Plan Review Details - Permit 16080680
Plan Review Stops For Permit 16080680
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-08-18 Cont ID  
Sent By cthroop+ Date 2016-08-18 Time 12:39 Rev Time 0.00
Received By cthroop Date 2016-08-18 Time 12:01 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-08-18 Cont ID  
Sent By lmarchan Date 2016-08-25 Time 08:31 Rev Time 0.00
Received By mvaldes Date 2016-08-18 Time 08:29 Sent To B
Notes
2016-08-18 09:14:32REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 PASSED WITH THE FOLLOWING PROVISO
  
 1) NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT
 LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR
 CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE
 THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT
 REQUIRING SERVICING.
 THE LIGHTING OUTLET SHALL BE PROVIDED AT OR NEAR THE
 EQUIPMENT REQUIRING SERVICING. [ FOR THE ATTIC ENTRANCE
 BY HVAC ]

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-08-22 Cont ID  
Sent By gjohnson Date 2016-08-22 Time 11:54 Rev Time 0.00
Received By gjohnson Date 2016-08-22 Time 11:54 Sent To  
Notes
2016-08-22 11:55:03GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-07 Cont ID  
Sent By lmarchan Date 2016-09-14 Time 09:44 Rev Time 0.00
Received By lmarchan Date 2016-09-06 Time 15:00 Sent To I
Notes
2016-09-06 15:01:20JVALIDO'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-25 Cont ID  
Sent By lmarchan Date 2016-08-25 Time 08:31 Rev Time 0.00
Received By lmarchan Date 2016-08-16 Time 08:52 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2016-09-14 Cont ID  
Sent By skennedy Date 2016-09-14 Time 12:47 Rev Time 0.00
Received By skennedy Date 2016-09-14 Time 12:47 Sent To  
Notes
2016-09-14 12:47:30THERE IS NO CHANGE TO THE MECHANICAL PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-09-06 Cont ID  
Sent By jvalido Date 2016-09-06 Time 17:33 Rev Time 0.00
Received By jvalido Date 2016-09-06 Time 16:41 Sent To  
Notes
2016-09-06 17:18:26CORRECTIONS REQUESTED ON PREVIOUS REVIEW WERE NOT
 ADDRESSED. PAGE TWO OF THE SUBMITTED BUILDING PLANS
 SHOWS THE AHU IN A DIFFERENT LOCATION THAN THE
 MECHANICAL PLANS. CLARIFY LOCATION.
  
 IF AHU IS IN A DIFFERENT LOCATION THAN PREVIOUSLY,
 ADDRESS REQUIRED CORRECTIONS DATED 8/24/2016.
  
 CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE MECHANICAL PLANS.
 (2) SHOW WHERE THE AHU WAS AND ALL NEW DUCTWORK NEEDED
 TO RECONFIGURE AT NEW AHU LOCATION.
  
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-24 Cont ID  
Sent By jvalido Date 2016-08-24 Time 18:27 Rev Time 0.00
Received By jvalido Date 2016-08-24 Time 18:25 Sent To  
Notes
2016-08-24 18:27:27CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE MECHANICAL PLANS.
 (2) SHOW WHERE THE AHU WAS AND ALL NEW DUCTWORK NEEDED
 TO RECONFIGURE AT NEW AHU LOCATION.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-08-22 Cont ID  
Sent By gearl Date 2016-08-22 Time 11:52 Rev Time 0.00
Received By gjohnson Date 2016-08-22 Time 11:52 Sent To  
Notes
***NONE***