Plan Review Details - Permit 16080840
Plan Review Stops For Permit 16080840
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-06-27 Cont ID  
Sent By jgomez Date 2017-06-27 Time 17:12 Rev Time 0.00
Received By jgomez Date 2017-06-27 Time 17:07 Sent To  
Notes
2017-06-27 17:16:04BUILDING REVIEW APPROVED WITH PROVISO: (NOTE: PROVIDE
 INFORMATION PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS)
 1- INFORMATION SHOWN ON THE FRAMING DETAIL AND WALL
 SECTION 1/A. DON'T MATCH. REVISE AS REQUIRED TO MATCH.
 NOTE: ENGINEER TO REVISE DETAILS AND PROVIDE NEW
 DRAWINGS WITHOUT WHITE-OUT OR PEN HANDWRITTEN
 INFORMATION.
 2- INFORMATION SHOWN ON THE FRAMING DETAIL IS NOT
 LEGIBLE. LETTERING IS TOO SMALL. REVISE AS REQ'D.
 PROVIDE LARGER LETTERING.
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: A) WINDOW
 MULLIONS. B) CURRENT HURRICANE SHUTTERS. C) MASTER
 BEDROOM EXTERIOR SWING DOOR. PROVIDE COMPLETE PRODUCT
 APPROVAL, INCLUDING THE FLORIDA PRODUCT APPROVAL COVER
 PAGE.
 4- ENGINEER OF RECORD TO APPROVE IN WRITING ABOVE
 PRODUCT APPROVALS.
 5- PROVIDE COMPLETE HURRICANE SHUTTERS INSTALLATION
 SCHEDULE (2 COPIES). SEE CITY SAMPLE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-05-04 Cont ID  
Sent By jgomez Date 2017-05-04 Time 08:48 Rev Time 0.00
Received By jgomez Date 2017-05-04 Time 07:43 Sent To  
Notes
2017-05-04 07:50:26RESIDENTIAL (R3) CHANGE OF USE/ALTERATION, SECOND
 BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014)
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT PERMIT MAY BE ISSUED AND CONTRACTOR MAY
 SUBMIT THE REQUIRED ITEMS AFTER THE PERMIT IS ISSUED
 BUT BEFORE INSPECTIONS TO AVOID CONFLICTS/DELAYS. NOTE:
 REVISION FEES MAY APPLY. CONTRACTOR TO RESPOND IN
 WRITING IF THE PROVISO OPTION IS PREFERRED AT THIS
 TIME. PERMIT MAY BE PROCESSED ONCE THE ENERGY
 CALCULATIONS ARE SIGNED BY THE OWNER/AGENT, CONTRACTOR
 COMPLETES THE EPL FORM AND THE COUNTY IMPACT FEES STAMP
 AND PAID RECEIPT (IF REQUIRED) IS PROVIDED.
  
 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. R101.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE: A) CONTRACTOR TO COMPLETE THE ENERGY
 PERFORMANCE LEVEL (EPL) CARD AS REQUIRED BY SEC.
 R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY AT THE
 BOTTOM OF THE ENERGY CALCULATIONS FORM SUBMITTED AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER NAME. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 2- INFORMATION SHOWN ON THE NEW "TYPICAL FRAMING AND
 CONNECTIONS @ OPENINGS" DETAIL DOESN'T MATCH
 INFORMATION SHOWN ON THE WALL SECTION 1/A. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- INFORMATION SHOWN ON THE NEW "TYPICAL FRAMING AND
 CONNECTIONS @ OPENINGS" DETAIL IS NOT LEGIBLE.
 LETTERING IS TOO SMALL TO READ AND IS NO ADEQUATE FOR
 RECORDS RETENTION SCANNING. SEC. 107.2.1 AND SEC.
 107.2.1.4 CITY AMENDMENTS. REVISE AS REQUIRED.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3 FOR:
 A) WINDOW MULLIONS AS SHOWN ON PLANS.
 RESPONSE: REPEAT COMMENT.
  
 B) NOA 12-0809.04 SUBMITTED FOR HURRICANE SHUTTERS
 EXPIRED ON 04/18/2017. PROVIDE 2 COPIES OF CURRENT NOA.
  
 C) NEW MASTER BEDROOM EXTERIOR SWING DOOR. PROVIDE
 FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPOND TO
 DRAWINGS SUBMITTED.
 RESPONSE: REPEAT COMMENT.
  
