Plan Review Details - Permit 16080793
Plan Review Stops For Permit 16080793
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-10-14 Cont ID  
Sent By jwitmer Date 2016-10-14 Time 08:09 Rev Time 0.00
Received By jwitmer Date 2016-10-14 Time 08:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-26 Cont ID  
Sent By jwitmer Date 2016-08-26 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2016-08-26 Time 06:25 Sent To  
Notes
2016-08-26 07:21:52BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080793
 ADD: 6000 N. FLAGLER DR.
 CONT: BLACK DIAMOND GENERAL CONTRACTING
 TEL: 561-746-3452
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. AUG. 26/2016
 ACTION: DENIED
  
 1) SHEET C5.01 NOW INDICATES A TOTAL OF 7 ACCESSIBLE
 PARKING SPACES. PLEASE REVIEW SECTION 208.2.4 OF
 THEACCESSIBILITY CODE WHERE VAN PARKING IS PROVIDED
 PURSUANT TO SECTION 502.2, FOR EVERY SIX OR FRACTION OF
 SIX PARKING SPACES REQUIRED BY 208.2 TO COMPLY WITH
 502, AT LEAST ONE SHALL BE A VAN PARKING SPACE
 COMPLYING WITH 502. SINCE THERE ARE 7 ACCESSIBLE
 PARKING SPACES THEN 2 ARE REQUIRED TO BE VAN
 ACCESSIBLE.
  
 2) PROVIDE SIGNAGE FOR ALL OF THE ACCESSIBLE PARKING
 STALLS AND VAN ACCESSIBLE STALLS SHALL HAVE SIGNAGE.
 PLEASE SHOW COMPLIANCE WITH ACCESS. CODE 502.6
 THE INTERNATIONAL SYMBOL OF ACCESSIBILITY COMPLYING
 WITH 703.7.2.1. SIGNS IDENTIFYING VAN PARKING SPACES
 WHEN REQUIRED BY 502.2 SHALL CONTAIN THE DESIGNATION
 ?VAN ACCESSIBLE.?
  
 3) PLEASE ALSO BE AWARE FOR THE VAN ACCESSIBLE PARKING
 SPACES FOR ANGLED PARKING SPACES NEED TO BE LAID OUT
 WITH THE ACCESS AISLES ON THE PASSENGER SIDE OF THE
 PARKING SPACES. SEE 2014 FBC-ACCESSIBILITY CODE
 502.3.4.LOCATION.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-10-20 Cont ID  
Sent By albarran Date 2016-10-20 Time 14:20 Rev Time 0.00
Received By albarran Date 2016-10-20 Time 14:05 Sent To I
Notes
2016-10-20 14:26:3710/20/16 I RECEIVED A LETTER FROM LEILA ROUADY
 ARCHITECT ASCERTAINING THE OCPD FOR THE MDP TO BE 800
 AMP AND NOT THE 600 AMP ORIGINALLY SHOWN ON PLANS.
2016-10-04 11:17:4110/4/16 BEFORE I FAIL THIS FOR IMPROPER SIZE OF OCP AT
 THE MDP I NEED TO DISCUSS THIS WITH THE DESIGN
 PROFESSIONAL I PLACED A CALL IN TO LEILA ROUADY AND AM
 WAITING TO HEAR BACK FROM HER. THE FILE IS ON MY DESK
 IN THE MEANTIME. MA

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-09-01 Cont ID  
Sent By albarran Date 2016-09-01 Time 13:21 Rev Time 0.00
Received By albarran Date 2016-09-01 Time 10:00 Sent To  
Notes
2016-09-01 13:22:12ELECTRICAL REVIEW:
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC)
  
 PROJECT NAME: FPL MANATEE LAGOON ADDITIONAL ITEMS
 JOB ADDRESS: 6000 N. FLAGLER
 DESCRIPTION: ADD HANDICAP RAMP, HANDICAP PARKING AND
 SIDEWALKS. INSTALL CAR CHARGING STATION
 MASTER PERMIT: 16080793
  
 AS DESCRIBED ABOVE, THE SCOPE OF THIS PERMIT INCLUDES
 THE INSTALLATION OF AN ELECTRIC VEHICLE CHARGING
 STATION WHICH IS FURTHER DESCRIBED ON SHEET C1.01 OF
 THE SUBMITTED PLANS. THE SUBMITTED PLANS REFER TO AN
 ELECTRICAL PAGE WHICH IS NOT INCLUDED IN THE PLAN SET.
 YOU WILL NEED TO PROVIDE THE FOLLOWING FOR A SUCCESSFUL
 ELECTRICAL REVIEW:
  
 1. PROVED AN ELECTRICAL SITE PLAN INDICATING THE
 LOCATION OF THE PROPOSED CHARGING STATION AND THE
 LOCATION OF THE POWER SOURCE FOR SAME.
 2. PROVIDE SPECS ON THE PROPOSED CHARGER TO DETERMINE
 THE DEMAND LOAD FOR THE EQUIPMENT.
 3. SUBMIT A RISER DIAGRAM INCLUDING LOAD CALCS TO
 ASCERTAIN THAT THE EXISTING SERVICE IS CAPABLE OF
 ACCEPTING THE ADDED LOAD.
 4. CONSIDER ALL THE REQUIREMENTS SET FORTH IN ARTICLE
 625 OF THE 2011 EDITION OF THE NEC
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2016-09-30 Cont ID  
Sent By mkhan Date 2016-09-30 Time 10:00 Rev Time 1.00
Received By mkhan Date 2016-09-30 Time 10:00 Sent To E
Notes
2016-09-30 12:20:41PROVISO USE NEW CITY STANDARD FOR PARKING STRIPING. SEE
 ATTACHED SHEET.
2016-09-30 10:07:35DELIVERED TO MANNYS DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-20 Cont ID  
Sent By albarran Date 2016-10-20 Time 14:26 Rev Time 0.00
Received By albarran Date 2016-09-30 Time 10:08 Sent To  
Notes
2016-10-20 14:29:0010/20/16 COMPLETED ELECTRICAL REVIEW AND PERMIT IS
 READY TO BE ISSUED. CONTRACTOR NOTIFIED VIA EMAIL. FILE
 SENT TO SMALL READY BIN B. MA

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-30 Cont ID  
Sent By skennedy Date 2016-09-30 Time 10:07 Rev Time 0.00
Received By skennedy Date 2016-08-18 Time 11:48 Sent To  
Notes
2016-08-19 11:51:26B02

Review Stop Z ZONING
Rev No 2 Status P Date 2016-10-13 Cont ID  
Sent By eschneid Date 2016-10-13 Time 11:25 Rev Time 0.25
Received By eschneid Date 2016-10-13 Time 11:25 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-08-25 Cont ID  
Sent By eshcneid Date 2016-08-25 Time 14:11 Rev Time 0.25
Received By eschneid Date 2016-08-25 Time 10:30 Sent To  
Notes
***NONE***