Plan Review Details - Permit 16080912
Plan Review Stops For Permit 16080912
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-12-15 Cont ID  
Sent By mvaldes Date 2016-12-15 Time 08:20 Rev Time 0.00
Received By mvaldes Date 2016-12-15 Time 08:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-25 Cont ID  
Sent By mvaldes Date 2016-08-25 Time 10:12 Rev Time 0.00
Received By mvaldes Date 2016-08-25 Time 10:12 Sent To  
Notes
2016-08-25 10:13:07REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 1] PROVIDE AN ADEQUATE SIGN AND SEAL PER FLORIDA STATUE
 471 & FLORIDA ADMINISTRATIVE CODE 61G15-23.002
  
 2] ADDRESS FIRE COMMENTS TO PASS THE ELECTRICAL REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-12-14 Cont ID  
Sent By wjolin Date 2016-12-14 Time 10:01 Rev Time 0.00
Received By wjolin Date 2016-12-14 Time 09:57 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-08-24 Cont ID  
Sent By wjolin Date 2016-08-24 Time 10:01 Rev Time 0.00
Received By wjolin Date 2016-08-24 Time 09:56 Sent To E
Notes
2016-08-24 10:01:22906 GRANT STREET
 PERMIT #16080912
 TRACKING #
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLANS INDICATE AN INCORRECT ADDRESS OF "906 GRAND
 STREET."
  
 NO PRODUCT CUTSHEETS SUBMITTED.
  
 NO SITE PLAN PROVIDED SHOWING THE LOCATION OF THE
 BUILDING.
  
 SEVERAL VISUAL APPLIANCES INDICATE A CANDELA OF 102CD.
  
 NO MANUAL PULL STATIONS PROVIDED ON FIRST FLOOR.
  
 SHEET FA-2: WHY IS THE ANNUNCIATOR PANEL LOCATED INSIDE
 DWELLING UNIT #110?
  
 SHEET FA-8: NOTE 5 INDICATES "BATTERY BACK-UP OF
 4-HOURS OF SUPERVISORY MODE" IS NEEDED. NFPA 72
 REQUIRES 24-HOURS OF A SECONDARY POWER SUPPLY IN
 STANDBY MODE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-15 Cont ID  
Sent By mvaldes Date 2016-12-15 Time 08:20 Rev Time 0.00
Received By mvaldes Date 2016-12-01 Time 16:04 Sent To  
Notes
2016-12-07 16:04:30RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-25 Cont ID  
Sent By mvaldes Date 2016-08-25 Time 10:13 Rev Time 0.00
Received By mvaldes Date 2016-08-22 Time 11:05 Sent To  
Notes
2016-08-22 11:06:02ROUTED TO FIRE INBOX