 5- ENGINEER OF RECORD TO APPROVE IN WRITING ABOVE
 PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 6- PROVIDE COMPLETE HURRICANE SHUTTERS INSTALLATION
 SCHEDULE (2 COPIES). SEE CITY SAMPLE. SEC. 107.2.1 CITY
 AMENDMENTS.
 RESPONSE: REPEAT COMMENT.
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-04-25 Cont ID  
Sent By jgomez Date 2017-04-25 Time 13:44 Rev Time 0.00
Received By jgomez Date 2017-04-25 Time 09:37 Sent To  
Notes
2017-04-25 09:38:14PLAN REVIEW FEES WERE NOT PAID. PLAN REVIEW FEES NEED
 TO BE PAID AT TIME OF PERMIT APPLICATION SUBMITTAL.
 PLAN REVIEW WILL NOT BE DONE UNTIL FEES ARE PAID.
 CONTRACTOR TO ADVICE WHEN THE FEES ARE PAID TO RESUME
 PLAN REVIEW CYCLE.
 THANK YOU.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-09-15 Cont ID  
Sent By jgomez Date 2016-09-15 Time 08:51 Rev Time 0.00
Received By jgomez Date 2016-09-15 Time 08:16 Sent To  
Notes
2016-09-15 08:54:57RESIDENTIAL (R3) CHANGE OF USE/ALTERATION, BUILDING
 REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
 ***NOTE:
 CONTRACTOR NEEDS TO UPDATE THE LICENSE STATUS WITH THE
 DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION
 (DBPR).
  
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
 NOTE: THIS MAY BE DONE LATER WHEN THE PERMIT IS READY
 TO BE PRINTED.
  
 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. R101.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 3- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE NEW EXTERIOR DOOR AND WINDOWS. SEC. R301.1
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 4- PROVIDE COMPLETE SPECIFICATIONS FOR THE WALL
 SHEATHING FASTENING AND EXTERIOR FINISH. SEC. R301.1
 FBC-RESIDENTIAL.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) WINDOW MULLIONS AS SHOWN ON PLANS. NOTE: CLEARLY
 SPECIFY MULLION SIZE TO BE USED TO VERIFY COMPLIANCE
 WITH THE CALCULATED DESIGN PRESSURES. SEC. R301.1
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 B) WINDOW PRODUCT APPROVAL NOA 14-0722.07 SUBMITTED IS
 FOR NON-IMPACT WINDOWS. THEREFORE NEED TO PROVIDE
 PRODUCT APPROVAL FOR HURRICANE SHUTTERS. AND PROVIDE
 COMPLETE INSTALLATION SCHEDULE. SEE CITY SAMPLE.
  
 C) NEW MASTER BEDROOM EXTERIOR SWING DOOR. PROVIDE
 FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPOND TO
 DRAWINGS SUBMITTED.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. NOTE: PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR ENGINEER TO LIST THE CURRENT FLORIDA
 PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED
 CONNECTOR.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ( NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-04-05 Cont ID  
Sent By vperez Date 2017-04-05 Time 08:42 Rev Time 0.00
Received By vperez Date 2017-04-05 Time 08:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-08-29 Cont ID  
Sent By mvaldes Date 2016-08-29 Time 12:26 Rev Time 0.00
Received By mvaldes Date 2016-08-29 Time 11:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-06-27 Cont ID  
Sent By jgomez Date 2017-06-27 Time 18:01 Rev Time 0.00
Received By jgomez Date 2017-06-26 Time 09:17 Sent To  
Notes
2017-06-27 09:18:05IMPACT FEES ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-05-04 Cont ID  
Sent By jgomez Date 2017-05-04 Time 11:42 Rev Time 0.00
Received By jgomez Date 2017-05-03 Time 07:42 Sent To  
Notes
2017-05-04 07:43:21MET WITH REGINALD. $75.00 PLAN REVIEW FEES WERE PAID.
 OK TO RESUME PLAN REVIEWS. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-25 Cont ID  
Sent By jgomez Date 2017-04-25 Time 16:09 Rev Time 0.00
Received By jgomez Date 2017-03-29 Time 09:59 Sent To  
Notes
2017-03-31 09:59:40R03

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-21 Cont ID  
Sent By tklarge Date 2016-09-21 Time 09:57 Rev Time 0.00
Received By tklarge Date 2016-08-19 Time 15:53 Sent To  
Notes
2016-08-19 15:53:33R06

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2017-06-27 Cont ID  
Sent By jgomez Date 2017-06-27 Time 17:04 Rev Time 0.00
Received By jgomez Date 2017-06-27 Time 17:04 Sent To  
Notes
2017-06-27 17:05:45$1,101.25 PAID. MU-2017-014548.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-05-04 Cont ID  
Sent By jgomez Date 2017-05-04 Time 08:48 Rev Time 0.00
Received By jgomez Date 2017-05-04 Time 08:48 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-09-15 Cont ID  
Sent By jgomez Date 2016-09-15 Time 08:55 Rev Time 0.00
Received By jgomez Date 2016-09-15 Time 08:55 Sent To  
Notes
2016-09-15 08:55:431- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-06-27 Cont ID  
Sent By jgomez Date 2017-06-27 Time 17:52 Rev Time 0.00
Received By jgomez Date 2017-06-27 Time 17:52 Sent To  
Notes
2017-06-27 17:59:44MECHANICAL REVIEW APPROVED WITH PROVISO: (NOTE: PROVIDE
 INFORMATION PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS)
 1- MASTER BEDROOM A/C PLAN NEEDS TO SHOW COMPLIANCE
 WITH THE BALANCED RETURN AIR AS REQUIRED BY SEC.
 M1602.4 FBC-RESIDENTIAL.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-05-04 Cont ID  
Sent By jgomez Date 2017-05-04 Time 11:16 Rev Time 0.00
Received By jgomez Date 2017-05-04 Time 11:16 Sent To  
Notes
2017-05-04 11:42:32RESIDENTIAL (R3) CHANGE OF USE/ALTERATION SECOND
 MECHANICAL REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 NOTE:
 MECHANICAL REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT PERMIT MAY BE ISSUED AND CONTRACTOR MAY
 SUBMIT THE REQUIRED ITEMS AFTER THE PERMIT IS ISSUED
 BUT BEFORE INSPECTIONS TO AVOID CONFLICTS/DELAYS. NOTE:
 REVISION FEES APPLY. CONTRACTOR TO RESPOND IN WRITING
 IF THE PROVISO OPTION IS PREFERRED AT THIS TIME.
  
