| 2016-09-09 15:13:36 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16080844 |
| | ADD: 1101 54TH ST. |
| | CONT: ALBU & ASSOCIATES |
| | TEL: 407-788-1450 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: THURS. SEPT. 08/2016 |
| | ACTION: DENIED |
| | |
| | 1) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH |
| | ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES |
| | TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH |
| | THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND |
| | THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR |
| | GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS |
| | ORDINANCE. |
| | PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| | CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| | ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| | 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| | PROJECT CONSTRUCTION COST. |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. |
| | FOR CONTACT INFORMATION PLEASE CONTACT: |
| | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR |
| | 822-1515 E-MAIL: [email protected] |
| | |
| | 2) THE BUILDING PERMIT FOR THIS PROJECT INDICATES THE |
| | VALUE FOR THE PROJECT OF $2,643,849.00 DOLLARS. PLEASE |
| | NOTE THIS VALUE SHOULD ONLY REFLECT THE BUILDING, NOT |
| | ANY OF THE PERMIT VALUES FOR THE SITE IMPROVEMENT. |
| | THERE ARE (4) PERMITS THAT WILL COST $80.00 AN |
| | ADMINISTRATIVE FEE, (MECHANICAL, ELECTRICAL, PLUMBING & |
| | ROOFING) THESE VALUES SHOULD REMAIN IN THE BUILDING |
| | PERMIT. THE OTHER PERMITS TO BE REVIEWED UNDER SEPARATE |
| | PERMIT, WITH SEPARATE ASSOCIATED FEES ARE: FIRE |
| | SPRINKLER, FIRE ALARM, ALL LOW VOLTAGE PERMITS, KITCHEN |
| | EXHAUST HOODS, FIRE SUPPRESSION SYSTEMS, WALK IN |
| | COOLERS & FREEZERS, GREASE INTERCEPTORS? |
| | |
| | PERMITS THAT ARE NOT INCLUDED IN THE BUILDING PERMIT |
| | VALUE AND ARE SITE IMPROVEMENT PERMITS WOULD BE |
| | SITE CLEARING PERMITS, UNDERGROUND UTILITIES, LIFT |
| | STATIONS, PAVING AND DRAINAGE, STRIPPING OF PARKING |
| | LOTS, IRRIGATION, LANDSCAPE, SIGN PERMITS AWNINGS? |
| | |
| | 3) SHEET LS1.0 UNDER THE HEADING CODE INFORMATION LIST |
| | THE WIND DESIGN TO ASCE 7-02. PLEASE REFER TO THE 2014 |
| | FBC-B 1609.1.1 AND CHAPTER 35 THE REFERENCED STANDARDS |
| | ASCE 7-10. |
| | |
| | 4) SHEET LS1.0 UNDER THE HEADING PROJECT USE A NEW |
| | CHEMICAL DEPENDENCY TREATMENT CENTER. THE OCCUPANCY |
| | TYPE A MIXED USE OF BUSINESS & I-1 ALCOHOL AND DRUG |
| | CENTERS). PLEASE BE AWARE IF THERE IS |
| | FOR MEDICAL CARE ON A 24-HOUR BASIS FOR MORE THAN FIVE |
| | PERSONS WHO ARE INCAPABLE OF SELF-PRESERVATION |
| | (DETOXIFICATION FACILITIES) THEN THE OCCUPANCY |
| | CLASSIFICATION WILL BE INSTITUTIONAL GROUP I-2. 2014 |
| | FBC-B 308.4. |
| | |
| | 5) PLEASE ALSO NOTE IF THIS PERMIT WERE RECLASSIFIED TO |
| | A GROUP I-2 OCCUPANCY THEN A BUILDING TYPE 5-B IS NOT |
| | ALLOWED. SEE FBC-B TABLE 503. |
| | |
| | 6) SHEET LS1.0 IN THE UPPER LEFT HAND CORNER OF THE |
| | SHEET IS A HEADING, RATING AT 1-A SEPARATE FROM |
| | B-WING 1 HOUR CONSTRUCTION UNDERSIDE OF DECK. THERE ARE |
| | 2 NOTES (1) THE CEILING SLEEPING WING TO BE DESIGNED TO |
| | UL LISTING P522 1 HOUR RATING. NOTE (2) THE INTERIOR |
| | SLEEPING ROOM CORRIDOR WALLS DESIGNED TO UL LISTING |
