Plan Review Details - Permit 16080906
Plan Review Stops For Permit 16080906
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-10-31 Cont ID  
Sent By jwitmer Date 2016-10-31 Time 09:57 Rev Time 0.00
Received By jwitmer Date 2016-10-31 Time 09:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-10-25 Cont ID  
Sent By jwitmer Date 2016-10-25 Time 08:51 Rev Time 0.00
Received By jwitmer Date 2016-10-25 Time 08:51 Sent To  
Notes
2016-10-25 08:56:44BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080906
 ADD: 1801 N. FLAGLER DR. SUITE # 532
 CONT: COPPERSTONE
 TEL: 561-628-7891
 E-MAIL: ???????? PLEASE PROVIDE E-MAIL ADDRESS, THAT IS
 HOW WE COMUNICATE TO THE CONTRACTOR.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. OCT. 25/2016
 ACTION: DENIED
  
 1) THE CONTRACTOR WHICH IS THE AUTHOR OF THE PLANS HAS
 NOT PRINTED THEIR NAME, SIGNED THEIR NAME NOR LICENSE
 NUMBER. 107.3.4.3 CERTIFICATIONS BY CONTRACTORS
 AUTHORIZED. THERE ARE NO FLOOR PLANS WHERE THE CGC HAS
 TAKEN OWNERSHIP OF THE DESIGNED PLAN BY PRINTING THEIR
 NAME, SIGNING THEIR NAME AND LICENSE NUMBER TO THE
 DOCUMENT.
  
 2) THE PLANS SUBMITTED INDICATE THE INSTALATION OF TILE
 IN THE BATHROOM. THE FLOOR INSULATION PRODUCT SUBMITTED
 QUIET CORK HAS NOT SUBMITTED THE REQUIRED (3) TEST
 REPORTS.
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) QEP HAS NO FIRE TESTING, THE REPORT SUBMITTED BY
 BADGER CORK HAS BEEN BOUGHT OUT BY ANOTHER COMPANY, QEP
 HAS TO HAVE THIER OWN FIRE TESTING REPORT.
 FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. INSULATION
 INSTALLED BETWEEN A FINISHED FLOOR AND SOLID DECKING
 WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-30 Cont ID  
Sent By jwitmer Date 2016-08-30 Time 11:13 Rev Time 0.00
Received By jwitmer Date 2016-08-30 Time 11:13 Sent To  
Notes
2016-08-30 11:27:11BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080906
 ADD: 1801 N. FLAGLER DR. SUITE # 532
 CONT: COPPERSTONE
 TEL: 561-628-7891
 E-MAIL: ???????? PLEASE PROVIDE E-MAIL ADDRESS, THAT IS
 HOW WE COMUNICATE TO THE CONTRACTOR.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. AUGUST 30/2016
 ACTION: DENIED
  
 1) THE CONTRACTOR WHICH IS THE AUTHOR OF THE PLANS HAS
 NOT PRINTED THEIR NAME, SIGNED THEIR NAME NOR LICENSE
 NUMBER. 107.3.4.3 CERTIFICATIONS BY CONTRACTORS
 AUTHORIZED.
  
 2) THE PLANS SUBMITTED INDICATE THE INSTALATION OF TILE
 IN THE BATHROOM. THE FLOOR INSULATION PRODUCT SUBMITTED
 QUIET CORK HAS NOT SUBMITTED THE REQUIRED (3) TEST
 REPORTS.
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-09-28 Cont ID  
Sent By albarran Date 2016-09-28 Time 09:00 Rev Time 0.00
Received By albarran Date 2016-09-28 Time 08:21 Sent To I
Notes
2016-09-28 09:00:58MET WITH JOEL CHAPEL OF TOWER ELECTRIC AT FRONT COUNTER
 AND ALL CORRECTIONS WERE MADE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-09-01 Cont ID  
Sent By albarran Date 2016-09-01 Time 15:47 Rev Time 0.00
Received By albarran Date 2016-09-01 Time 15:37 Sent To  
Notes
2016-09-01 16:02:35ELECTRICAL REVIEW:
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC)
  
 PROJECT NAME:
 JOB ADDRESS: 1801 N. FLAGLER DR. #522
 DESCRIPTION: INSTALL DRYWALL IN BATHROOM/INSTALL TILE
 ON FLOOR & PAINT/INSTALL 5902 FT. CORK
 MASTER PERMIT: 16080906
  
 BELOW IS A LIST OF THE DEFICIENCIES NOTED ON THE
 SUBMITTED DRAWING: ADDITIONAL COMMENTS MAY ARISE OUT OF
 THE NEXT SUBMITTAL.
  
 1. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS REQUIRE
 THAT THE CONSTRUCTION DOCUMENTS BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE PROPOSED WORK AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO CODE REQUIREMENTS. (CLEARLY DEFINE YOUR
 SCOPE OF WORK ON THE PLANS). SUCH DRAWINGS SHALL
 INDICATE THE APPLICABLE DESIGN CODE, AND FURTHERMORE,
 THE DRAWINGS SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. (YOUR NAME AND
 SIGNATURE SHALL APPEAR ON ALL DOCUMENTS).
 2. ON THE DRAWING YOU INDICATE SOME DEVICES AS EXISTING
 AND OTHERS AS NEW. THIS AS WELL IS VERY AMBIGUOUS
 BECAUSE THERE IS NO DEFINITE COURSE OF ACTION WITH
 THESE ITEMS.
 3. THE CODE HAS SPECIFIC OUTLET PLACEMENT REQUIREMENTS
 FOR BOTH THE KITCHEN & BATHROOM, THEREFORE THE BATHROOM
 FIXTURES AND KITCHEN CABINET LAYOUT SHALL BE PROVIDED
 TO ASCERTAIN COMPLIANCE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-10-18 Cont ID  
Sent By pleduc Date 2016-10-18 Time   Rev Time 0.00
Received By pleduc Date 2016-10-17 Time 17:06 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-08-29 Cont ID  
Sent By pleduc Date 2016-08-29 Time   Rev Time 0.00
Received By pleduc Date 2016-08-26 Time 13:51 Sent To  
Notes
2016-08-26 14:07:10THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED PLAN LACKS SUFFICIENT DETAIL TO
 COMPLETE AN ACCURATE FIRE REVIEW.
  
  
 2) PROVIDE MANUFACUTURES DETAIL FOR THE FLAME AND SMOKE
 SPREAD OF THE CORK MATERIAL.
  
 THE FLOORING UNDERLAYMENT SHALL MEET THE REQUIRMENTS OF
 NFPA 101, CHAOTER 10, INTERIOR FINISH, CONTENTS, AND
 FURNISHINGS, AND ALL APPLICABLE CODES.
  
  
 3) PLEASE INDICATE IF THE SPACE HAS A FIRE ALARM AND/OR
 FIRE SPRINKLERS.
  
 PLEASE INDICATE AND FIRE ALARM DEVICE OR SPRINKLER HEAD
 EXISTS IN THE BATHROOM AND IF THE NEW SHOWER
 INSTALLATION WILL IMPACT THOSE DEVICES.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-10-25 Cont ID  
Sent By jwitmer Date 2016-10-25 Time 08:51 Rev Time 0.00
Received By jwitmer Date 2016-10-12 Time 13:56 Sent To  
Notes
2016-10-13 13:57:00RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-28 Cont ID  
Sent By albarran Date 2016-09-28 Time 09:01 Rev Time 0.00
Received By albarran Date   Time   Sent To  
Notes
2016-09-28 09:03:079/28/16 APPROVED ELECTRICAL REVIEW AND RETURNED FILE TO
 SMALL C. CONTRACTOR PREVIOUSLY NOTIFIED BY GJ. MA

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-22 Cont ID  
Sent By gjohnson Date 2016-09-22 Time 14:34 Rev Time 0.00
Received By gjohnson Date 2016-08-22 Time 12:48 Sent To  
Notes
2016-08-22 12:49:09B10

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-09-22 Cont ID  
Sent By gjohnson Date 2016-09-22 Time 14:30 Rev Time 0.00
Received By gjohnson Date 2016-09-22 Time 14:30 Sent To  
Notes
***NONE***