 1- PLANS DON'T SPECIFY IF A/C EQUIPMENT IS EXISTING OR
 NEW. IT DOESN'T SPECIFY SIZE OF EQUIPMENT. PROVIDE
 EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY SEC.
 R403.6 FBC-ENERGY CONSERVATION, 5TH EDITION (2014) TO
 VERIFY COMPLIANCE WITH THE ADDITIONAL LOAD.
 RESPONSE: PLANS ARE NOT CLEAR IF THE EXISTING A/C UNIT
 NEEDS TO BE UPDATED TO SERVE THE ADDITIONAL LOAD.
 CLEARLY SPECIFY ON PLANS IF THE A/C UNIT WAS UPDATED
 AND SPECIFY ON PLANS EQUIPMENT LISTED IN THE EQUIPMENT
 SIZING CALCULATIONS SUBMITTED.
  
 2- A/C PLANS NEEDS TO SHOW COMPLIANCE WITH THE BALANCED
 RETURN AIR AS REQUIRED BY SEC. M1602.4 FBC-RESIDENTIAL,
 5TH EDITION (2014). NOTE: TAKE INTO CONSIDERATION THAT
 NEED TO COUNT ALL THE SUPPLY AIR GOING TO THE MASTER
 BEDROOM, INCLUDING THE SUPPLY AIR TO THE UTILITY AREA
 AND BATHROOM.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-04-25 Cont ID  
Sent By jgomez Date 2017-04-25 Time 16:09 Rev Time 0.00
Received By jgomez Date 2017-04-25 Time 16:09 Sent To  
Notes
2017-04-25 16:09:49PLAN REVIEW FEES WERE NOT PAID. PLAN REVIEW FEES NEED
 TO BE PAID AT TIME OF PERMIT APPLICATION SUBMITTAL.
 PLAN REVIEW WILL NOT BE DONE UNTIL FEES ARE PAID.
 CONTRACTOR TO ADVICE WHEN THE FEES ARE PAID TO RESUME
 PLAN REVIEW CYCLE.
 THANK YOU.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-09-19 Cont ID  
Sent By jgomez Date 2016-09-19 Time 17:22 Rev Time 0.00
Received By jgomez Date 2016-09-19 Time 17:21 Sent To  
Notes
2016-09-19 17:23:40RESIDENTIAL (R3) CHANGE OF USE/ALTERATION MECHANICAL
 REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- PLANS DON'T SPECIFY IF A/C EQUIPMENT IS EXISTING OR
 NEW. IT DOESN'T SPECIFY SIZE OF EQUIPMENT. PROVIDE
 EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY SEC.
 R403.6 FBC-ENERGY CONSERVATION, 5TH EDITION (2014) TO
 VERIFY COMPLIANCE WITH THE ADDITIONAL LOAD.
  
 2- A/C PLANS NEEDS TO SHOW COMPLIANCE WITH THE BALANCED
 RETURN AIR AS REQUIRED BY SEC. M1602.4 FBC-RESIDENTIAL,
 5TH EDITION (2014). NOTE: TAKE INTO CONSIDERATION THAT
 NEED TO COUNT ALL THE SUPPLY AIR GOING TO THE MASTER
 BEDROOM, INCLUDING THE SUPPLY AIR TO THE UTILITY AREA
 AND BATHROOM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-04-21 Cont ID  
Sent By gjohnson Date 2017-04-21 Time 14:53 Rev Time 0.00
Received By gjohnson Date 2017-04-21 Time 12:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-09-21 Cont ID  
Sent By tklarge Date 2016-09-21 Time 09:57 Rev Time 0.00
Received By tklarge Date 2016-09-21 Time 09:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2017-04-07 Time   Rev Time 0.00
Received By pgreilic Date 2017-04-07 Time 11:24 Sent To  
Notes
2017-04-07 11:25:01PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2016-09-19 Cont ID  
Sent By pgrehic Date 2016-09-19 Time 14:25 Rev Time 0.00
Received By pgreilic Date 2016-09-19 Time 14:25 Sent To  
Notes
***NONE***