| | U419. |
| | |
| | PLEASE REFER TO SECTION 708.4 FBC-B EXCEPTION # 3. IT |
| | APPEARS YOU ARE TAKING THIS EXCEPTION BY NOT RUNNING |
| | THE 1 HOUR FIRE RATED CORRIDOR WALLS UP TO THE |
| | UNDERSIDE OF THE ROOF DECK. EXCEPTION # 3 WHERE THE |
| | CORRIDOR CEILING IS CONSTRUCTED AS REQUIRED FOR THE |
| | CORRIDOR WALLS, THE WALLS SHALL BE PERMITTED TO |
| | TERMINATE AT THE UPPER MEMBRANE OF SUCH CEILING |
| | ASSEMBLY. |
| | |
| | PLEASE SEE THE 2012 IBC BASE CODE COMMENTARY. EXCEPTION |
| | # 3 ALLOWS FOR A CORRIDOR TO BE CONSTRUCTED IN A TUNNEL |
| | FASHION- WITH RATED WALLS AND A RATED TOP. IN THESE |
| | CASES THE WALLS ARE NOT REQUIRED TO EXTEND TO THE |
| | UNDERSIDE OF A RATED ASSEMBLY. THIS IS A UNIQUE |
| | PROVISION IN THE CODE AND THE FACT THAT IT PERMITS A |
| | WALL ASSEMBLY TO BE TURNED INTO A HORIZONTAL POSITION |
| | SHOULD NOT BE APPLIED TO OTHER SECTIONS OF THE CODE OR |
| | OTHER RATED ASSEMBLIES. SEE FIGURE 708.4(2)( C ) FIRE |
| | PARTITION CONTINUITY. |
| | |
| | IN THIS CASE THE RATED WALL ASSEMBLY UL LISTING U419 |
| | NEEDS TO BE TURNED ON ITS SIDE AND RATED DRYWALL ON |
| | EACH FACE OF THE HORIZONTAL ASSEMBLY. |
| | |
| | 7) SHEET LS1.1 MISSING SCALE FOR THIS SHEET. 107.2.1.3 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 8) SHEET LS1.1 INDICATES THE BUILDING IS TO BE FIRE |
| | SPRINKLERED. THE BUILDING DOES NOT INDICATE IF THE FIRE |
| | SPRINKLER IS TO BE NFPA 13 FOR THE FULL BUILDING OR A |
| | PORTION THE INSTITUTIONAL DESIGNED TO BE A NFPA 13-R IN |
| | ACCORDANCE WITH 903.2.6 EXCEPTION 1 & 2. PLEASE NOTE IF |
| | THE FULL BUILDING IS NOT DESIGNED AS A FULL NFPA 13 |
| | SYSTEM THEN THE AREA INCREASE FOR FIRE SPRINKLERS |
| | CANNOT BE TAKEN. FBC-B 506.3. |
| | |
| | 9) SHEET A4.1 THE DOORS IDENTIFIED AS # 8 TO THE |
| | RESTROOMS 109 & 110 BOTH ARE SHOWN ON THE LIFE SAFETY |
| | SHEET IN A 1 HOUR FIRE RATED WALL BUT THE DOOR SCHEDULE |
| | ON A6.2 DOES NOT SHOW A FIRE RATED DOOR AND FRAME. 2014 |
| | FBC-B TABLE 716.5. |
| | |
| | 10) SHEET A4.1 VERSES S2.0 & S3.0 ON SHEET S2.0 NOTE # |
| | 2 INDICATES THE USE OF AN INTERNAL MONOLITHIC FOOTING |
| | IN THE NORTH END OF THE BUILDING BUT THERE ARE NO WALL |
| | IDENTIFICATION TAGS INDICATING THESE WALLS ARE TO BE |
| | LOAD BEARING WALLS. THE WALL SCHEDULE SHOWS A WALL TYPE |
| | P4 AS A BEARING WALL. ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 11) SHEET A4.2 VERSES S2.0 & S3.0 IN THE SOUTH END OF |
| | THE BUILDING ALSO INDICATES THE USE OF INTERNAL |
| | MONOLITHIC FOUNDATIONS. SHEET A4.2 ALSO SHOWS THE WALL |
| | TAG #7 FOR FIRE RATED WALLS. SHEET A6.1 IDENTIFIES THE |
| | P7 WALL AS UL LISTING U419 A NON-BEARING WALL? SHEET |
| | S3.0 DENOTES THIS AS A LOAD BEARING WALL, (362S162-33 |
| | METAL/ 16 INCHES O. C. |
| | |
| | 12) SHEET A4.2 AND SHEET LS1.1 DISCREPANCY IN PLANS, |
| | DOOR # 05 (CORRIDOR) HAS A 45 MIN. DOOR RATING SHEET |
| | LS1.1 AND A4.2, THE SAME DOOR IS IDENTIFIED AS # 5, THE |
| | DOOR SCHEDULE A6.2 INDICATES A 20 MIN. RATING, |
| | DISCREPANCY IN PLANS. 107.2.1.3 ADDITIONAL INFORMATION |
| | IS REQUIRED. SEE TABLE 716.5 FBC-B. |
| | |
| | 13) SHEET A4.2 AND SHEET LS1.1 DISCREPANCY IN PLANS, |
| | DOOR NUMBER 13 (NURSES BREAKROOM 147) HAS A 45 MIN. |
| | DOOR RATING SHEET LS1.1 AND A4.2, THE SAME DOOR IS |
