Plan Review Details - Permit 16080744
Plan Review Stops For Permit 16080744
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2016-11-23 Cont ID  
Sent By tklarge Date 2016-11-23 Time 06:26 Rev Time 0.00
Received By tklarge Date 2016-11-23 Time 06:09 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2016-11-10 Cont ID  
Sent By tklarge Date 2016-11-10 Time 11:53 Rev Time 0.00
Received By tklarge Date 2016-11-10 Time 11:31 Sent To  
Notes
2016-11-10 11:41:301) PROVIDE THE BTU LOAD FOR EACH GAS APPLIANCE. I
 CANNOT DO A REVIEW WITHOUT THE BTU LOAD OF EACH
 APPLIANCE. THE ORIGINAL GAS DRAWING THAT HAS BEEN
 SUBMITTED IS SO SMALL IN SIZE IT IS ILLEGIBLE.
  
 2.) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G
 2407.
  
 3) SUBMIT COPIES OF THE SIZING TABLES YOU ARE USING FOR
 THE PE PIPE AND THE CSST OR REFERENCE THE SPECIFIC
 SIZING TABLES THAT ARE BEING USED ON THE PLANS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-08-22 Cont ID  
Sent By tklarge Date 2016-08-22 Time 04:33 Rev Time 0.00
Received By tklarge Date 2016-08-22 Time 04:09 Sent To  
Notes
2016-08-22 04:33:151.SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413. THE DRAWING THAT HAS BEEN SUBMITTED IS SO SMALL
 IN SIZE IT IS ILLEGIBLE.
  
 2.SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 3. TYPE OF GAS (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS.401.8
 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37) OR
 2014 FBC-RES. SEC. G2413.
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER
 OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS
 SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G
 2407.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS
 SECS. 502 THRU 505 OR 2014 FBC-RES. SEC.G2426.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-11-23 Cont ID  
Sent By tklarge Date 2016-11-23 Time 06:27 Rev Time 0.00
Received By tklarge Date 2016-11-22 Time 15:10 Sent To  
Notes
2016-11-22 15:10:39RESUB OF REVISION ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-10 Cont ID  
Sent By tklarge Date 2016-11-10 Time 11:53 Rev Time 0.00
Received By tklarge Date 2016-11-09 Time 11:53 Sent To  
Notes
2016-11-09 11:53:36RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-22 Cont ID  
Sent By tklarge Date 2016-08-22 Time 04:33 Rev Time 0.00
Received By tklarge Date 2016-08-18 Time 13:10 Sent To  
Notes
2016-08-19 13:11:16TKLARGE'S DESK