TO FRIEDERIKE
 MITTNER, AT 561.822.1457.
2017-03-27 16:32:503/27/2017 - PLANS STILL REFLECT WORK THAT REQUIRES A
 COA - PERMIT FAILED UNTIL APPLICANT SUBMITS COA AND
 SPEAKS TO HISTORIC PRESERVATION SECTION. DLE
2017-03-27 14:45:08ROUTED TO DESIREE ESTABROOK

Review Stop HIST HISTORICAL
Rev No 3 Status F Date 2017-03-14 Cont ID  
Sent By destabro Date 2017-03-14 Time 15:10 Rev Time 0.00
Received By destabro Date 2017-03-14 Time 15:10 Sent To B
Notes
2017-03-14 15:12:333/14/2017 - FAILED TO SUBMIT COA OR ADDRESS HISTORIC
 COMMENTS.

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2016-11-04 Cont ID  
Sent By destabro Date 2016-11-04 Time 14:31 Rev Time 0.00
Received By destabro Date 2016-11-04 Time 14:31 Sent To Z
Notes
2016-11-04 14:35:1011/4/16 - COA REQUIRED FOR PROPOSED WORK. REPLACEMENT
 WINDOWS AND GARAGE CONVERSION STILL REQUIRE REVIEW, AND
 COMMENTS FROM HISTORIC WERE NOT ADDRESSED. DLE

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2016-09-23 Cont ID  
Sent By destabro Date 2016-09-23 Time 10:39 Rev Time 0.00
Received By destabro Date 2016-09-23 Time 10:39 Sent To B
Notes
2016-09-23 10:44:099/23/16 - APPLICANT PREVIOUSLY ADVISED THAT THIS IS A
 CONTRIBUTING PROPERTY TO THE NORTHWOOD HILLS HISTORIC
 DISTRICT. NEW SIDING, WINDOW REPLACEMENTS, AND ANY
 OTHER EXTERIOR WORK WILL REQUIRE A COA AND HISTORIC
 REVIEW. PROPOSED SCOPE OF WORK DOES NOT FOLLOW THE
 DESIGN GUIDELINES FOR THIS HISTORIC DISTRICT. QUESTIONS
 MAY BE DIRECTED TO EITHER FRIEDERIKE MITTNER OR DESIREE
 ESTABROOK, HISTORIC PRESERVATION PLANNERS, AT
 561.822.1457.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-03-29 Cont ID  
Sent By jgomez Date 2017-03-29 Time 07:27 Rev Time 0.00
Received By jgomez Date 2017-03-21 Time 14:08 Sent To  
Notes
2017-03-27 14:09:2203/27/17 PLANS SENT TO ZONING SHELF FOR HISTORIC
 REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-03-15 Cont ID  
Sent By cpuell Date 2017-03-15 Time 16:26 Rev Time 0.00
Received By cpuell Date 2017-01-26 Time 11:50 Sent To  
Notes
2017-01-27 11:50:43R25

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-27 Cont ID  
Sent By lmarchan Date 2017-01-27 Time 11:50 Rev Time 0.00
Received By lmarchan Date 2016-10-20 Time 11:00 Sent To  
Notes
2016-10-21 11:00:47R10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-22 Cont ID  
Sent By albarran Date 2016-09-22 Time 18:58 Rev Time 0.00
Received By albarran Date 2016-08-22 Time 13:06 Sent To  
Notes
2016-09-22 18:58:309/22/16-FAILED MULTIPLE TRADE REVIEWS. CONTRACTOR
 NOTIFIED VIA EMAIL. FILE SENT TO LARGE DENIED B DRAWER.
 MA
2016-08-23 13:07:02R25

