| 2016-08-20 06:32:11 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16080781 |
| | ADD: 1301 SUMMIT BLVD. (PANTHER HOLDING BUILDING) |
| | CONT: ROOFING UNLIMITED |
| | TEL: 561-842-0025 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. AUGUST 20/2016 |
| | ACTION: DENIED |
| | |
| | 1) ONLY ONE SET OF ROOFING PRODUCT APPROVALS WERE |
| | SUBMITTED. ) INFORMATIONAL 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1.3: PLEASE SUBMIT 2 OF ALL |
| | SURVEYS, PLANS, REPORTS, REVISIONS, PRODUCT APPROVALS |
| | AND OR SUBMITTALS FOR REVIEW FOR PERMIT. |
| | |
| | 2) THE SUBMITTED PRODUCT APPROVALS HAVE NOT BEEN |
| | REVIEWED BY THE DESIGNER OF RECORD. ADMINISTRATION |
| | 107.3.4 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL BE RESPONSIBLE FOR REVIEWING AND COORDINATING |
| | SUBMITTAL DOCUMENTS PREPARED BY OTHERS, INCLUDING |
| | PHASED AND DEFERRED SUBMITTAL ITEMS, FOR COMPATIBILITY |
| | WITH THE DESIGN OF THE BUILDING. THOSE PRODUCTS WHICH |
| | ARE REGULATED BY DCA RULE 9N-3SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 3) PLEASE NOTE THE DESIGNER OF RECORD THOMAS L. ADAMS |
| | P. E. LIST PRESSURES ON SHEET S0.1 FOR COMPONENTS AND |
| | CLADDING IN VULT AND VASD FOR ROOF ZONES 1-3. ROOF ZONE |
| | 3 IS LISTED AT A -89.1. THE SUBMITTED APPROVAL FL |
| | 14645-R2 METAL SALES MANUFACTURING CORP., 14645.1 2.5 |
| | CORRUGATED ROOFING IS ONLY GOOD FOR -86.0. SEE PAGE 2 |
| | OF 3 IN THE REPORT. PLEASE ALSO SEE PRODUCT LIMITATION. |
| | THE MAXIMUM FASTENER SPACING LISTED HEREIN SHALL NOT BE |
| | EXCEEDED. |
| | |
| | 4) THE CONTRACTOR DID NOT INDICATE WHICH SUB-SYSTEM OF |
| | THE POLYGLASS FL 5259-R24 WAS TO BE INSTALLED SEE |
| | ASSOCIATED PRESSURES FOR SUB-SYSTEMS. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |