| 2016-09-14 16:33:17 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| | COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) |
| | FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED |
| | PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY |
| | IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| | CODE. |
| | |
| | 2- SPECIFY CARBON MONOXIDE ALARMS WITHIN ALL BEDROOMS |
| | AS REQUIRED BY SEC. R315 FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). |
| | |
| | 3- CLARIFY WHY SUBMITTING NOA 12-0426.06 FOR ROOF |
| | COATING SYSTEMS. THIS PRODUCT MAY NO BE SUITABLE FOR |
| | THE EXISTING ROOF SYSTEM. SEE LIMITATIONS ON LAST PAGE |
| | OF NOA SUBMITTED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) ROOF UNDERLAYMENT: NOA 11-1011.05 SUBMITTED EXPIRED |
| | ON 03/03/15. PROVIDE CURRENT NOA. |
| | |
| | B) ROOFING TILES: FLORIDA PRODUCT APPROVAL FL7473-R5 |
| | SUBMITTED IS FOR THE 2010 FBC. NEED TO PROVIDE PRODUCT |
| | APPROVAL FOR THE CURRENT 2014 CODE. |
| | |
| | C) FIXED WINDOWS SIZES AS SHOWN ON PLANS. NOA |
| | 14-0515.11 SUBMITTED IS FOR SMALL MISSILE IMPACT. NEED |
| | LARGE MISSILE IMPACT PROTECTION AS REQUIRED BY SEC. |
| | R301.2.1.2 FBC-RESIDENTIAL. |
| | |
| | D) HORIZONTAL SLIDING WINDOWS AS SHOWN ON PLANS. |
| | |
| | E) USP AND SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | FRAMING PLANS AND DETAILS. FLORIDA PRODUCT APPROVAL |
| | NUMBERS SPECIFIED ON THE TRUSS ANCHOR SCHEDULE NEED TO |
| | BE UPDATED TO THE CURRENT 2014 CODE. AND, SPECIFY THE |
| | FLORIDA PRODUCT APPROVAL NUMBER NEXT TO EACH SIMPSON |
| | CONNECTORS SPECIFIED ON ALL OTHER DETAILS. OR, PROVIDE |
| | THE FLORIDA PRODUCT APPROVAL COVER PAGE AND PAGE |
| | SHOWING ALL THE SPECIFIED CONNECTORS. |
| | |
| | 5- DESIGNER OF RECORD TO REVIEW/APPROVE ALL PRODUCT |
| | APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| | AMENDMENTS. NOTE: PLEASE PLACE THE REVIEW STAMP ON THE |
| | FRONT OF THE PRODUCT APPROVAL NOT ON THE BACK OF THE |
| | FRONT PAGE. THIS IS REQUIRED FOR PROPER SCANNING OF |
| | DOCUMENTS FOR RECORDS RETENTION AS REQUIRED BY SEC. |
| | 107.2.1.4 CITY AMENDMENTS. |
| | |
| | 6- CLEARLY SPECIFY MULLION SIZE ON PRODUCT APPROVAL |
| | SUBMITTED TO VERIFY COMPLIANCE WITH THE CALCULATED |
| | DESIGN PRESSURES. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. DON"T STAPLE OLD DRAWINGS. SUBMITT OLD |
| | DRAWINGS FOR REFERENCE. |
| | |