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-03-27 Cont ID  
Sent By jgomez Date 2016-11-16 Time 09:26 Rev Time 0.00
Received By jgomez Date 2016-11-16 Time 09:25 Sent To  
Notes
2016-11-16 09:26:50NO IMPACT FEES DUE. MU-2016-25851 DATED 10/18/16.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-09-19 Cont ID  
Sent By jgomez Date 2016-09-19 Time 11:08 Rev Time 0.00
Received By jgomez Date 2016-09-19 Time 11:01 Sent To  
Notes
2016-09-19 11:08:251- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2017-03-27 Cont ID  
Sent By jgomez Date 2017-03-27 Time 13:28 Rev Time 0.00
Received By jgomez Date 2017-03-27 Time 10:38 Sent To HIST
Notes
2017-03-27 10:37:57RESIDENTIAL (R3) CHANGE OF USE/ALTERATION MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 MECHANICAL REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT CONTRACTOR MAY SUBMIT REQUIRED INFORMATION
 AFTER THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO
 AVOID CONFLICTS/DELAYS. REVISION FEES WILL APPLY.
 CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED AT
 THIS TIME OR IF RE-SUBMITTING CORRECT INFORMATION.
  
 1- REVISED EQUIPMENT CALCULATIONS FOR THE REAR
 STRUCTURE NEEDS TO BE REVISED. SELECTED EQUIPMENT NEEDS
 TO BE CHANGED. "THE CORRESPONDING LATENT CAPACITY OF
 THE EQUIPMENT SHALL NOT BE LESS THAN THE CALCULATED
 LATENT LOAD". SEC. R403.6.1.1 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 2- EQUIPMENT SHOWN ON DRAWING M1 FOR THE REAR STRUCTURE
 DOESN'T MATCH EQUIPMENT SHOWN ON THE REVISED EQUIPMENT
 SIZING CALCULATIONS. REVISE AS REQUIRED TO MATCH ,
 INCLUDING THE SEER. SEC. R403.6.1.1 FBC-ENERGY
 CONSERVATION.
  
 3- ONLY THE SUMMARY SHEET OF THE EQUIPMENT SIZING
 CALCULATIONS WAS SUBMITTED. PROVIDE THE COMPLETE
 EQUIPMENT SIZING CALCULATIONS FOR THE MAIN HOUSE AND
 FOR THE REAR STRUCTURE. SEC. R403.6.1.1 FBC-ENERGY
 CONSERVATION.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-02-06 Cont ID  
Sent By jgomez Date 2017-02-06 Time 11:16 Rev Time 0.00
Received By jgomez Date 2017-02-06 Time 11:11 Sent To  
Notes
2017-02-06 11:16:34RESIDENTIAL (R3) CHANGE OF USE/ALTERATION THIRD
 MECHANICAL REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY
 SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). PROVIDE THE EQUIPMENT MANUFACTURER AND MODEL
 NUMBER OF THE OUTDOOR AND INDOOR UNITS AND THE AHRI
 LISTING. NOTE: ALL EQUIPMENT INFORMATION TO MATCH
 EQUIPMENT INFORMATION SHOWN ON DRAWING M1 SUBMITTED.
 NOTE: NEED EQUIPMENT SIZING CALCULATIONS FOR EACH
 SEPARATE STRUCTURE.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
 NEED TO PROVIDE THE COMPLETE EQUIPMENT SIZING
 CALCULATIONS FOR EACH BUILDING. ONLY A ONE SUMMARY FOR
 THE MAIN HOUSE WAS SUBMITTED. PROVIDE COMPLETE LOAD
 CALCULATIONS FOR EACH BUILDING.
  
 2- PROVIDE MANUFACTURER'S INFORMATION FOR THE A/C UNIT
 SPECIFIED FOR THE GARAGE CONVERSION SHOWING THE SEER
 SPECIFIED ON PLANS. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-11-16 Cont ID  
Sent By jgomez Date 2016-11-16 Time 10:22 Rev Time 0.00
Received By jgomez Date 2016-11-16 Time 10:22 Sent To P
Notes
2016-11-16 10:26:25RESIDENTIAL (R3) CHANGE OF USE/ALTERATION SECOND
 MECHANICAL REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 ORIGINAL COMMENT:
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY
 SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). PROVIDE THE EQUIPMENT MANUFACTURER AND MODEL
 NUMBER OF THE OUTDOOR AND INDOOR UNITS AND THE AHRI
 LISTING. NOTE: ALL EQUIPMENT INFORMATION TO MATCH
 EQUIPMENT INFORMATION SHOWN ON DRAWING M1 SUBMITTED.
 CHECK CFM'S SPECIFIED FOR UNIT #1 AND UNIT #2. WHY THE
 GUEST HOUSE HAS MORE CFM'S THAN THE MAIN HOUSE?
 NOTE: NEED EQUIPMENT SIZING CALCULATIONS FOR EACH
 SEPARATE STRUCTURE.
  
 RESPONSE:
 NEED TO PROVIDE THE COMPLETE EQUIPMENT SIZING
 CALCULATIONS FOR EACH BUILDING. ONLY A ONE SUMMARY FOR
 THE MAIN HOUSE WAS SUBMITTED. PROVIDE COMPLETE LOAD
 CALCULATIONS FOR EACH BUILDING.
  
 NEW COMMENT:
 2- PROVIDE MANUFACTURER'S INFORMATION FOR THE A/C UNIT
 SPECIFIED FOR THE GARAGE CONVERSION SHOWING THE SEER
 SPECIFIED ON PLANS. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-09-19 Cont ID  
Sent By jgomez Date 2016-09-19 Time 15:12 Rev Time 0.00
Received By jgomez Date 2016-09-19 Time 15:12 Sent To  
Notes
2016-09-19 15:17:18RESIDENTIAL (R3) CHANGE OF USE/ALTERATION MECHANICAL
 REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY
 SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). PROVIDE THE EQUIPMENT MANUFACTURER AND MODEL
 NUMBER OF THE OUTDOOR AND INDOOR UNITS AND THE AHRI
 LISTING. NOTE: ALL EQUIPMENT INFORMATION TO MATCH
 EQUIPMENT INFORMATION SHOWN ON DRAWING M1 SUBMITTED.
 CHECK CFM'S SPECIFIED FOR UNIT #1 AND UNIT #2. WHY THE
 GUEST HOUSE HAS MORE CFM'S THAN THE MAIN HOUSE?
 NOTE: NEED EQUIPMENT SIZING CALCULATIONS FOR EACH
 SEPARATE STRUCTURE.
  
 2- BALANCE RETURN INFORMATION FOR BEDROOM #2 IS NOT
 CLEAR. CLEARLY SPECIFY SIZE OF TRANSFER DUCT FOR
 BEDROOM #2. SEE SIZE OF GRILLE SPECIFIED. AND, PROVIDE
 DETAILS SHOWING HOW IS IT GOING TO BE INSTALLED WITHOUT
 INTERFERING WITH THE AIR HANDLER UNIT ABOVE. SEC.
 M1602.4 FBC-RESIDENTIAL. 5TH EDITION (2014).
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-02-14 Cont ID  
Sent By gjohnson Date 2017-02-14 Time 17:01 Rev Time 0.00
Received By gjohnson Date 2017-02-14 Time 16:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-11-22 Cont ID  
Sent By gjohnson Date 2016-11-22 Time 17:08 Rev Time 0.00
Received By gjohnson Date 2016-11-22 Time 17:08 Sent To  
Notes
2016-11-22 17:10:121ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLUMBING PAGES MISSING FROM NEW SET OF PLANS ,
 PLEASE PROVIDE PLUMBING RISER DIAGRAMS. PER WPB AMEND
 TO FBC 107.2.1

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-09-22 Cont ID  
Sent By gjohnson Date 2016-09-22 Time 15:39 Rev Time 0.00
Received By gjohnson Date 2016-09-22 Time 15:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2017-03-14 Cont ID  
Sent By njwira Date 2017-02-07 Time   Rev Time 0.00
Received By njwira Date 2017-02-07 Time 13:49 Sent To I
Notes
2017-02-07 15:50:422/7/17- PASSED
 NO 2ND KITCHEN OR UNIT PERMITTED
 LANDSCAPE PERMIT REQUIRED
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  
2017-02-03 18:39:31NEED RE-STAMP. TWO NEW SET OF DRAWINGS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 2 Status P Date 2016-11-14 Cont ID  
Sent By njwira Date 2016-11-14 Time 10:59 Rev Time 0.00
Received By njwira Date 2016-11-07 Time 08:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-09-19 Cont ID  
Sent By nwair Date 2016-09-07 Time 13:26 Rev Time 0.00
Received By njwira Date 2016-08-26 Time 15:50 Sent To E
Notes
2016-09-19 10:45:24CANNOT HAVE A SECOND UNIT WITH A SECOND KITCHEN.
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  