| 2016-08-22 07:00:21 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16080725 |
| | ADD: 4187 N. HAVERHILL/ SUITE # 506 |
| | CONT: ENTERPRISE CONTRACTORS, INC. |
| | TEL: 561-279-0133 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. AUGUST 21/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) THE PLANS SUBMITTED BY THE CONTRACTOR DOES NOT |
| | INDICATE WHO CREATED THE PLANS. PLEASE NOTE THE |
| | CONTRACTOR WHO DREW THE PLANS HAS TO HAVE THE LICENSE |
| | FOR THAT TRADE. ANOTHER WORDS THERE SHOWS NEW ELECTRIC |
| | WORK AS WELL AS NEW WORK COVERED UNDER THE CGC LISENCE. |
| | THE QUALIFIER FOR THE TRADE REPRESENTED ON THE PLANS |
| | THAT DREW THE PLANS AND IS GOING TO DO THE INSTALATION |
| | UNDER THE PROPOSED PERMIT CAN SIGN THERE NAME AND PRINT |
| | THEIR NAME AND ASSOCIATED LICENSURE. |
| | |
| | 107.3.4.3 CERTIFICATIONS BY CONTRACTORS AUTHORIZED |
| | UNDER THE PROVISIONS OF SECTION 489.115 FLORIDA |
| | STATUTES, SHALL BE CONSIDERED EQUIVALENT TO SEALED |
| | PLANS AND SPECIFICATIONS BY A PERSON LICENSED UNDER |
| | CHAPTER 471, FLORIDA STATUTES, OR CHAPTER 481 FLORIDA |
| | STATUTES, BY LOCAL ENFORCEMENT AGENCIES FOR PLANS |
| | REVIEW FOR PERMITTING PURPOSES RELATING TO COMPLIANCE |
| | WITH THE WIND-RESISTANCE PROVISIONS OF THE CODE OR |
| | ALTERNATE METHODOLOGIES APPROVED BY THE FLORIDA |
| | BUILDING COMMISSION FOR ONE AND TWO-FAMILY DWELLINGS. |
| | LOCAL ENFORCEMENT AGENCIES MAY RELY UPON SUCH |
| | CERTIFICATION BY CONTRACTORS THAT THE PLANS AND |
| | SPECIFICATIONS SUBMITTED CONFORM TO THE REQUIREMENTS OF |
| | THE CODE FOR WIND RESISTANCE. UPON GOOD CAUSE SHOWN, |
| | LOCAL GOVERNMENT CODE ENFORCEMENT AGENCIES MAY ACCEPT |
| | OR REJECT PLANS SEALED BY PERSONS LICENSED UNDER |
| | CHAPTERS 471,481 OR 489, FLORIDA STATUTES. |
| | |
| | 2) PLEASE NOTE PRODUCT LITERATURE SUBMITTED FOR WHISPER |
| | MAT CS IS JUST A SALES BROCHURE. THE CITY REQUIRES THE |
| | ACTUAL TEST REPORTS. PLEASE NOTE THIS PRODUCT IS FOR |
| | TILE NOT WOOD FLOORING PRODUCTS. WHISPER MAT ALSO MAKES |
| | A PRODUCT FOR WOOD INSTALATIONS CALLED WHISPER MAT HW |
| | FOR 6 INCH CONCRETE FLOORS. |
| | |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2014) |
| | FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| | HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES |
| | TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| | LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| | CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. |
| | |
| | 2C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |