Plan Review Details - Permit 16080719
Plan Review Stops For Permit 16080719
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-10-24 Cont ID  
Sent By jgomez Date 2016-10-24 Time 15:13 Rev Time 0.00
Received By jgomez Date 2016-10-24 Time 15:12 Sent To  
Notes
2016-10-24 15:26:46BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR HORIZONTAL
 SLIDING WINDOWS AS SHOWN ON PLANS (NOA 15-0619.06
 SUBMITTED IS FOR DOORS).
 2- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVAL. SEC. 107.3.4.1 CITY AMENDMENTS.
 3- WINDOW MULLIONS: CLEARLY MARK THE MULLION SIZE ON
 THE LOAD DESIGN CHART OF THE NOA PROVIDED TO VERIFY THE
 DESIGN PRESSURES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-09-15 Cont ID  
Sent By jgomez Date 2016-09-14 Time 16:31 Rev Time 0.00
Received By jgomez Date 2016-09-14 Time 15:09 Sent To  
Notes
2016-09-14 16:33:17RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- SPECIFY CARBON MONOXIDE ALARMS WITHIN ALL BEDROOMS
 AS REQUIRED BY SEC. R315 FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 3- CLARIFY WHY SUBMITTING NOA 12-0426.06 FOR ROOF
 COATING SYSTEMS. THIS PRODUCT MAY NO BE SUITABLE FOR
 THE EXISTING ROOF SYSTEM. SEE LIMITATIONS ON LAST PAGE
 OF NOA SUBMITTED. SEC. 107.2.1 CITY AMENDMENTS.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF UNDERLAYMENT: NOA 11-1011.05 SUBMITTED EXPIRED
 ON 03/03/15. PROVIDE CURRENT NOA.
  
 B) ROOFING TILES: FLORIDA PRODUCT APPROVAL FL7473-R5
 SUBMITTED IS FOR THE 2010 FBC. NEED TO PROVIDE PRODUCT
 APPROVAL FOR THE CURRENT 2014 CODE.
  
 C) FIXED WINDOWS SIZES AS SHOWN ON PLANS. NOA
 14-0515.11 SUBMITTED IS FOR SMALL MISSILE IMPACT. NEED
 LARGE MISSILE IMPACT PROTECTION AS REQUIRED BY SEC.
 R301.2.1.2 FBC-RESIDENTIAL.
  
 D) HORIZONTAL SLIDING WINDOWS AS SHOWN ON PLANS.
  
 E) USP AND SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 FRAMING PLANS AND DETAILS. FLORIDA PRODUCT APPROVAL
 NUMBERS SPECIFIED ON THE TRUSS ANCHOR SCHEDULE NEED TO
 BE UPDATED TO THE CURRENT 2014 CODE. AND, SPECIFY THE
 FLORIDA PRODUCT APPROVAL NUMBER NEXT TO EACH SIMPSON
 CONNECTORS SPECIFIED ON ALL OTHER DETAILS. OR, PROVIDE
 THE FLORIDA PRODUCT APPROVAL COVER PAGE AND PAGE
 SHOWING ALL THE SPECIFIED CONNECTORS.
  
 5- DESIGNER OF RECORD TO REVIEW/APPROVE ALL PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS. NOTE: PLEASE PLACE THE REVIEW STAMP ON THE
 FRONT OF THE PRODUCT APPROVAL NOT ON THE BACK OF THE
 FRONT PAGE. THIS IS REQUIRED FOR PROPER SCANNING OF
 DOCUMENTS FOR RECORDS RETENTION AS REQUIRED BY SEC.
 107.2.1.4 CITY AMENDMENTS.
  
 6- CLEARLY SPECIFY MULLION SIZE ON PRODUCT APPROVAL
 SUBMITTED TO VERIFY COMPLIANCE WITH THE CALCULATED
 DESIGN PRESSURES. SEC. R301.1 FBC-RESIDENTIAL.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON"T STAPLE OLD DRAWINGS. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-10-20 Cont ID  
Sent By mvaldes Date 2016-10-20 Time 09:29 Rev Time 0.00
Received By mvaldes Date 2016-10-19 Time 18:57 Sent To B
Notes
2016-10-20 09:29:36ROUTED TO JG.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-22 Cont ID  
Sent By mvaldes Date 2016-08-22 Time 13:40 Rev Time 0.00
Received By mvaldes Date 2016-08-22 Time 13:33 Sent To  
Notes
2016-08-22 13:51:14REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] PROVIDE EXISTING ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.FBC- 107.3.5.3
  
 2] ALL NEWLY INSTALLED RECEPTACLES SHALL BE TAMPER
 RESISTANT PER FBC-R SECTION E4002.14
  
 3] ALL NEWLY INSTALLED LUMINAIRES SHALL BE 75 % HIGH
 EFFICIENT AND IC RATED SEALED TO NOT COMPROMISE
 BUILDING THERMAL ENVELOPE IN ACCORDANCE WITH FBC-E
 SECTIONS 402.4.4 & 404.1

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-24 Cont ID  
Sent By jgomez Date 2016-10-24 Time 16:45 Rev Time 0.00
Received By jgomez Date 2016-10-13 Time 15:39 Sent To  
Notes
2016-10-13 15:39:29RESUB ROUTED TO AWOOTEN VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-19 Cont ID  
Sent By jgomez Date 2016-09-19 Time 14:36 Rev Time 0.00
Received By jgomez Date 2016-08-17 Time 14:55 Sent To  
Notes
2016-09-19 14:37:23LAST REVIEW DONE ON 09/17/16.
2016-08-17 14:55:22R10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2016-10-24 Cont ID  
Sent By jgomez Date 2016-10-24 Time 15:11 Rev Time 0.00
Received By jgomez Date 2016-10-24 Time 11:36 Sent To  
Notes
2016-10-24 15:12:15NO FEES. MU-2016-23845.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-09-14 Cont ID  
Sent By jgomez Date 2016-09-14 Time 17:56 Rev Time 0.00
Received By jgomez Date 2016-09-14 Time 17:55 Sent To  
Notes
2016-09-14 17:57:001- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2016-09-19 Cont ID  
Sent By jgomez Date 2016-09-19 Time 14:39 Rev Time 0.00
Received By jgomez Date 2016-09-19 Time 14:39 Sent To  
Notes
2016-09-19 14:40:15NO INFORMATION SUBMITTED FOR HVAC WORK.

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-09-17 Cont ID  
Sent By tklarge Date 2016-09-17 Time 06:52 Rev Time 0.00
Received By tklarge Date 2016-09-17 Time 06:43 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2016-10-24 Cont ID  
Sent By jgomez Date 2016-10-24 Time 18:25 Rev Time 0.00
Received By jgomez Date 2016-10-24 Time 18:24 Sent To  
Notes
2016-10-24 18:28:271) ROOF TILE ADHESIVE NOA 12-0228.18.
  
 2) CONCRETE TILE NOA 16-0314.08.
  
 3- UNDERLAYMENT NOA 15-0223.21

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-09-15 Cont ID  
Sent By jgomez Date 2016-09-15 Time 08:00 Rev Time 0.00
Received By jgomez Date 2016-09-15 Time 07:31 Sent To  
Notes
2016-09-15 08:01:581- CLARIFY WHY SUBMITTING NOA 12-0426.06 FOR ROOF
 COATING SYSTEMS. THIS PRODUCT MAY NO BE SUITABLE FOR
 THE EXISTING ROOF SYSTEM. SEE LIMITATIONS ON LAST PAGE
 OF NOA SUBMITTED. SEC. 107.2.1 CITY AMENDMENTS.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF UNDERLAYMENT: NOA 11-1011.05 SUBMITTED EXPIRED
 ON 03/03/15. PROVIDE CURRENT NOA.
  
 B) ROOFING TILES: FLORIDA PRODUCT APPROVAL FL7473-R5
 SUBMITTED IS FOR THE 2010 FBC. NEED TO PROVIDE PRODUCT
 APPROVAL FOR THE CURRENT 2014 CODE.
  
 3- DESIGNER OF RECORD TO REVIEW/APPROVE ALL PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS. NOTE: PLEASE PLACE THE REVIEW STAMP ON THE
 FRONT OF THE PRODUCT APPROVAL NOT ON THE BACK OF THE
 FRONT PAGE. THIS IS REQUIRED FOR PROPER SCANNING OF
 DOCUMENTS FOR RECORDS RETENTION AS REQUIRED BY SEC.
 107.2.1.4 CITY AMENDMENTS.
  

Review Stop Z ZONING
Rev No 2 Status N Date 2016-10-18 Cont ID  
Sent By awooten Date 2016-10-18 Time 10:20 Rev Time 0.00
Received By awooten Date 2016-10-18 Time   Sent To E
Notes
2016-10-14 14:09:35ALANA WOOTEN

Review Stop Z ZONING
Rev No 1 Status P Date 2016-09-14 Cont ID  
Sent By awooten Date 2016-09-14 Time 09:12 Rev Time 0.00
Received By awooten Date 2016-09-12 Time 08:33 Sent To  
Notes
***NONE***