| | IDENTIFIED A6.2 AS # 5, THE DOOR SCHEDULE INDICATES A |
| | 20 MIN. RATING, DISCREPANCY IN PLANS. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. SEE TABLE 716.5 |
| | FBC-B. |
| | |
| | 14) SHEET A4.2 AND SHEET LS1.1 DISCREPANCY IN PLANS. |
| | THE ADA RESTROOM # 193, 196 BOTH HAVE WALL TAG |
| | IDENTIFYING THE WALL AS P10 A 6 INCH 30 MIN RATING ON |
| | SHEET A4.2 WHEREAS SHEET LS1.1 IS INDICATED AS A 1 HOUR |
| | WALL DISCREPANCY IN PLANS. NOTE 708.3 EXCEPTION # 1 |
| | REFERS YOU TO TABLE 1018.1 WHEN REVIEWING BOTH |
| | FOOTNOTES B & C NO REDUCTION CAN BE TAKEN, 1 HOUR |
| | CORRIDOR WALL. |
| | |
| | 15) SHEET A4.2 AND SHEET LS1.1 THE DOCTORS OFFICE |
| | CORRIDOR WALL TYPE IDENTIFIED AS P7 1 HOUR RATED U419 |
| | ALSO HAS A WINDOW IDENTIFIED AS #7. SHEET A6.2 THE |
| | WINDOW SCHEDULE DOES NOT SHOW ANY COLUMN FOR FIRE RATED |
| | OPENINGS. PLEASE SHOW COMPLIANCE WITH SECTION TABLE |
| | 716.6 OF THE FBC-B. |
| | |
| | 16) SHEET A4.3 AND SHEET LS1.1. SHEET A4.3 ONLY HAS |
| | WALL IDENTIFICATION TAGS ON THE CORRIDOR WALLS. NONE OF |
| | THE OTHER WALLS WHICH LS1.1 SHOWS AS RATED WALLS ARE |
| | IDENTIFIED ON A4.3. PLEASE SHOW COMPLIANCE WITH SECTION |
| | 708.1 OF THE FBC-B. |
| | |
| | 17) SHEET S1.0 PROVIDES THE WIND DESIGN CRITERIA WITH |
| | AN EXPOSURE B. PLEASE REVIEW SECTION 1609.4.2 SURFACE |
| | ROUGHNESS C. OPEN TERRAIN WITH SCATTERED OBSTRUCTIONS |
| | HAVING HEIGHTS GENERALLY LESS THAN 30 FEET. THIS |
| | CATEGORY INCLUDES FLAT OPEN COUNTRY, AND GRASSLANDS. |
| | THIS SURFACE ROUGHNESS SHALL ALSO APPLY TO ANY BUILDING |
| | LOCATED WITHIN SURFACE ROUGHNESS B TYPE TERRAIN WHERE |
| | THE BUILDING IS WITHIN 100 FEET HORIZONTALLY IN ANY |
| | DIRECTION OF OPEN AREAS OF SURFACE ROUGHNESS C OR |
| | D-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET IN THE |
| | UPWIND DIRECTION AND A WIDTH GREATER THAN 150 FEET. |
| | |
| | 18) THE WINDOW AND DOOR PRESSURES WILL INCREASE WITH |
| | THE C EXPOSURE WITH THE ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. SEE TABLE 1609.7(2) FBC-B. |
| | |
| | 19) PLEASE ALSO PROVIDE THE ROOF PRESSURES FOR ZONES 1, |
| | 2, & 3. PLEASE PROVIDE THE PRESSURES IN THE VASD VALUES |
| | SINCE THE PRODUCT APPROVALS ARE IN VASD. PLEASE NOTE |
| | (2) ROOF CHARTS WILL BE REQUIRED, (1) FOR THE FLAT AREA |
| | OF THE ROOF AND A CHART FOR THE SLOPED ROOF 4:12. 2014 |
| | FBC-B 1603.1.4 WIND DESIGN DATA. |
| | |
| | 20A) PLEASE INDICATE IF EITHER THE CONTRACTOR OR THE |
| | DESIGNER OF RECORD WOULD PREFER TO DEFER THE PRODUCT |
| | APPROVALS UNTIL AFTER PERMIT ISSUANCE. 2014 FLORIDA |
| | BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 20B) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 20C) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 21) ROOF TOP A/C STANDS WILL REQUIRE A PRODUCT |
| | APPROVAL. EITHER THE CONTRACTOR OR THE DESIGNER OF |
| | RECORD WILL NEED TO COMPLETE THE FOLLOWING ON THE |
| | PRODUCT APPROVAL IN CALCULATING THE AREA OF THE ROOF |
| | TOP COMPRESSORS, THE MEAN ROOF HEIGHT OF THE STAND AND |
| | COMPRESSORS, WEIGHT, CIRCLED THE DESIGN PARAMETERS IN |
| | THE TABLES , ANCHORS AND UPLIFT VERSES MOMENT. |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS. |
| | |
| | 22) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 23) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |